Drag OUT4 from I/O → Output Objects, connect the 50-3 Pickup output to the OUT4 input, and save the logic.
Name OUT4 "50-3 Pickup" in "Programmable Output" → "Contact Output".
Upload logic and settings to device (Communication → Upload Settings and Logic). After completion, when the current exceeds 5.62A, OUT4 will close and Trip action will trip through OUT1.

4. Application and verification of key protection functions
BE1-11f provides a variety of protective components, and correct setting and verification are key to preventing misoperation or refusal to move.
4.1 Overcurrent protection (50/51)
Instantaneous overcurrent (50): used for quick break, can be set as phase, neutral, negative sequence, grounded, or unbalanced mode. Pay attention to directionality (forward/reverse) and use 67 directional components.
Inverse time overcurrent (51): Provides multiple standard curves (CO, IAC, etc.) and user-defined curves. When setting up, attention should be paid to matching the time dial with the curve type and coordinating with downstream equipment.
Verification method: Use a relay protection tester to apply current, observe the status of Pickup and Trip, and check if the action time is consistent with the curve.
4.2 Voltage Protection (27/59)
Undervoltage (27P) and overvoltage (59P): Supports "1/3", "2/3" or "3/3" logic, and can set inverse or fixed time limits.
Auxiliary undervoltage/overvoltage (27X/59X): can monitor positive sequence, negative sequence, zero sequence (3V0) or Vx fundamental/third harmonic, suitable for ground fault detection or generator protection.
Verification: Apply three-phase unbalanced voltage or boost voltage to verify the action threshold and delay.
4.3 Frequency Protection (81)
Over/Under Frequency and Frequency Change Rate (ROCOF): Used for islanding detection and low-frequency load shedding. Positive and negative change rate directions can be set separately.
Verification: Simulate deviation using a frequency source and observe the action time. Pay attention to the Voltage Inhibit function, which can be locked at low voltage to prevent misoperation.
4.4 Circuit Breaker Failure Protection (50BF)
Using the "52BFI" external start or internal overcurrent start, if the current still exists after a delay, a re trip signal will be sent.
It is necessary to correctly configure the "Breaker Status" logic (from the auxiliary contact of 52a) to ensure that the failure logic is only valid when the circuit breaker is closed.
Verification: The current still exists after the simulated circuit breaker trips, check the delay and outlet action.
4.5 Synchronization Check (25)
Compare the amplitude, angle, and slip frequency of the compared voltage with the auxiliary voltage. Angle Compensation is used to compensate for PT phase differences (such as star delta transformation).
Output 25 (synchronous) and 25VM (voltage monitoring) can participate in reclosing or manual closing logic.
5. Fault report and event record analysis
The powerful fault recording and sequence event recording (SER) of BE1-11f is the core tool for accident analysis.
5.1 Fault triggering logic
Trip expression: Define a trip trigger used to initiate target recording and light up the Trip LED.
Pickup expression: defines the startup fault recording and timing fault clearing time.
Logic expression: Used for external triggering of waveform recording (such as switch displacement).
The default logic will directly connect the protected component output to these expressions, which can be customized by the user.
5.2 Viewing Fault Reports
You can view the fault summary (including time, type, fault phase, current/voltage value, distance, etc.) through the "Metering Explorer" → "Reports" → "Fault Records" of BESTCOMSPlus.
Click on a single fault to download the COMTRADE format waveform file, using BESTwave ™ Software analysis of waveforms.
5.3 Sequential Event Recording (SER)
Record over 1000 events with time stamps (resolution 1ms), covering input/output status, alarms, targets, etc.
CSV files can be viewed or exported through "Reports" → "Sequence of Events".
5.4 Target Reset and LED Status
After the protective action, the Trip LED will remain sealed until the target is reset. You can press the Reset button on the front panel (if security permissions allow) or reset the TARGETRESET component logic through BEST logicPlus.
If the target cannot be reset, check the security settings (whether the Unsecured Access Level allows control operations).

6. Common troubleshooting and solutions
6.1 Communication connection failure
USB unrecognized: Check if the driver is installed correctly (if prompted, manually point to C: Program Files Basler Electric BESTCOMSPlus USBDeviceDrivers ). Reconnect the USB or restart the PC.
Ethernet connection timeout: Confirm that the device IP address is on the same subnet as the PC and that 'Enable Web Pages' is checked. You can view/modify the IP address through the front panel "Settings → Communication → Ethernet".
Multi port conflict: There can only be one Ethernet connection at a time, ensuring that no other software is occupying it.