In the excitation system of synchronous generators, the stability of the voltage regulator (AVR) directly determines the quality and dynamic response capability of the output voltage of the generator set. Basler AVC63-12 and AVC125-10, as two classic analog automatic voltage regulators, are widely used in marine, industrial, and emergency generator sets due to their wide frequency adaptation range (50-400 Hz), fast response (<4 ms), and rich programmable functions (V/Hz slope, over excitation shutdown, and parallel sag compensation). However, on-site engineers often encounter issues such as voltage failure, oscillation, and uneven distribution of reactive power during the initial operation or replacement of old AVRs. This article is based on the complete technical manual AVC63-12/AVC125-10, systematically summarizing its key technical parameters, installation and wiring specifications, refined adjustment methods, and typical troubleshooting processes, providing operational technical guidance for the maintenance and renovation of generator sets.
Comparison of Product Positioning and Core Specifications
AVC63-12 and AVC125-10 are both self exciting voltage regulators that generate error signals by detecting the generator terminal voltage and comparing it with an internal reference to control the excitation field current and maintain a constant output voltage. The main difference between the two lies in the power level:
Parameter AVC63-12 AVC125-10
Continuous output of 12 A @ 63 Vdc, 10 A @ 125 Vdc
10 second strong excitation output 24 A @ 125 Vdc 20 A @ 250 Vdc
Minimum magnetic field resistance 5.25 Ω 12.5 Ω
Power input voltage range 90-153 Vac 180-264 Vac
Maximum continuous power consumption 1092 VA 1750 VA
Both support single-phase or three-phase power input, with a frequency adaptation range of 50-400 Hz (distinguished by model suffix), and have automatic residual voltage excitation function (AVC63-12 not less than 6 Vac, AVC125-10 not less than 12 Vac). They can also be equipped with external accessories to achieve advanced functions such as remote voltage regulation, power factor control, and excitation limitation.
Selection prompt: If the magnetic field resistance of the exciter is lower than 12.5 Ω, AVC63-12 must be selected; If the system voltage is 120V level, select AVC63-12; Choose AVC125-10 for 240V level.
Installation and mechanical precautions
The regulator adopts a fully enclosed plastic shell with a high level of protection and can be installed in any direction (it is recommended to install vertically for heat dissipation). The external dimensions are shown in Figure 5 (width approximately 162 mm, height approximately 162 mm, depth not specified but lightweight), weighing approximately 1.1 kg. M8 or equivalent bolts should be used during installation, and the maximum tightening torque should not exceed 65 in lb (7.34 N · m) to prevent the shell from breaking.
Environmental requirements:
Working temperature: -40 ° C to+70 ° C
Storage temperature: -40 ° C to+70 ° C
Maximum humidity: 95% (no condensation)
The installation location should be away from severe vibration sources, but the regulator has passed 20 G impact and 4.5 G (18-2000 Hz) vibration tests and is suitable for the vast majority of industrial environments.

Terminal definition and wiring specifications
The regulator is divided into two sets of terminals: upper layer (control/signal) and lower layer (power/sensing). Table 1 lists them in detail:
Upper terminal (control side)
CH GND: Chassis grounding (must be reliably grounded)
Terminals 2 and 3: Accessory input (± 3 Vdc signal from SCP 250 or EL 200, positive voltage decrease set point, negative voltage increase set point)
Terminals 4 and 7: Internal voltage regulation (4-7 short circuit enable panel VLT ADJ, can be remotely adjusted by external 10k Ω potentiometer after removal)
Terminals 5, 5A, 6: CT input (5 is 1A CT, 5A is 5A CT, 6 is common terminal)
Terminal 6a: Function selection common terminal
Terminal 8: Connect 6a and select 1 PU V/Hz slope (if not connected, select 2 PU slope)
Terminal 9: Connect 6a and select three-phase voltage detection (otherwise it is single-phase)
Lower level terminal (power/sensing side)
20. 22, 24: Voltage detection input (phases A, B, C)
26, 28, 30: Power input (single-phase connected to 26 and 30, three-phase connected to 26-28-30)
F1, F2: Excitation output (F1 positive, F2 negative), be careful not to reverse polarity.
Key grounding rules: The CT secondary side must be grounded at only one point, and the grounding point should be as close to the CT as possible. If multiple CTs are interconnected, only one of them can be grounded on the secondary side to avoid circulating interference caused by multiple grounding points.
On site adjustment steps and fine calibration
4.1 Field Flashing
When it is first put into operation or the residual magnetism of the generator is insufficient, the voltage cannot be established. If the voltage between terminals 26/28/30 of AVC63-12 is detected to be lower than 6 Vac (or AVC125-10 is lower than 12 Vac), it is necessary to perform magnetization in the shutdown state:
Use an ungrounded DC power supply (≤ 24 Vdc) with a series current limiting resistor (1 Ω per volt, power ≥ 1W/2), for example, a 24V power supply with a 24 Ω/24W resistor.
Connect the positive pole to F1 and the negative pole to F2, and turn on the power for about 10 seconds before disconnecting.
If the first attempt is unsuccessful, check if the power polarity is correct (positive to F1, negative to F2).
It is strictly prohibited to magnetize the generator while it is rotating, otherwise it may damage the regulator.
4.2 Voltage Setting (VLT ADJ)
Short circuit terminals 4 and 7 to make panel VLT ADJ effective. Rotate clockwise to increase the output voltage.
If remote voltage regulation is required: Remove the 4-7 short circuit, connect a 10k Ω (2W) potentiometer between 6a and 7, and turn the panel VLT ADJ clockwise to the maximum. At this point, the resistance of the external potentiometer increases, and the output voltage rises.
4.3 Stability Adjustment (STB)
Stability (STB) potentiometer is used to suppress voltage oscillation ("traveling car"):
Use an oscilloscope to monitor the voltage of the generator.
Under no-load conditions, rotate the STB counterclockwise until the voltage begins to oscillate slightly, and then rotate clockwise until it reaches a stable point.
Add various loads to verify dynamic response. If the response is too slow, it can be slightly counterclockwise; If oscillating, then clockwise. This adjustment needs to be repeated until there is no voltage overshoot or oscillation when switching between full load and no-load.
4.4 Frequency compensation (UF KNEE and slope selection)
Frequency compensation (also known as underfrequency turning) is used to automatically reduce the output voltage according to the V/Hz curve when the speed of the prime mover decreases, in order to prevent magnetic circuit saturation.
Turning point setting: At the rated frequency, first adjust UF KNEE counterclockwise, adjust VLT ADJ to make the voltage at the rated value, then rotate UF KNEE clockwise until the voltage starts to drop, and then counterclockwise adjust it back to the rated value - this point is the turning frequency (usually slightly lower than the rated frequency).
Slope selection: When terminal 8 is not connected to 6a, it is 2 PU V/Hz (steep slope); When connected to 6a, it is 1 PU V/Hz (gentle slope). The 400 Hz model is also applicable, and the actual curve shape is shown in Figure 1 and Figure 2.
4.5 Factory Calibration (FAC CAL) - Use with Caution
This potentiometer has been calibrated at the factory and users generally do not touch it. If there is an unexpected disturbance, the following steps can be taken to restore it:
Rotate FAC CAL counterclockwise to the end, and rotate the external pressure regulator (if any) clockwise to the end.
Slowly rotate FAC CAL clockwise until the output voltage reaches the required maximum value, at which point the factory calibration point is restored.
Parallel sag and line voltage drop compensation
5.1 Parallel Droop
When multiple generators are running in parallel, to avoid reactive power circulation, it is necessary to introduce reactive power droop characteristics. Detect the load current through CT (terminal 5/5A) and adjust the droop amount (0-10% adjustable) through DRP potentiometer. Increase the sag clockwise to make the reactive power distribution more balanced.
5.2 Line Drop Compensation (LDC)
When there is a long transmission line between the generator and the load, the impedance of the line will cause the voltage at the load end to be lower than that at the generator end. LDC connects CT in reverse (i.e. CT polarity reversed) and adjusts DRP to make the regulator "sense" the line voltage drop and increase the generator voltage for compensation. Note: LDC only compensates for voltage drop caused by line inductance and reactive load components, and does not compensate for resistive voltage drop.

Optional modules and extended functions
Remote voltage adjustment: external 10k Ω potentiometer (see 4.2).
Excitation limiter (EL 200): Provides rapid overexcitation limitation, and when the excitation current exceeds the set value, sends a signal to the regulator accessory input (terminals 2, 3) to lower the set point.
Power factor/reactive power controller (SCP 250): During grid connected operation, DC signals are injected through terminals 2 and 3 to adjust the regulator according to the set power factor or reactive power.
Current boost system (CBS 212): Provides additional excitation current boost to help clear faults or start large motors when voltage drops due to motor start-up or short circuit faults.
Manual voltage control (MVC-112): serves as a backup manual excitation control in case of regulator failure.
Surge current suppression module (ICRM-15): When there is already voltage on the power supply side, it can be connected to a regulator to suppress the instantaneous surge current when powered on.
Start trial operation and functional verification
According to the recommended startup process in the manual:
Check all wiring and confirm that there are no errors before starting the prime mover to the rated speed.
If the voltage is not established, perform magnetization operation and reset the overexcitation shutdown circuit (power off for 1 minute).
Slowly adjust VLT ADJ to rated voltage.
Check stability: Increase or decrease load, observe voltage fluctuations and recovery time.
Adjust UF KNEE to activate the under frequency protection at the correct turning point.
If running in parallel, add droop CT and adjust DRP to balance reactive power distribution.
Simple functional test (detached from the generator, using the test circuit shown in Figure 9):
Apply the corresponding test voltage to the regulator (see Table 2, for example, AVC63-12A1 is 120Vac/50Hz), and connect the bulb and resistor in series as the load between F1-F2.
Rotate VLT ADJ counterclockwise to the bottom, the light bulb should turn off; Rotate clockwise until the light bulb lights up, then retract to the critical point of extinguishing, indicating that the regulator is basically normal.
Common fault phenomena and troubleshooting logic
Possible causes and solutions for malfunction phenomena
Voltage cannot establish residual magnetism deficiency or polarity reversal; Overexcitation shutdown action; Excitation circuit open circuit shutdown magnetization; Power off for 1 minute to reset; Check F1/F2 wiring and exciter field resistance
The voltage is too high or too low, and the VLT ADJ adjustment is ineffective. The remote voltage regulator potentiometer is wired incorrectly or short circuited; FAC CAL was mistakenly activated to confirm 4-7 short circuit status; Check the external voltage regulation circuit; Recalibrate FAC CAL
Voltage oscillation (hunting) STB setting too small (too much counterclockwise); The prime mover governor is unstable. Rotate the STB clockwise until it stabilizes; Check the prime mover speed regulator
Uneven distribution of reactive power during parallel operation, drooping CT polarity reversal or inconsistent DRP setting; Check CT polarity for mismatched sag coefficients of each machine (terminal 5/5A); Unified adjustment of DRP to make the reactive current of each machine proportional to the same load
When the load changes, the voltage drops severely and the frequency inflection point is set too high; Activate the excitation limiter to lower the UF KNEE turning point; Check the EL 200 setting value
External voltage regulation is ineffective. The external potentiometer wiring is incorrect or the resistance value does not match. Confirm that terminals 6a-7 are connected to 10k Ω, and the panel VLT ADJ has been turned clockwise to the maximum
Maintenance and spare parts replacement suggestions
Regular inspection: Check the wiring terminals for looseness every six months, remove dust, and measure whether the excitation voltage and current between F1-F2 are within the rated range.
Overexcitation shutdown test: It can simulate excitation overcurrent and verify whether the shutdown action time conforms to the curves in Figure 3 and Figure 4 (AVC63-12 shuts off in about 10 seconds at 125Vdc and about 1 second at 210Vdc).
Replacement selection: If the original system uses the earlier AVC63-7 or AVC125-7, this new model can be directly replaced, but the input voltage range and output capacity need to be checked. If PMG (permanent magnet generator) excitation is used on site, it is necessary to confirm that the power input comes from PMG rather than the main output. This regulator supports PMG input.
Storage: For long-term backup, it is recommended to power on every six months to maintain the performance of the internal electrolytic capacitor.
