Welcome to the Industrial Automation website!

NameDescriptionContent
XING-Automation
E-mail  
Password  
  
Forgot password?
  Register
当前位置:

Basler BE1-60 Voltage Balance Relay Setting Test

F: | Au:FANS | DA:2026-06-24 | 371 Br: | 🔊 点击朗读正文 ❚❚ | Share:

Engineering application of Basler BE1-60 voltage balance relay in generator PT disconnection protection and overcurrent lockout

In power plants and substations, the disconnection or failure of the secondary circuit of voltage transformers (PT) is one of the common hidden dangers that can cause protective devices to malfunction. Once the PT fuse is blown or the circuit contact is poor, equipment such as voltage control/voltage limiting overcurrent relays, impedance relays, synchronous relays, excitation regulators, etc. may mistakenly send trip signals due to sensing incorrect voltage, causing unplanned shutdown of the unit or even equipment damage. The BE1-60 voltage balancing relay from Basler Electric is a fast response component specifically designed to solve such problems. Starting from engineering practice, this article systematically sorts out the functional principles, selection points, on-site wiring, setting strategies, and testing verification methods of the relay, providing an operable reference document for electrical maintenance and relay protection personnel.


Product positioning and typical protection scenarios

BE1-60 belongs to the voltage balance relay, and its core task is to continuously compare the difference between two three-phase voltages (usually the power PT secondary voltage and the measured PT secondary voltage). When the voltage difference of any phase exceeds the preset threshold, it quickly sends an alarm or lockout signal to prevent the downstream protection device from malfunctioning due to PT disconnection. This relay is particularly suitable for the following scenarios:

When a generator equipped with a static excitation system experiences a power PT or measurement PT disconnection, the excitation system may output over excitation or under excitation due to abnormal voltage feedback. BE1-60 can distinguish the fault location and initiate the corresponding shutdown or alarm process.

Locking of voltage controlled or voltage limited overcurrent relay: When the sensitivity of the overcurrent relay is abnormally increased due to PT disconnection during measurement, BE1-60 disconnects the tripping circuit of the overcurrent relay through its normally closed contact to avoid false tripping.

Impedance protection, synchronization devices, voltage regulators, and other equipment that require high voltage integrity can all achieve reliable PT disconnection locking through the auxiliary output contacts of BE1-60.


Working principle and signal flow

BE1-60 receives two three-phase voltages (referred to as circuit 1 and circuit 2 respectively) through a step-down transformer internally. After full wave rectification and integration of each phase voltage, a DC level representing the amplitude of that phase voltage is obtained. Next, a dedicated differential amplifier compares the same phase of the two signals and calculates the voltage difference. The difference is compared with the threshold set on the panel (5%~50% rated value, step size 5%). If it exceeds the limit, the corresponding output relay will be triggered.

The noteworthy details are:

The two circuits are independently monitored, and the action direction of the output relay points to the side with lower voltage. For example, if the voltage of one phase of circuit 1 is lower than the corresponding phase of circuit 2, the output relay of circuit 1 will be excited (indicating that there is an undervoltage fault in circuit 1).

When the voltage difference returns below the threshold, the relay will not immediately reset, but will have a fixed delay of about 0.75 seconds to prevent frequent actions caused by transient fluctuations.

For input types (E-type and F-type) that use Scott transformers (T-connection), the three-phase voltage is internally synthesized into a single-phase quantity proportional to the average value. At this time, the sensitivity of the relay will be reduced, and a lower setting gear needs to be selected.

Interpretation of Model Code and Key Points for Selection

The model code of BE1-60 consists of multiple fields, and a correct understanding is beneficial for precise selection. Taking the example model D1H-A1R-C0C2F as an example, the meanings of each field are as follows:

D: Inductive input type, three-phase star (Wye) input converted to three-phase delta internal connection, suitable for 208V line voltage system; There are also options such as A (single-phase), B (three-phase star), C (three-phase delta), E (single-phase to three-phase star), F (single-phase to three-phase delta), etc.

1: The induction range, which is 60% to 125% of the rated voltage, is usually matched with the secondary voltage of the system PT.

H: Output relay configuration, in this example, there are two normally closed (NC) outputs, one for each circuit; Other options include normally open or mixed.

A1: Timing characteristic, here it is instantaneous action (<150ms).

R: Control power type, 24 Vdc (low range), also available O(48/125Vdc)、P(125Vdc/120Vac)、S(48/125Vdc)、T(250Vdc/240Vac) Wait.

C: Target indicator type, internal excitation type (can light up without external current), optional current type or none.

0: No power status output, optional 1 is with power status output.

C: Output test button with push to test button.

2: Auxiliary output type, normally closed (NC) auxiliary contact, one for each circuit.

F: Shell form, semi embedded installation.

When selecting, it is important to pay attention to whether the input voltage level and wiring method (star or delta) are consistent with the on-site PT; The output contact form (normally open/normally closed) needs to meet the requirements of the interlocking circuit (usually requiring normally closed series connection to the trip circuit); The control power supply voltage needs to match the on-site DC or AC power supply.


Key points for installation wiring and grounding

BE1-60 adopts S1 chassis and supports semi embedded or protruding installation. The installation dimensions and panel opening diagram are detailed in the manual (in inches and millimeters). Due to the solid-state design of the relay, there are no special restrictions on the installation angle.

Key Wiring Guide:

Voltage input terminal: According to the induction input type (A~F), connect the two three-phase voltages to the corresponding terminal blocks according to Figure 4-8 in the manual. For example, a three-phase star input needs to be connected to the A, B, C phases and neutral point (if any), while a delta input needs to be connected to the line voltage.

Output contact: The main output (loop 1 and loop 2) is usually used for trip locking or alarm. If used for blocking overcurrent relays, the normally closed contacts should be connected in series in the overcurrent relay trip outlet circuit.

Auxiliary power supply: The power terminals have no polarity, but it is necessary to ensure that the voltage is within the allowable range. When the power supply is normal, the green LED on the panel lights up.

Grounding: A copper wire of not less than 12 AWG must be used to reliably connect the grounding terminal of the enclosure to the ground grid, and it is recommended that each device be independently led to avoid common ground interference.

Important precautions:

If the output contact drives the external relay coil, it is recommended to parallel reverse diodes at both ends of the coil to suppress EMI interference.

If insulation withstand voltage testing is required, the connecting plug must be unplugged and the relay must be removed from the chassis first, otherwise it may damage the internal electronic components.

Setting strategy and typical settings

The only user setting component for BE1-60 is the ten level differential setting switch on the panel, corresponding to 5% to 50% rated voltage, with a step size of 5%. Reasonable tuning should take into account the following factors:

The inherent deviation of the two PTs during normal operation: Due to the fact that the power PT and measurement PT may be taken from different positions, there may be a 2% to 5% difference in their secondary voltage during load changes. For example, when the generator is fully loaded, the power PT voltage may be 5% lower than when it is unloaded, so the set value should be greater than the maximum normal deviation, usually taking 10% to 15% as the starting point.

For E/F type input (single-phase synthesis): Due to internal averaging processing, the actual sensitivity is reduced. It is recommended to use a lower gear (such as B=10% or C=15%), otherwise single-phase disconnection may not be detected.

Coordination with other protections in the system: If used to block voltage controlled overcurrent relays, it is necessary to ensure that BE1-60 can send a blocking signal before the overcurrent relay acts when the voltage drop caused by PT disconnection reaches the set value. Due to the BE1-60 action time being less than 150ms, which is much faster than the timing or inverse time limit of the overcurrent relay, it usually meets the coordination requirements.

Example calculation: Assuming the rated voltage of the system is 120Vac and the normal voltage difference between the power PT and the measured PT does not exceed 8%, the setting switch can be set to C (15%) or D (20%), leaving sufficient margin. If using E/F type input, it is recommended to place it at B (10%), because the equivalent difference synthesized internally during single-phase disconnection is only one-third of the actual phase voltage difference (such as the 40V synthesized difference mentioned above). If placed at G (42V), it may not function.


On site testing and functional verification

After new installation or maintenance, it is recommended to perform functional testing according to the following steps to verify that the relay wiring is correct and the setting is reasonable.

Required instruments: Adjustable three-phase or single-phase AC voltage source (accuracy ± 1%), multimeter, timer.

6.1 Basic Actions and Reset Test (Taking Three Phase Star Input as an Example)

Set the difference setting switch to the lowest gear A (5%).

Apply rated voltage (such as 120Vac line voltage) to both inputs, wait for the state to stabilize, confirm that both output relays are in normal state (normally closed type is closed, normally open type is open), and reset the target indicator (if any).

Slowly increase the A-phase voltage of circuit 1 (while keeping the other phases rated), and observe when the output relay of circuit 2 shifts (indicating that the voltage of the phase where circuit 2 is located is relatively low). According to the manual, the change point should be between 125~127Vac (i.e. 104~106% of the rated voltage) - because at this point, the difference reaches more than 5%. Record the value and compare it with the theoretical value.

Reduce the phase voltage of circuit 1A back to 120Vac, and the relay should automatically reset (output returns to normal state) after about 0.75 seconds. Reset the target indicator.

6.2 High setting value test (verify setting range)

Set the setting switch to the highest position K (50%).

Slowly reduce the A-phase voltage of circuit 1 (while keeping the other phases rated) until the output relay of circuit 1 shifts (indicating that the voltage of circuit 1 is too low). In theory, the change point should be between 57~63Vac (i.e. 47%~53% of the rated voltage), as the difference reaches about 50% at this time.

Record the change point and calculate whether the error is within the allowable range (± 1V or ± 5% of the set value, whichever is greater).

6.3 Multiphase testing (applicable to three-phase input types B/C/D)

Repeat the above steps and perform single-phase voltage rise and fall tests on phases B and C respectively to ensure that the differential circuit of each phase is working properly.

6.4 Verification of output contacts and target indicators

If equipped with a "push test" button, use a non-conductive rod to press the corresponding test button for circuit 1 or circuit 2, observe whether the corresponding output relay is excited (target on, contact status changes), and verify the integrity of the external wiring circuit.

For current type targets, it is necessary to ensure that the tripping circuit current is not less than 200mA, otherwise the target will not light up.

6.5 System cascading adjustment (actual locking effect)

Under simulated PT disconnection conditions (such as manually disconnecting one phase voltage), observe whether BE1-60 can issue a lockout signal before the overcurrent relay acts. An oscilloscope or event recorder can be used to capture the timing of actions, ensuring that the locking contact opens before the tripping contact.


Maintenance and Storage Suggestions

BE1-60 is a solid-state relay with extremely low daily maintenance requirements. It is recommended to conduct a complete functional test once a year to confirm that the setting values and action times are still within the specifications. If the relay is kept in stock for a long time, it should be powered on for 30 minutes every year to maintain the performance of the internal electrolytic capacitor and extend its service life. In case of malfunction, on-site dismantling and repair should not be carried out, and Basler Electric technical support should be contacted in a timely manner.

  • Basler DECS-250-CGCM-LN2SA1C Digital Excitation Control System
  • Valmet Automation PLC Module A413171
  • Valmet Automation 542852-3A Rack-Mount Cross Connect Panel
  • Valmet Marine Damatic M851565 Main Keyboard
  • Valmet TIU 6 Printed Circuit Board A413110
  • Metso Valmet U4440253V1.1 RMI CPU 300
  • Metso Valmet A413016 Ver.12 NCU2
  • Valmet M851565 Damatic Keyboard
  • Valmet ATB16-4 16 Channel Relay Card
  • Valmet Metso A413331 SPU Power Supply
  • Valmet PUD 10B Automation Control Rack
  • Valmet MT917 ABMB DMU PCB I/O Module
  • Valmet M851565 Damatic Keyboard Mkb2
  • Valmet EDS-518A-MM-SC Ethernet Gateway
  • Valmet 542836-6A PCB Card
  • Valmet ATB16-4/2 Terminal Board 9144047
  • Valmet ATB16-4 Controller Board 0-50°C 4-20mA Analog Output
  • Valmet 542852-3A Slot Rack Chassis Module
  • Valmet A413026 Ver.M1 FBC Board
  • Valmet IQ Basis Weight SH Sending Assembly A418081
  • Valmet PMB 2R Monolithic Backplane 8-Slot PCB 542821-5A and -5B
  • Valmet ATB16-4 16-Channel Relay Card Controller Board 22195028
  • Valmet Diff-EL SL6NK227SF0 Pressure Transmitter 0-380 mBar
  • Valmet A413110 TIU6 Board Ver.M1
  • Neles Automation A413278 Control Module
  • Valmet BCUTB Terminal Module 10101006 11091002
  • Valmet Senso 160 Measuring Station Display 160.2
  • Valmet AIU 1A Analog Input Unit M851245
  • Valmet IQ Web Caliper Sensor A420734
  • Valmet M851040/M8510401 Memory Board
  • Valmet AN35S1MC02RA Valve
  • Valmet M851121 M2 Cross Connect Panel
  • Valmet AIU-8 Simulator Board 421522-1A
  • Metso BIU 82 D200533 Binary Input Unit
  • Valmet M851121 M2 Module Rack
  • Valmet A413383 PC Board Module
  • Valmet N0542 NO54 ABMB PCB - 545200-3A Board
  • Valmet Metso IOP304 Input Module 181503
  • Valmet PDP601 Distributed Processing Unit 181585
  • Valmet A413084 CPU Board - Processor Module for Automation Systems
  • Valmet AIU 16T Analog Input Module M8512081 M1
  • Valmet AIU 16 Analog Input Module 545100-3A and 545100-3B
  • Metso Valmet BIU4 A413146 Binary Input Unit
  • Valmet AIU-8 Simulateur Board 421522-1a Analog Simulator
  • Valmet BIU8A Binary Input Unit 542803-3B M851222 M1
  • Valmet IQ Web Color DH Photoelectric Sensor A418182 2.04
  • Valmet A413200 AIU-8 Simulator Board 191151 421522-1A
  • Valmet Automation SCU M851006 System Control Unit Module
  • Valmet 857565/851565 Damatic Keyboard IP40 5V Operator Interface
  • Valmet A413077 FBC2 Module Rev 06 Field Bus Controller
  • Valmet DMU 2 PCB Module 545142-3A DM Data Management Unit
  • Valmet AIU16T PCB Card M851208 Analog Input Module
  • Valmet A413181 PLU Board
  • Valmet m851006 SCU Module
  • Valmet Metso 181226 Digital Input Module
  • Valmet AIU16T Analog Input Module - 16-Channel 65421466-2B MT924 V1.3
  • Valmet WIN3136875 Slide Clutch
  • Metso Valmet TIU61 A413111 Temperature Input Unit
  • Valmet MC12S Slitter Motor
  • Valmet A413139 AOH4 Board - Analog Output High Module
  • Valmet A409001 BIU85 Board
  • Valmet A413063 DMU Board
  • Valmet A413325 IPU I/O Power Unit
  • Valmet M851004 M2 CPU Module
  • Valmet IOP345 Digital Input Module
  • Metso Valmet A413215 Communication Board
  • Valmet DIFF-EL 80 M1 Transmitter
  • Valmet A413001 CPU Module
  • Valmet M899520 TDC-2 Module
  • Valmet A409001 BIU85 Board
  • Metso Valmet A413005 CPU Module
  • VALMET PUD 10 B Process Automation Rack with CPU SCU Module
  • Valmet A413091 GDU1 Board
  • VALMET M851006 M2 SCU Module
  • Lyngso Valmet Marine 990.896.000 Position Loop Card
  • Valmet Cooking Liquor Measurement 3417H
  • VALMET ABMB MT831 PCB Card
  • Valmet Automation A413325 IPU I/O Power Unit
  • Valmet Metso Consistency Transmitter Smart Pulp M2
  • VALMET METSO A413274 Connection Module
  • VALMET PI33S1KSA02RSA-ELI26 Switch
  • VALMET ND9103HN-CE07-K05 Intelligent Valve Controller
  • VALMET PMB 2R 16 Slot Backplane PCB Card
  • NELES VALMET A413135 AOU 4 Output Module
  • Metso Valmet A413345 FPU Power Unit
  • VALMET A413171 PIC Module
  • VALMET A413620 Repeater Module
  • Valmet M851521 Memory Card
  • Valmet DIFF-EL 140 M1 Transmitter
  • Valmet A413064 DMU Module
  • Valmet IOP371 I/O Bus Extender Module
  • Valmet Cooking Liquor Measurement 3400 Model 3417H
  • Metso Valmet A413043 CPU Module – Industrial Processor
  • Valmet BIU4 M851221 Binary Input Module
  • Valmet PMB 1S CPU SCU Rack Module
  • Valmet A413248 Controller Module
  • Valmet PDP601 Distributed Processing Unit
  • VALMET M851004 M2 CPU Printed Circuit Board Module
  • Metso Valmet A413045 Ver.05 CPU Module
  • Valmet A413181 Ver.05 PLU1 Board
  • Lyngso Valmet ATB16 Controller Board
  • VALMET AIU 16 Analog Input Unit 545100-3A/3B
  • VALMET PUD 10 B Power Supply PCB Rack Module
  • Valmet MS-50V/120V Bearing Unit
  • Valmet PDP603 Distributed Processing Unit – DPU Module
  • Valmet A413110 TIU Board – Terminal Interface Unit
  • Valmet S420154 I/O Backplane PCB – Printed Circuit Board
  • Valmet A413173 Industrial Control Module
  • Valmet A413044 CPU Module
  • Valmet A4IU1 Analog I/O Module
  • Valmet A413325 IPU Power Unit – PLC Module
  • Valmet M851002 CPU Module – Central Processing Unit
  • Valmet PUD10B Power Supply Board
  • Valmet K00990 Master CPU Electronic Assy
  • Valmet Metso IOP345 Input Module
  • Metso Automation T545215 Board
  • Valmet Metso IOP304 Input Module
  • Valmet 542844-6A SCU Module
  • Metso A413043 Ver.11 Valmet CPU Module
  • Valmet Automation BIU 8A Input Module
  • Metso A413044 Ver05 Valmet CPU Module
  • VALMET 542821-5A Control System Rack Module
  • Metso A413005 Ver.04 Valmet CPU Module
  • Valmet M851207 AIU16 Card
  • Valmet BIU8 Binary Input Unit
  • VALMET 547070-2B CPU Printed Circuit Board Module
  • Valmet Automation A413325 Power Module
  • VALMET AUTOMATION A413135 AOU4 Module