Welcome to the Industrial Automation website!

NameDescriptionContent
XING-Automation
E-mail  
Password  
  
Forgot password?
  Register
当前位置:

Basler BE1-60 Voltage Balance Relay Setting Test

F: | Au:FANS | DA:2026-06-24 | 13 Br: | 🔊 点击朗读正文 ❚❚ | Share:

Engineering application of Basler BE1-60 voltage balance relay in generator PT disconnection protection and overcurrent lockout

In power plants and substations, the disconnection or failure of the secondary circuit of voltage transformers (PT) is one of the common hidden dangers that can cause protective devices to malfunction. Once the PT fuse is blown or the circuit contact is poor, equipment such as voltage control/voltage limiting overcurrent relays, impedance relays, synchronous relays, excitation regulators, etc. may mistakenly send trip signals due to sensing incorrect voltage, causing unplanned shutdown of the unit or even equipment damage. The BE1-60 voltage balancing relay from Basler Electric is a fast response component specifically designed to solve such problems. Starting from engineering practice, this article systematically sorts out the functional principles, selection points, on-site wiring, setting strategies, and testing verification methods of the relay, providing an operable reference document for electrical maintenance and relay protection personnel.


Product positioning and typical protection scenarios

BE1-60 belongs to the voltage balance relay, and its core task is to continuously compare the difference between two three-phase voltages (usually the power PT secondary voltage and the measured PT secondary voltage). When the voltage difference of any phase exceeds the preset threshold, it quickly sends an alarm or lockout signal to prevent the downstream protection device from malfunctioning due to PT disconnection. This relay is particularly suitable for the following scenarios:

When a generator equipped with a static excitation system experiences a power PT or measurement PT disconnection, the excitation system may output over excitation or under excitation due to abnormal voltage feedback. BE1-60 can distinguish the fault location and initiate the corresponding shutdown or alarm process.

Locking of voltage controlled or voltage limited overcurrent relay: When the sensitivity of the overcurrent relay is abnormally increased due to PT disconnection during measurement, BE1-60 disconnects the tripping circuit of the overcurrent relay through its normally closed contact to avoid false tripping.

Impedance protection, synchronization devices, voltage regulators, and other equipment that require high voltage integrity can all achieve reliable PT disconnection locking through the auxiliary output contacts of BE1-60.


Working principle and signal flow

BE1-60 receives two three-phase voltages (referred to as circuit 1 and circuit 2 respectively) through a step-down transformer internally. After full wave rectification and integration of each phase voltage, a DC level representing the amplitude of that phase voltage is obtained. Next, a dedicated differential amplifier compares the same phase of the two signals and calculates the voltage difference. The difference is compared with the threshold set on the panel (5%~50% rated value, step size 5%). If it exceeds the limit, the corresponding output relay will be triggered.

The noteworthy details are:

The two circuits are independently monitored, and the action direction of the output relay points to the side with lower voltage. For example, if the voltage of one phase of circuit 1 is lower than the corresponding phase of circuit 2, the output relay of circuit 1 will be excited (indicating that there is an undervoltage fault in circuit 1).

When the voltage difference returns below the threshold, the relay will not immediately reset, but will have a fixed delay of about 0.75 seconds to prevent frequent actions caused by transient fluctuations.

For input types (E-type and F-type) that use Scott transformers (T-connection), the three-phase voltage is internally synthesized into a single-phase quantity proportional to the average value. At this time, the sensitivity of the relay will be reduced, and a lower setting gear needs to be selected.

Interpretation of Model Code and Key Points for Selection

The model code of BE1-60 consists of multiple fields, and a correct understanding is beneficial for precise selection. Taking the example model D1H-A1R-C0C2F as an example, the meanings of each field are as follows:

D: Inductive input type, three-phase star (Wye) input converted to three-phase delta internal connection, suitable for 208V line voltage system; There are also options such as A (single-phase), B (three-phase star), C (three-phase delta), E (single-phase to three-phase star), F (single-phase to three-phase delta), etc.

1: The induction range, which is 60% to 125% of the rated voltage, is usually matched with the secondary voltage of the system PT.

H: Output relay configuration, in this example, there are two normally closed (NC) outputs, one for each circuit; Other options include normally open or mixed.

A1: Timing characteristic, here it is instantaneous action (<150ms).

R: Control power type, 24 Vdc (low range), also available O(48/125Vdc)、P(125Vdc/120Vac)、S(48/125Vdc)、T(250Vdc/240Vac) Wait.

C: Target indicator type, internal excitation type (can light up without external current), optional current type or none.

0: No power status output, optional 1 is with power status output.

C: Output test button with push to test button.

2: Auxiliary output type, normally closed (NC) auxiliary contact, one for each circuit.

F: Shell form, semi embedded installation.

When selecting, it is important to pay attention to whether the input voltage level and wiring method (star or delta) are consistent with the on-site PT; The output contact form (normally open/normally closed) needs to meet the requirements of the interlocking circuit (usually requiring normally closed series connection to the trip circuit); The control power supply voltage needs to match the on-site DC or AC power supply.


Key points for installation wiring and grounding

BE1-60 adopts S1 chassis and supports semi embedded or protruding installation. The installation dimensions and panel opening diagram are detailed in the manual (in inches and millimeters). Due to the solid-state design of the relay, there are no special restrictions on the installation angle.

Key Wiring Guide:

Voltage input terminal: According to the induction input type (A~F), connect the two three-phase voltages to the corresponding terminal blocks according to Figure 4-8 in the manual. For example, a three-phase star input needs to be connected to the A, B, C phases and neutral point (if any), while a delta input needs to be connected to the line voltage.

Output contact: The main output (loop 1 and loop 2) is usually used for trip locking or alarm. If used for blocking overcurrent relays, the normally closed contacts should be connected in series in the overcurrent relay trip outlet circuit.

Auxiliary power supply: The power terminals have no polarity, but it is necessary to ensure that the voltage is within the allowable range. When the power supply is normal, the green LED on the panel lights up.

Grounding: A copper wire of not less than 12 AWG must be used to reliably connect the grounding terminal of the enclosure to the ground grid, and it is recommended that each device be independently led to avoid common ground interference.

Important precautions:

If the output contact drives the external relay coil, it is recommended to parallel reverse diodes at both ends of the coil to suppress EMI interference.

If insulation withstand voltage testing is required, the connecting plug must be unplugged and the relay must be removed from the chassis first, otherwise it may damage the internal electronic components.

Setting strategy and typical settings

The only user setting component for BE1-60 is the ten level differential setting switch on the panel, corresponding to 5% to 50% rated voltage, with a step size of 5%. Reasonable tuning should take into account the following factors:

The inherent deviation of the two PTs during normal operation: Due to the fact that the power PT and measurement PT may be taken from different positions, there may be a 2% to 5% difference in their secondary voltage during load changes. For example, when the generator is fully loaded, the power PT voltage may be 5% lower than when it is unloaded, so the set value should be greater than the maximum normal deviation, usually taking 10% to 15% as the starting point.

For E/F type input (single-phase synthesis): Due to internal averaging processing, the actual sensitivity is reduced. It is recommended to use a lower gear (such as B=10% or C=15%), otherwise single-phase disconnection may not be detected.

Coordination with other protections in the system: If used to block voltage controlled overcurrent relays, it is necessary to ensure that BE1-60 can send a blocking signal before the overcurrent relay acts when the voltage drop caused by PT disconnection reaches the set value. Due to the BE1-60 action time being less than 150ms, which is much faster than the timing or inverse time limit of the overcurrent relay, it usually meets the coordination requirements.

Example calculation: Assuming the rated voltage of the system is 120Vac and the normal voltage difference between the power PT and the measured PT does not exceed 8%, the setting switch can be set to C (15%) or D (20%), leaving sufficient margin. If using E/F type input, it is recommended to place it at B (10%), because the equivalent difference synthesized internally during single-phase disconnection is only one-third of the actual phase voltage difference (such as the 40V synthesized difference mentioned above). If placed at G (42V), it may not function.


On site testing and functional verification

After new installation or maintenance, it is recommended to perform functional testing according to the following steps to verify that the relay wiring is correct and the setting is reasonable.

Required instruments: Adjustable three-phase or single-phase AC voltage source (accuracy ± 1%), multimeter, timer.

6.1 Basic Actions and Reset Test (Taking Three Phase Star Input as an Example)

Set the difference setting switch to the lowest gear A (5%).

Apply rated voltage (such as 120Vac line voltage) to both inputs, wait for the state to stabilize, confirm that both output relays are in normal state (normally closed type is closed, normally open type is open), and reset the target indicator (if any).

Slowly increase the A-phase voltage of circuit 1 (while keeping the other phases rated), and observe when the output relay of circuit 2 shifts (indicating that the voltage of the phase where circuit 2 is located is relatively low). According to the manual, the change point should be between 125~127Vac (i.e. 104~106% of the rated voltage) - because at this point, the difference reaches more than 5%. Record the value and compare it with the theoretical value.

Reduce the phase voltage of circuit 1A back to 120Vac, and the relay should automatically reset (output returns to normal state) after about 0.75 seconds. Reset the target indicator.

6.2 High setting value test (verify setting range)

Set the setting switch to the highest position K (50%).

Slowly reduce the A-phase voltage of circuit 1 (while keeping the other phases rated) until the output relay of circuit 1 shifts (indicating that the voltage of circuit 1 is too low). In theory, the change point should be between 57~63Vac (i.e. 47%~53% of the rated voltage), as the difference reaches about 50% at this time.

Record the change point and calculate whether the error is within the allowable range (± 1V or ± 5% of the set value, whichever is greater).

6.3 Multiphase testing (applicable to three-phase input types B/C/D)

Repeat the above steps and perform single-phase voltage rise and fall tests on phases B and C respectively to ensure that the differential circuit of each phase is working properly.

6.4 Verification of output contacts and target indicators

If equipped with a "push test" button, use a non-conductive rod to press the corresponding test button for circuit 1 or circuit 2, observe whether the corresponding output relay is excited (target on, contact status changes), and verify the integrity of the external wiring circuit.

For current type targets, it is necessary to ensure that the tripping circuit current is not less than 200mA, otherwise the target will not light up.

6.5 System cascading adjustment (actual locking effect)

Under simulated PT disconnection conditions (such as manually disconnecting one phase voltage), observe whether BE1-60 can issue a lockout signal before the overcurrent relay acts. An oscilloscope or event recorder can be used to capture the timing of actions, ensuring that the locking contact opens before the tripping contact.


Maintenance and Storage Suggestions

BE1-60 is a solid-state relay with extremely low daily maintenance requirements. It is recommended to conduct a complete functional test once a year to confirm that the setting values and action times are still within the specifications. If the relay is kept in stock for a long time, it should be powered on for 30 minutes every year to maintain the performance of the internal electrolytic capacitor and extend its service life. In case of malfunction, on-site dismantling and repair should not be carried out, and Basler Electric technical support should be contacted in a timely manner.

  • Siemens SINUMERIK 840D SL NCU 720.3B with PLC 317-3 PN/DP
  • Siemens 6AV6618-7GD01-3AB0 HMI Panel
  • OMRON F150-C15E-3 Vision Mate Controller PLC Overview
  • Mitsubishi MELSEC A Series PLC System A63P A3ACPU A616AD A68RD3
  • M68-2000 2 Axis Motion Controller SCE SERVO CNC
  • OMRON FZ-S2M PLC Camera Vision System
  • VISOLUX SLVA-4K PLC Module from Elektronik GmbH
  • OMRON CJ1M-CPU23 V2.0 PLC CPU Unit
  • ABB AI86-16CHF PCB Card 5761751-9 B Specifications
  • Allen-Bradley 100-D140ZJ22L Contactor Overview
  • Merlin Gerin PB80 PLC Rack
  • WEIR WE203 Power Supply PLC
  • OMRON NX-TS3102 Temperature Input Unit
  • Siemens 6ES7146-6FF00-0AB0 I/O Module
  • Fanuc A16B-3300-0057 Circuit Board
  • OMRON CJ1W-IDP01 Input Module
  • Siemens 6FX2007-1AD13 Handheld Unit
  • Gems EM54 PLC Module PCB
  • Beckhoff CX2030-0121 Embedded PC CPU
  • OMRON NJ301-1100 Machine Automation Controller
  • Biesse Rover CNI PLC 2153 030 7146.30 Numerical Control Module
  • OMRON CJ1W DA08V Analog Output Module
  • OMRON CS1D ETN21D Ethernet Module
  • Allen Bradley 1768 L43 CompactLogix Controller
  • Schneider TWDLMDA40DTK Twido PLC Module
  • Mitsubishi NZ2EX2B 60AD4 Analog Input Module
  • OMRON NS8 TV00B V2 Touch Display Panel
  • Mitsubishi AY71 CMOS TTL Output Module
  • OMRON C500 CPU11 E Processor Module
  • OMRON CJ1W PTS51 Temperature Input Module
  • Siemens 6SL3100-1DE22-0AA1 600V DC Supply
  • OMRON CJ1M-CPU23 PLC CPU 9‑Pin Serial
  • Schlumberger IMT4N 24‑250VAC 48‑230VAC PLC Timer
  • OMRON CJ1M-CPU22 PLC CPU Unit V2.0
  • Allen‑Bradley 2711P-B7C6D2 Touch Screen PanelView
  • ADSP-2181KST-160 Analog Devices DSP IC Specs
  • Schneider LC1F400 400A Contactor Specifications
  • Yaskawa SGDH-10DE-OY 1kW 400V Servo Drive
  • Schneider TM262L10MESE8T M262 PLC 5ns Inst
  • Mitsubishi AA104VJ05 10.4in LCD Panel Specs
  • Allen Bradley 1761-L32BWA MicroLogix 1000 PLC
  • Siemens 6ES7431-7KF00-0AB0 Analog Input Module
  • Allen Bradley 1769-OB16 Output Module
  • Siemens 6ES7131-1BL12-0XB0 Input Module
  • Beckhoff EP7041-3002 EtherCAT Box Module
  • Siemens RK7243-2AA30-0XB0 Communication Module
  • Siemens 4AM5742-8DD40-0FA0 Transformer
  • Siemens 3TK2834-1BB40 Safety Relay
  • Brother BAS 311 Sewing Machine Circuit Board
  • Yaskawa SGDH-10DE-OY Servo Driver
  • OMRON C60H C6DR DE V1 Sysmac PLC
  • MITSUBISHI ELECTRIC A2ACPU21 S1 CPU Module
  • ABB BAILEY INNPM12 Network Process Module
  • HONEYWELL 620 0073C IPC PLC Module
  • Mitsubishi 15050 PR02B PLC Circuit Board
  • SIEMENS 6SY7000 0AC37 Drive Control Module
  • OMRON TJ2 ECT16 Traxial EtherCAT Controller
  • GE Fanuc IC698PSD300D Power Supply Module
  • Texas Instruments Series 505 16 Position Base
  • OMRON YASKAWA SGDH 10DE OY Servo Drive
  • Allen‑Bradley 440G-MT Safety Interlock Switch Specs
  • Rubycon PD27A 24V 8A Power Supply Module
  • SK-H1-GDB1-F11D PLC Gate Driver Board Kit
  • VIPA 441-4UA14 451-4UA14 PLC Module Rack
  • Mitsubishi FX5U-80MT ESS PLC Controller Specs
  • Mitsubishi Q64TCRTN Temperature PLC Module
  • GE 1C31170G Rev10 PLC Circuit Board Module
  • Schneider TWDLMDA40DTK PLC Controller Module
  • Omron FQM1-MMA22 Motion Control Module Specs
  • OMRON CJ1W-NCF71 Position Control Unit Specs
  • Schneider TSXETY4103 Ethernet Module
  • Mitsubishi Q12PHCPU Process CPU
  • Yaskawa 3G3HV-A4022-CE AC Drive
  • Cincinnati Milacron 3-533-0669G Temperature Control Board
  • Allen Bradley 20AC030A3AYNANC0 PowerFlex 70 Drive
  • Siemens 6ES7314-6BG03-0AB0 CPU 314C-2 DP
  • Carrier 17EX54007903 PLC Module
  • OMRON CS1W-V600C12 ID Controller Module
  • Honeywell 51402755-100 PCB Card
  • Heidenhain ECN 113 Rotary Encoder
  • OMRON B7AM-8B16 I/O Terminal Block
  • Fanuc A06B-6110-H026 Power Supply Module
  • Schneider TSXETG3021 Ethernet Gateway
  • OMRON CS1W-CLK21-V1 Controller Link Unit
  • NP1W6406T-Z704 PLC I/O Module
  • OMRON CJ1W-DA08C Analog Output Module
  • Yaskawa 3G3HV-A4022-CE AC Drive
  • OMRON NB7W-TW01B CP1L-EL20DR-D Power Panel
  • OMRON C500-NC103-E Position Control Unit
  • Steag Hamatech PLC DCS Servo Control System
  • Siemens 6SN1123-1AA00-0DA1 Power Supply Module
  • GE IC693CHS391H CPU & AD693CMM301A PLC Module
  • Siemens 6FC5303-0AF23-1AA1 PLC Control Panel
  • Square D CM4000T PowerLogic Circuit Monitor J1 F16
  • Siemens 6FX5002-5DG10-1BA0 MOTION-CONNECT 500 Cable
  • Schmersal SRB324ST 101195504 Safety Relay 24V
  • Mitsubishi 15050-PR02A PLC Circuit Board Module
  • OMRON CQM1-AD041 Analog Input PLC Module
  • Beckhoff EL5042 EtherCAT PLC Terminal Module
  • OMRON C200HW-MC402-E Motion Control Unit
  • C36TC0UA1100 Industrial Temperature Controller
  • NL8048BC24 12 Industrial Control LCD Module
  • OMRON R88D Servo Drive and Motor System
  • OMRON CS1W CLK21 V1 Controller Link Module
  • OMRON YASKAWA R7M A20030 S1 D Servo Motor
  • SIEMENS 6AV2128 3KB06 0AX1 Unified Comfort Panel
  • Schneider Electric METSEPM8240 PowerLogic Meter
  • Advanced AMCI 1PLC 1 31F Programmable Limit Switch
  • ABB PM582 ETH Programmable Logic Processor
  • SIEMENS 6FC5110 0CB01 0AA0 CPU Control Board
  • Schleicher P03GS13A CPU Module
  • Siemens 6SN1123-1AA00-0BA1 Power Module
  • Mitsubishi A1S61PN Power Supply Module
  • Yaskawa CPS-IONB DC Power Supply Module
  • Siemens 6ES7215-2BD00 CPU 215-2
  • Mitsubishi A2ACPU MELSEC PLC System Kit
  • ProSoft 3150-MCM Communication Module
  • Mitsubishi OSE104ET Incremental Encoder
  • OMRON CJ1W-AD081-V1 Analog Input Module
  • Broadcom BCM5464A1KRB Quad Port Ethernet IC
  • Modicon M221-24IO TM221C24 PLC 24 PNP Transistor
  • Allen-Bradley 1321-3R160-B Line Reactor 3R160B
  • Beckhoff CX1020-0012 Embedded PLC Module Specs
  • Turck BL20-PF-24VDC-D Power Feed Module Specs
  • Siemens 6SY7000-0AC37 Power Supply Module
  • Yaskawa SGDH-10DE-OY 1kW 400V Servo Drive Specs
  • Omron 3G3SV-BB015-E 1.5kW 220V VFD Specs
  • Uni-Pro CPU91-PLC J 23.020167X Processor Module