Welcome to the Industrial Automation website!

NameDescriptionContent
XING-Automation
E-mail  
Password  
  
Forgot password?
  Register
当前位置:

Basler BE1-60 Voltage Balance Relay Setting Test

F: | Au:FANS | DA:2026-06-24 | 692 Br: | 🔊 点击朗读正文 ❚❚ ▶ | Share:

Engineering application of Basler BE1-60 voltage balance relay in generator PT disconnection protection and overcurrent lockout

In power plants and substations, the disconnection or failure of the secondary circuit of voltage transformers (PT) is one of the common hidden dangers that can cause protective devices to malfunction. Once the PT fuse is blown or the circuit contact is poor, equipment such as voltage control/voltage limiting overcurrent relays, impedance relays, synchronous relays, excitation regulators, etc. may mistakenly send trip signals due to sensing incorrect voltage, causing unplanned shutdown of the unit or even equipment damage. The BE1-60 voltage balancing relay from Basler Electric is a fast response component specifically designed to solve such problems. Starting from engineering practice, this article systematically sorts out the functional principles, selection points, on-site wiring, setting strategies, and testing verification methods of the relay, providing an operable reference document for electrical maintenance and relay protection personnel.


Product positioning and typical protection scenarios

BE1-60 belongs to the voltage balance relay, and its core task is to continuously compare the difference between two three-phase voltages (usually the power PT secondary voltage and the measured PT secondary voltage). When the voltage difference of any phase exceeds the preset threshold, it quickly sends an alarm or lockout signal to prevent the downstream protection device from malfunctioning due to PT disconnection. This relay is particularly suitable for the following scenarios:

When a generator equipped with a static excitation system experiences a power PT or measurement PT disconnection, the excitation system may output over excitation or under excitation due to abnormal voltage feedback. BE1-60 can distinguish the fault location and initiate the corresponding shutdown or alarm process.

Locking of voltage controlled or voltage limited overcurrent relay: When the sensitivity of the overcurrent relay is abnormally increased due to PT disconnection during measurement, BE1-60 disconnects the tripping circuit of the overcurrent relay through its normally closed contact to avoid false tripping.

Impedance protection, synchronization devices, voltage regulators, and other equipment that require high voltage integrity can all achieve reliable PT disconnection locking through the auxiliary output contacts of BE1-60.


Working principle and signal flow

BE1-60 receives two three-phase voltages (referred to as circuit 1 and circuit 2 respectively) through a step-down transformer internally. After full wave rectification and integration of each phase voltage, a DC level representing the amplitude of that phase voltage is obtained. Next, a dedicated differential amplifier compares the same phase of the two signals and calculates the voltage difference. The difference is compared with the threshold set on the panel (5%~50% rated value, step size 5%). If it exceeds the limit, the corresponding output relay will be triggered.

The noteworthy details are:

The two circuits are independently monitored, and the action direction of the output relay points to the side with lower voltage. For example, if the voltage of one phase of circuit 1 is lower than the corresponding phase of circuit 2, the output relay of circuit 1 will be excited (indicating that there is an undervoltage fault in circuit 1).

When the voltage difference returns below the threshold, the relay will not immediately reset, but will have a fixed delay of about 0.75 seconds to prevent frequent actions caused by transient fluctuations.

For input types (E-type and F-type) that use Scott transformers (T-connection), the three-phase voltage is internally synthesized into a single-phase quantity proportional to the average value. At this time, the sensitivity of the relay will be reduced, and a lower setting gear needs to be selected.

Interpretation of Model Code and Key Points for Selection

The model code of BE1-60 consists of multiple fields, and a correct understanding is beneficial for precise selection. Taking the example model D1H-A1R-C0C2F as an example, the meanings of each field are as follows:

D: Inductive input type, three-phase star (Wye) input converted to three-phase delta internal connection, suitable for 208V line voltage system; There are also options such as A (single-phase), B (three-phase star), C (three-phase delta), E (single-phase to three-phase star), F (single-phase to three-phase delta), etc.

1: The induction range, which is 60% to 125% of the rated voltage, is usually matched with the secondary voltage of the system PT.

H: Output relay configuration, in this example, there are two normally closed (NC) outputs, one for each circuit; Other options include normally open or mixed.

A1: Timing characteristic, here it is instantaneous action (<150ms).

R: Control power type, 24 Vdc (low range), also available O(48/125Vdc)、P(125Vdc/120Vac)、S(48/125Vdc)、T(250Vdc/240Vac) Wait.

C: Target indicator type, internal excitation type (can light up without external current), optional current type or none.

0: No power status output, optional 1 is with power status output.

C: Output test button with push to test button.

2: Auxiliary output type, normally closed (NC) auxiliary contact, one for each circuit.

F: Shell form, semi embedded installation.

When selecting, it is important to pay attention to whether the input voltage level and wiring method (star or delta) are consistent with the on-site PT; The output contact form (normally open/normally closed) needs to meet the requirements of the interlocking circuit (usually requiring normally closed series connection to the trip circuit); The control power supply voltage needs to match the on-site DC or AC power supply.


Key points for installation wiring and grounding

BE1-60 adopts S1 chassis and supports semi embedded or protruding installation. The installation dimensions and panel opening diagram are detailed in the manual (in inches and millimeters). Due to the solid-state design of the relay, there are no special restrictions on the installation angle.

Key Wiring Guide:

Voltage input terminal: According to the induction input type (A~F), connect the two three-phase voltages to the corresponding terminal blocks according to Figure 4-8 in the manual. For example, a three-phase star input needs to be connected to the A, B, C phases and neutral point (if any), while a delta input needs to be connected to the line voltage.

Output contact: The main output (loop 1 and loop 2) is usually used for trip locking or alarm. If used for blocking overcurrent relays, the normally closed contacts should be connected in series in the overcurrent relay trip outlet circuit.

Auxiliary power supply: The power terminals have no polarity, but it is necessary to ensure that the voltage is within the allowable range. When the power supply is normal, the green LED on the panel lights up.

Grounding: A copper wire of not less than 12 AWG must be used to reliably connect the grounding terminal of the enclosure to the ground grid, and it is recommended that each device be independently led to avoid common ground interference.

Important precautions:

If the output contact drives the external relay coil, it is recommended to parallel reverse diodes at both ends of the coil to suppress EMI interference.

If insulation withstand voltage testing is required, the connecting plug must be unplugged and the relay must be removed from the chassis first, otherwise it may damage the internal electronic components.

Setting strategy and typical settings

The only user setting component for BE1-60 is the ten level differential setting switch on the panel, corresponding to 5% to 50% rated voltage, with a step size of 5%. Reasonable tuning should take into account the following factors:

The inherent deviation of the two PTs during normal operation: Due to the fact that the power PT and measurement PT may be taken from different positions, there may be a 2% to 5% difference in their secondary voltage during load changes. For example, when the generator is fully loaded, the power PT voltage may be 5% lower than when it is unloaded, so the set value should be greater than the maximum normal deviation, usually taking 10% to 15% as the starting point.

For E/F type input (single-phase synthesis): Due to internal averaging processing, the actual sensitivity is reduced. It is recommended to use a lower gear (such as B=10% or C=15%), otherwise single-phase disconnection may not be detected.

Coordination with other protections in the system: If used to block voltage controlled overcurrent relays, it is necessary to ensure that BE1-60 can send a blocking signal before the overcurrent relay acts when the voltage drop caused by PT disconnection reaches the set value. Due to the BE1-60 action time being less than 150ms, which is much faster than the timing or inverse time limit of the overcurrent relay, it usually meets the coordination requirements.

Example calculation: Assuming the rated voltage of the system is 120Vac and the normal voltage difference between the power PT and the measured PT does not exceed 8%, the setting switch can be set to C (15%) or D (20%), leaving sufficient margin. If using E/F type input, it is recommended to place it at B (10%), because the equivalent difference synthesized internally during single-phase disconnection is only one-third of the actual phase voltage difference (such as the 40V synthesized difference mentioned above). If placed at G (42V), it may not function.


On site testing and functional verification

After new installation or maintenance, it is recommended to perform functional testing according to the following steps to verify that the relay wiring is correct and the setting is reasonable.

Required instruments: Adjustable three-phase or single-phase AC voltage source (accuracy ± 1%), multimeter, timer.

6.1 Basic Actions and Reset Test (Taking Three Phase Star Input as an Example)

Set the difference setting switch to the lowest gear A (5%).

Apply rated voltage (such as 120Vac line voltage) to both inputs, wait for the state to stabilize, confirm that both output relays are in normal state (normally closed type is closed, normally open type is open), and reset the target indicator (if any).

Slowly increase the A-phase voltage of circuit 1 (while keeping the other phases rated), and observe when the output relay of circuit 2 shifts (indicating that the voltage of the phase where circuit 2 is located is relatively low). According to the manual, the change point should be between 125~127Vac (i.e. 104~106% of the rated voltage) - because at this point, the difference reaches more than 5%. Record the value and compare it with the theoretical value.

Reduce the phase voltage of circuit 1A back to 120Vac, and the relay should automatically reset (output returns to normal state) after about 0.75 seconds. Reset the target indicator.

6.2 High setting value test (verify setting range)

Set the setting switch to the highest position K (50%).

Slowly reduce the A-phase voltage of circuit 1 (while keeping the other phases rated) until the output relay of circuit 1 shifts (indicating that the voltage of circuit 1 is too low). In theory, the change point should be between 57~63Vac (i.e. 47%~53% of the rated voltage), as the difference reaches about 50% at this time.

Record the change point and calculate whether the error is within the allowable range (± 1V or ± 5% of the set value, whichever is greater).

6.3 Multiphase testing (applicable to three-phase input types B/C/D)

Repeat the above steps and perform single-phase voltage rise and fall tests on phases B and C respectively to ensure that the differential circuit of each phase is working properly.

6.4 Verification of output contacts and target indicators

If equipped with a "push test" button, use a non-conductive rod to press the corresponding test button for circuit 1 or circuit 2, observe whether the corresponding output relay is excited (target on, contact status changes), and verify the integrity of the external wiring circuit.

For current type targets, it is necessary to ensure that the tripping circuit current is not less than 200mA, otherwise the target will not light up.

6.5 System cascading adjustment (actual locking effect)

Under simulated PT disconnection conditions (such as manually disconnecting one phase voltage), observe whether BE1-60 can issue a lockout signal before the overcurrent relay acts. An oscilloscope or event recorder can be used to capture the timing of actions, ensuring that the locking contact opens before the tripping contact.


Maintenance and Storage Suggestions

BE1-60 is a solid-state relay with extremely low daily maintenance requirements. It is recommended to conduct a complete functional test once a year to confirm that the setting values and action times are still within the specifications. If the relay is kept in stock for a long time, it should be powered on for 30 minutes every year to maintain the performance of the internal electrolytic capacitor and extend its service life. In case of malfunction, on-site dismantling and repair should not be carried out, and Basler Electric technical support should be contacted in a timely manner.

  • ALSTOM 029.204 687 Digital I/O VME Board
  • National Instruments PXI-6509 Digital I/O Module
  • National Instruments FP-AI-112 Analog Input Module
  • National Instruments cRIO-9065 CompactRIO Controller
  • National Instruments PXI-2570 SPDT Relay Module
  • National Instruments PXI-5610 Module
  • National Instruments cFP-RTD-122 Module
  • National Instruments PXI-8336 Module
  • National Instruments NI 9237 Module
  • National Instruments PCI-6224 DAQ Card
  • National Instruments USB-6218 DAQ Device
  • National Instruments PCI-6601 Device
  • National Instruments SCXI-1124 Module
  • National Instruments USB-6525 DIO Device
  • National Instruments cDAQ-9189 Chassis
  • National Instruments PXIe-8394 MXI Module
  • National Instruments PXIe-4112 Power Supply
  • National Instruments 778472-01 Module
  • National Instruments cFP-DO-401 Module
  • National Instruments PXIe-8379 Interface Card
  • National Instruments PXIe-7965R Module
  • National Instruments NI-9485 Relay Module
  • National Instruments 181045-01 Module
  • National Instruments TB-4302 Terminal Block
  • National Instruments PXI-2533 Matrix Switch Module
  • National Instruments PCI-6220 Analog Input Card
  • National Instruments PXI-2529 Matrix Switch Module
  • National Instruments 783732-01 Ordering Part Number
  • National Instruments PXI-6542 Digital Waveform Module
  • National Instruments PCI-1411 Image Acquisition Card
  • National Instruments PXI-6511 Industrial Digital I/O Module
  • National Instruments TPC-2012 Touch Panel Computer
  • National Instruments PXI-8101 Embedded Controller
  • National Instruments cRIO-9035 CompactRIO Controller
  • National Instruments PXIe-5114 Digitizer Card
  • National Instruments SCXI-1315 Block
  • National Instruments PXI-7842R Card
  • National Instruments PCI-6031E DAQ Device
  • National Instruments NI-9792 Gateway
  • National Instruments PXI-4132 SMU
  • National Instruments USB-5132 Digitizer
  • National Instruments NI 9244 Input Module
  • National Instruments SCXI-1163R Module
  • National Instruments PCI-6221 DAQ Device
  • National Instruments cFP-2120 Compact FieldPoint Controller
  • National Instruments cRIO-9073 CompactRIO Controller
  • National Instruments PCI-8516 CAN Interface Card
  • National Instruments PXIe-1073 5-Slot Chassis
  • National Instruments NI 9421 DSUB Digital Input Module
  • National Instruments PXI-4204 High Voltage Input Module
  • National Instruments PCI-6111 Multifunction DAQ Card
  • National Instruments cRIO-9035 CompactRIO Controller
  • National Instruments NI 9759 Powertrain Control Module
  • National Instruments 187254A-01 Ordering Part Number
  • National Instruments PXI-6624 Module
  • National Instruments cDAQ-9137 Chassis
  • National Instruments PXIe-8133 Controller
  • National Instruments 779139-01 Module
  • National Instruments FP-DI-301 Module
  • National Instruments 194021D-01L Module
  • National Instruments PXI-1000B Chassis
  • National Instruments PXIe-8510 Module
  • National Instruments PXI-6221 DAQ Card
  • National Instruments cDAQ-9188 Chassis
  • National Instruments PXI-5421 Arbitrary Waveform Generator
  • National Instruments cRIO-9023 CompactRIO Controller
  • National Instruments PCI-6221 Multifunction DAQ Card
  • National Instruments PXI-4065 Digital Multimeter Card
  • National Instruments NI 9477 Digital Output Module
  • National Instruments cDAQ-9185 TSN Ethernet Chassis
  • National Instruments NI 9147 4-Slot cRIO Chassis
  • National Instruments USB-6259 Mass Termination DAQ Device
  • National Instruments 184120F-01 Ordering Part Number
  • National Instruments PCI-4472B Sound and Vibration Module
  • National Instruments SCXI-1130 Switch
  • National Instruments VB-8012 VirtualBench
  • National Instruments PXI-7350 Controller
  • National Instruments eDAQ-9174 Chassis
  • National Instruments PXI-4461 DSA Module
  • National Instruments PCI-6280 DAQ Card
  • National Instruments PXI-6251 DAQ Card
  • National Instruments PXI-6653 Module
  • National Instruments PCI-6509 DIO Device
  • National Instruments NI 9751 Driver Module
  • National Instruments PXIe-6361 Multifunction I/O Module
  • National Instruments cRIO-9014 CompactRIO Controller
  • National Instruments PCI-7390 Motion Control Card
  • National Instruments PXI-8512 CAN Interface Module
  • National Instruments sbRIO-9636 Single-Board Controller
  • National Instruments IC-3120 Industrial Controller
  • National Instruments PCI-6220 M Series DAQ Card
  • National Instruments PXI-8176 Embedded Controller
  • National Instruments PXI-6132 S Series DAQ Module
  • National Instruments NI 9206 Analog Input Module
  • National Instruments PXI-2584 Switch Module
  • National Instruments 196541B-01L Module
  • National Instruments 778075-01 Module
  • National Instruments FP-RLY-420 Module
  • National Instruments USRP-2920 Radio
  • National Instruments PCIe-6351 DAQ Card
  • National Instruments cRIO-9040 Controller
  • National Instruments NI 9201 Input Module
  • National Instruments NI 9411 Input Module
  • National Instruments NI 9216 Input Module
  • National Instruments PCI-6221 DAQ Device
  • National Instruments PXI-4498 DSA Module
  • National Instruments PXI-6259 DAQ Card
  • National Instruments PXI-7354 Motion Controller
  • National Instruments FP-AI-110 Input Module
  • National Instruments 192172F-04L Module
  • National Instruments PXIe-8115 Controller
  • National Instruments 142931B-01L Module
  • National Instruments PXI-2503 Switch Module
  • National Instruments 776246-01 Module
  • National Instruments CFP-2110 Compact FieldPoint Controller
  • National Instruments 779429-01 Ordering Part Number
  • National Instruments NI-9149 8-Slot EtherCAT Chassis
  • National Instruments PXI-4110 Programmable DC Supply
  • National Instruments 192061-10 Ordering Part Number
  • National Instruments cDAQ-9181 Chassis Module Carrier
  • National Instruments NI 9437 Digital Input Module
  • National Instruments cFP-2020 Compact FieldPoint Controller
  • National Instruments PCI-6259 Multifunction DAQ Card
  • National Instruments FP-TC-120 Thermocouple Module
  • National Instruments NI-9174 CompactDAQ Chassis
  • National Instruments PXI-6030E DAQ Module
  • National Instruments PXIe-5160 Oscilloscope
  • National Instruments PXI-4462 DSA Module