Welcome to the Industrial Automation website!

NameDescriptionContent
XING-Automation
E-mail  
Password  
  
Forgot password?
  Register
当前位置:

Basler BE1-47N Relay Field Setting and Testing Guide

F: | Au:FANS | DA:2026-06-24 | 313 Br: | 🔊 点击朗读正文 ❚❚ | Share:


Practical Guide for Field Application and Setting Test of Basler BE1-47N Voltage Phase Sequence Relay

In industrial power distribution and motor protection systems, voltage asymmetry, phase sequence errors, and phase loss operation are common causes of equipment damage and production interruptions. The BE1-47N voltage phase sequence relay from Basler Electric provides a reliable monitoring and protection solution for such issues. This article combines the actual technical data of this type of relay and systematically sorts out its selection points, installation wiring, panel operation, parameter setting, and verification testing methods from the perspective of on-site application, providing engineering and technical personnel with a directly referenceable practical document.


Product positioning and typical application scenarios of BE1-47N

BE1-47N belongs to voltage phase sequence relays, whose core function is to respond to negative sequence voltage (V2) in three-phase systems. The occurrence of negative sequence voltage often indicates asymmetric faults or incorrect wiring in the system, such as phase loss, reversed phase sequence, severe three-phase load imbalance, etc. This relay not only detects these abnormalities, but also has built-in overvoltage and undervoltage protection functions (optional), allowing it to provide protection in various scenarios.

Typical applications include:

The phase sequence protection and phase loss protection of the motor prevent the motor from starting or running in case of phase sequence error or phase loss;

The voltage and phase sequence verification in the automatic transfer switch (ATS) scheme ensures the correct phase sequence before the backup power supply is connected;

Grid connection or line switching protection for generators, transformers, and synchronous phase-shifting cameras;

Phase sequence and voltage imbalance monitoring of power capacitor banks.

It is worth noting that BE1-47N has high sensitivity in detecting negative sequence voltage and can identify negative sequence voltage components as low as 2%. In industrial power supply systems, a negative sequence voltage of 1% to 2% is within the normal range. Once it significantly increases, it usually indicates abnormal power supply. If not dealt with in a timely manner, it may cause serious production problems.


Key selection points and model code interpretation

The model code of BE1-47N includes key information such as voltage level, frequency, output configuration, timing characteristics, control power supply, target indication mode, and housing form of the equipment. Correctly understanding the model code is the first step in selecting a model.

Model code example: E3FE1PA1R0F

The disassembly is as follows:

E: Three phase line voltage detection method;

3: The rated voltage is 120 Vac and the frequency is 60 Hz;

F: Equipped with two output relays, the contact form is normally open (NO);

E1: Negative sequence voltage protection adopts timed delay characteristics;

P: The auxiliary power supply is 125 Vdc or 120 Vac;

1: Built in 1 internal incentive target indicator;

1: Contains instantaneous undervoltage components;

R: Contains instantaneous overvoltage components;

0: No auxiliary output relay;

F: Semi embedded installation shell.

When selecting, special attention should be paid to whether the voltage level and frequency match the on-site system (such as 120 Vac/60 Hz or 208 Vac/60 Hz), and whether undervoltage and overvoltage protection functions are required. If normally closed contacts or additional signal contacts are required on site, they should also be clearly selected in the model.

Installation method and structural dimensions

BE1-47N adopts S1 type chassis, supporting two installation methods: semi embedded installation and protruding installation. Due to the use of solid-state circuit design, the relay itself does not need to be installed vertically, and the installation angle can be flexibly selected according to the cabinet space.

Key installation dimensions (taking semi embedded as an example):

The size of the panel opening should refer to the panel cutting diagram in the manual;

The depth of the chassis is about 141.3 mm (calculated from the back of the panel);

When installed in a protruding manner, there is an increased demand for rear space.

Special attention should be paid to grounding issues during installation: the relay housing must be reliably connected to the ground through a copper wire of not less than 12 AWG, and it is recommended that each device be independently led to the grounding busbar to avoid interference caused by shared grounding wires.


Precautions for Electrical Connections and Wiring

The wiring of BE1-47N mainly includes voltage detection input, auxiliary power input, output contacts, and status indication contacts.

Voltage detection input:

According to different models, the detection input is divided into 120 Vac, 208 Vac (60 Hz) or 100 Vac, 173 Vac (50 Hz). In typical wiring, the three-phase voltages A, B, and C are respectively connected to the corresponding terminals on the back of the relay. The manual clearly states that the relay is sensitive to phase sequence, and all wiring diagrams and settings are based on ABC positive phase sequence. If the actual phase sequence on site is ACB, the phase sequence needs to be adjusted or the test values need to be recalculated.

Auxiliary power supply:

The power supply types include DC (such as 24 Vdc, 48 Vdc, 125 Vdc, 250 Vdc) and AC (such as 120 Vac, 240 Vac). The power terminals have no polarity requirements, but it is necessary to ensure that the voltage is within the allowable range. When the power is normal, the red LED indicator on the panel lights up.

Output contact:

The main output contact is used for tripping circuits and can be selected as normally open or normally closed. The auxiliary output contact can be used for signal remote transmission or alarm. If a current type target indicator is selected, it is necessary to ensure that the tripping circuit current is not less than 200 mA, otherwise the target indicator may not function properly.

Suggestions for wiring construction:

Unless otherwise specified, the wire diameter should not be less than 14 AWG;

If the output contact is used to drive the external relay coil, it is recommended to parallel reverse diodes at both ends of the coil to suppress EMI interference generated during power failure;

If insulation withstand voltage testing is required, it is necessary to first unplug the connection plug and extract the relay from the chassis to avoid damaging the internal circuit.


Panel controls and operating instructions

The layout of the BE1-47N panel is clear, with operation controls concentrated on the front for easy on-site tuning and status viewing.

The main controls include:

Negative sequence voltage setting dip switch: 16 positions, corresponding to negative sequence voltage setting values of 2% to 32%, with an interval of 2% between each position. The panel is accompanied by a comparison table, indicating the percentage values corresponding to grades A to S.

Undervoltage setting dip switch (optional): The setting range is 2% to 32% below the rated voltage.

Overvoltage setting toggle switch (optional): The setting range is 2% to 32% higher than the rated voltage.

Delay setting dip switch: For timed characteristics, it can be set from 0.1 seconds to 9.9 seconds with a step size of 0.1 seconds; For the inverse time characteristic, the range is set from 01 to 99.

Target reset button: used to manually reset the target indicator that has been activated.

Output test hole: A non-conductive rod can be inserted into the panel hole to manually trigger the output relay for circuit inspection.

Status indication:

Power indicator light: green or red LED, lit up to indicate that the auxiliary power supply is normal.

Pick up indicator lights for negative sequence, undervoltage, and overvoltage protection units: red LED, which lights up when the corresponding power exceeds the set value, indicating a delayed or instantaneous action state.

Target indicator: Electronic locking type red LED, which remains lit when the output relay is activated until manually reset.

Parameter tuning methods and principles

Reasonable setting is a prerequisite for relays to perform protective functions. The following are the principles for setting various protections.

Negative sequence voltage setting:

The negative sequence voltage in normal industrial power supply is usually between 1% and 2%. It is recommended to set the initial setting value to 4%~6% to avoid frequent misoperation caused by normal system imbalance.

If the motor load is heavy, the setting value can be appropriately increased, but should not exceed 10%, otherwise it may not effectively protect the equipment from the impact of phase loss faults.

Undervoltage setting:

Usually set at 80% to 90% of the rated voltage, used to detect significant drops in the supply voltage.

It needs to match the minimum operating voltage allowed by the system to avoid misoperation during brief voltage drops such as motor start-up.

Overvoltage setting:

Generally set to 110%~120% of the rated voltage, used to prevent excessive voltage caused by capacitor bank switching or system faults.

Delay characteristic selection:

Fixed time limit: Suitable for situations with clear requirements for time limits, such as cooperating with subordinate protection.

Inverse time limit: applicable to equipment such as motors or transformers, whose ability to withstand asymmetric voltage rapidly decreases with the increase of negative sequence voltage.

Instantaneous (delay set to 00): Used for severe faults that require immediate action, with an action time of less than 50 milliseconds.


On site testing and functional verification

To ensure reliable operation of the relay after it is put into operation, it is recommended to conduct basic functional tests under on-site conditions. The following testing methods are all from official technical manuals and are suitable for on-site implementation.

7.1 Negative sequence voltage pickup and return value test (single-phase method)

Due to the laboratory level symmetrical component testing requiring three-phase voltage sources and phase measurements, a simplified single-phase method can be used on site:

Set the negative sequence setting switch to K position (corresponding to 20%);

Short circuit the terminals of phases B and C (simulate Vbc=0);

Apply a single-phase voltage between phases A and B/C at the rated frequency;

Calculate according to the formula:

V_AB = V2PU × √3 × VN

VN is the rated phase voltage (such as 120 Vac), and V2PU is the set value (such as 0.2 pu).

For a 120 Vac system, the calculated value is approximately 41.57 Vac. At this time, the negative sequence picking LED should light up.

Slowly decrease the voltage and observe the voltage value when the LED is turned off. The return value should be around 98% of the picked up value, which is approximately 40.7 Vac.

This method can quickly verify whether the negative sequence detection circuit is normal and confirm the accuracy of the setting switch.

7.2 Overvoltage and undervoltage pickup test

Overvoltage test:

Set the overvoltage setting switch to E position (10%);

Apply 1.10 times the rated voltage (such as 132 Vac) between phases B and C;

The overvoltage pickup LED should light up;

Reduce the voltage until the LED goes out, and the return value should be around 98% of the pickup value.

Undervoltage test:

Set the undervoltage setting switch to E position (10%);

Apply 0.90 times the rated voltage (such as 108 Vac) between phases B and C;

The undervoltage pickup LED should light up;

Raise the voltage until the LED turns off, and the return value should be around 102% of the pickup value.

7.3 Fixed time and inverse time delay verification

Time limited verification (taking overvoltage as an example):

Set the delay switch to 33 (i.e. 3.3 seconds);

Set the overvoltage setting to A level (2%);

Apply 1.20 times the rated voltage and start the timer at the same time;

The output contact should close within 3.3 seconds ± 5%.

Inverse time limit verification (taking negative sequence as an example):

Set the negative sequence to B level (4%) and set the delay to 10;

Short circuit phases B and C;

Apply a voltage twice the value of the pickup (refer to the table in the manual);

The measurement of the time from voltage application to contact closure should be consistent with the corresponding value of the inverse time curve provided in the manual (such as 5.96 seconds ± 0.298 seconds).


Maintenance and Storage Suggestions

BE1-47N is a solid-state relay with less daily maintenance workload. It is recommended to conduct a functional test on a regular basis (such as annually) to confirm that all protection parameters and action times meet the requirements. If the relay is stored for a long time as a backup, it should be powered on for 30 minutes every 12 months to maintain the performance of the internal electrolytic capacitor and extend its service life.

If there is an abnormality in the relay, it is not recommended to disassemble and repair it on site. It is necessary to promptly contact Basler Electric technical support for professional repair services.

  • Basler DECS-250-CGCM-LN2SA1C Digital Excitation Control System
  • Valmet Automation PLC Module A413171
  • Valmet Automation 542852-3A Rack-Mount Cross Connect Panel
  • Valmet Marine Damatic M851565 Main Keyboard
  • Valmet TIU 6 Printed Circuit Board A413110
  • Metso Valmet U4440253V1.1 RMI CPU 300
  • Metso Valmet A413016 Ver.12 NCU2
  • Valmet M851565 Damatic Keyboard
  • Valmet ATB16-4 16 Channel Relay Card
  • Valmet Metso A413331 SPU Power Supply
  • Valmet PUD 10B Automation Control Rack
  • Valmet MT917 ABMB DMU PCB I/O Module
  • Valmet M851565 Damatic Keyboard Mkb2
  • Valmet EDS-518A-MM-SC Ethernet Gateway
  • Valmet 542836-6A PCB Card
  • Valmet ATB16-4/2 Terminal Board 9144047
  • Valmet ATB16-4 Controller Board 0-50°C 4-20mA Analog Output
  • Valmet 542852-3A Slot Rack Chassis Module
  • Valmet A413026 Ver.M1 FBC Board
  • Valmet IQ Basis Weight SH Sending Assembly A418081
  • Valmet PMB 2R Monolithic Backplane 8-Slot PCB 542821-5A and -5B
  • Valmet ATB16-4 16-Channel Relay Card Controller Board 22195028
  • Valmet Diff-EL SL6NK227SF0 Pressure Transmitter 0-380 mBar
  • Valmet A413110 TIU6 Board Ver.M1
  • Neles Automation A413278 Control Module
  • Valmet BCUTB Terminal Module 10101006 11091002
  • Valmet Senso 160 Measuring Station Display 160.2
  • Valmet AIU 1A Analog Input Unit M851245
  • Valmet IQ Web Caliper Sensor A420734
  • Valmet M851040/M8510401 Memory Board
  • Valmet AN35S1MC02RA Valve
  • Valmet M851121 M2 Cross Connect Panel
  • Valmet AIU-8 Simulator Board 421522-1A
  • Metso BIU 82 D200533 Binary Input Unit
  • Valmet M851121 M2 Module Rack
  • Valmet A413383 PC Board Module
  • Valmet N0542 NO54 ABMB PCB - 545200-3A Board
  • Valmet Metso IOP304 Input Module 181503
  • Valmet PDP601 Distributed Processing Unit 181585
  • Valmet A413084 CPU Board - Processor Module for Automation Systems
  • Valmet AIU 16T Analog Input Module M8512081 M1
  • Valmet AIU 16 Analog Input Module 545100-3A and 545100-3B
  • Metso Valmet BIU4 A413146 Binary Input Unit
  • Valmet AIU-8 Simulateur Board 421522-1a Analog Simulator
  • Valmet BIU8A Binary Input Unit 542803-3B M851222 M1
  • Valmet IQ Web Color DH Photoelectric Sensor A418182 2.04
  • Valmet A413200 AIU-8 Simulator Board 191151 421522-1A
  • Valmet Automation SCU M851006 System Control Unit Module
  • Valmet 857565/851565 Damatic Keyboard IP40 5V Operator Interface
  • Valmet A413077 FBC2 Module Rev 06 Field Bus Controller
  • Valmet DMU 2 PCB Module 545142-3A DM Data Management Unit
  • Valmet AIU16T PCB Card M851208 Analog Input Module
  • Valmet A413181 PLU Board
  • Valmet m851006 SCU Module
  • Valmet Metso 181226 Digital Input Module
  • Valmet AIU16T Analog Input Module - 16-Channel 65421466-2B MT924 V1.3
  • Valmet WIN3136875 Slide Clutch
  • Metso Valmet TIU61 A413111 Temperature Input Unit
  • Valmet MC12S Slitter Motor
  • Valmet A413139 AOH4 Board - Analog Output High Module
  • Valmet A409001 BIU85 Board
  • Valmet A413063 DMU Board
  • Valmet A413325 IPU I/O Power Unit
  • Valmet M851004 M2 CPU Module
  • Valmet IOP345 Digital Input Module
  • Metso Valmet A413215 Communication Board
  • Valmet DIFF-EL 80 M1 Transmitter
  • Valmet A413001 CPU Module
  • Valmet M899520 TDC-2 Module
  • Valmet A409001 BIU85 Board
  • Metso Valmet A413005 CPU Module
  • VALMET PUD 10 B Process Automation Rack with CPU SCU Module
  • Valmet A413091 GDU1 Board
  • VALMET M851006 M2 SCU Module
  • Lyngso Valmet Marine 990.896.000 Position Loop Card
  • Valmet Cooking Liquor Measurement 3417H
  • VALMET ABMB MT831 PCB Card
  • Valmet Automation A413325 IPU I/O Power Unit
  • Valmet Metso Consistency Transmitter Smart Pulp M2
  • VALMET METSO A413274 Connection Module
  • VALMET PI33S1KSA02RSA-ELI26 Switch
  • VALMET ND9103HN-CE07-K05 Intelligent Valve Controller
  • VALMET PMB 2R 16 Slot Backplane PCB Card
  • NELES VALMET A413135 AOU 4 Output Module
  • Metso Valmet A413345 FPU Power Unit
  • VALMET A413171 PIC Module
  • VALMET A413620 Repeater Module
  • Valmet M851521 Memory Card
  • Valmet DIFF-EL 140 M1 Transmitter
  • Valmet A413064 DMU Module
  • Valmet IOP371 I/O Bus Extender Module
  • Valmet Cooking Liquor Measurement 3400 Model 3417H
  • Metso Valmet A413043 CPU Module – Industrial Processor
  • Valmet BIU4 M851221 Binary Input Module
  • Valmet PMB 1S CPU SCU Rack Module
  • Valmet A413248 Controller Module
  • Valmet PDP601 Distributed Processing Unit
  • VALMET M851004 M2 CPU Printed Circuit Board Module
  • Metso Valmet A413045 Ver.05 CPU Module
  • Valmet A413181 Ver.05 PLU1 Board
  • Lyngso Valmet ATB16 Controller Board
  • VALMET AIU 16 Analog Input Unit 545100-3A/3B
  • VALMET PUD 10 B Power Supply PCB Rack Module
  • Valmet MS-50V/120V Bearing Unit
  • Valmet PDP603 Distributed Processing Unit – DPU Module
  • Valmet A413110 TIU Board – Terminal Interface Unit
  • Valmet S420154 I/O Backplane PCB – Printed Circuit Board
  • Valmet A413173 Industrial Control Module
  • Valmet A413044 CPU Module
  • Valmet A4IU1 Analog I/O Module
  • Valmet A413325 IPU Power Unit – PLC Module
  • Valmet M851002 CPU Module – Central Processing Unit
  • Valmet PUD10B Power Supply Board
  • Valmet K00990 Master CPU Electronic Assy
  • Valmet Metso IOP345 Input Module
  • Metso Automation T545215 Board
  • Valmet Metso IOP304 Input Module
  • Valmet 542844-6A SCU Module
  • Metso A413043 Ver.11 Valmet CPU Module
  • Valmet Automation BIU 8A Input Module
  • Metso A413044 Ver05 Valmet CPU Module
  • VALMET 542821-5A Control System Rack Module
  • Metso A413005 Ver.04 Valmet CPU Module
  • Valmet M851207 AIU16 Card
  • Valmet BIU8 Binary Input Unit
  • VALMET 547070-2B CPU Printed Circuit Board Module
  • Valmet Automation A413325 Power Module
  • VALMET AUTOMATION A413135 AOU4 Module