Welcome to the Industrial Automation website!

NameDescriptionContent
XING-Automation
E-mail  
Password  
  
Forgot password?
  Register
当前位置:

Basler PRS 250 Synchronous Relay Maintenance and Replacement Guide

F: | Au:FANS | DA:2026-06-29 | 520 Br: | 🔊 点击朗读正文 ❚❚ ▶ | Share:

Basler PRS 250 Veri Sync Synchronous Relay Engineering Application and Field Troubleshooting Manual

In the grid connected system of generator sets, the synchronous relay is the last electrical barrier to prevent asynchronous closing. When the old Woodward SPM series or Beckwith synchronous inspection relays are gradually discontinued, while a large number of small and medium-sized generator sets below 2000KVA are still operating on site, Basler PRS 250 Veri Sync, as a CSA certified solid-state verification synchronous relay, has become a popular choice for replacement upgrades due to its wide voltage adaptation range, adjustable phase window, and extreme temperature tolerance. However, on-site engineers often face practical problems such as fuzzy parameter tuning, misjudgment of slip boundary, and improper matching of contact capacity. This article combines the official technical specifications of PRS 250, and systematically outlines a set of operable technical solutions from grid connection principles, parameter configuration, installation inspection to typical troubleshooting, to help maintenance personnel quickly restore system reliability during emergency replacement or annual maintenance.


The positioning and core functions of PRS 250 VeriSync

The Basler PRS 250 is a "verifying" synchronous relay, not an automatic quasi synchronous device. Its role is to passively allow - only when the voltage difference, frequency difference, and phase difference between the generator to be connected and the bus all fall within the preset "allow window", its output contacts close, allowing the operator to manually issue a closing command. This design balances operational flexibility (manual decision-making) and safety (relay control), making it particularly suitable for backup generators, emergency diesel units, and small hydropower stations.

The PDF document specifies that it is suitable for generators with a maximum capacity of 2000KVA, a frequency range of 45-65Hz, and covers two standard formats of 50Hz and 60Hz. This means that it can be used not only in the 60Hz system in North America, but also in the 50Hz power grid in Europe, Asia and other regions. It only needs to adjust the reference value in the frequency slip calculation.


Deep interpretation of key technical parameters

2.1 Dual range design of input voltage

Range 1: 65-140VAC (commonly used on the secondary side of 120V bus PT)

Range 2: 130-305VAC (commonly used for 240V or 277V busbars)

Two ranges are selected through internal jumpers or terminals, and on-site confirmation is required based on the actual PT ratio. If the 120V signal is mistakenly connected to the high range, it will cause the undervoltage detection to fail and the relay to be permanently locked; Otherwise, it may damage the input circuit. The document does not clearly indicate the terminal number, but the actual wiring diagram (refer to manual A90 88800 991) will indicate the "VOLTAGE SELECT" terminal, which must be strictly followed.

2.2 Voltage Acceptance Band

Fixed at 6.6% of the bus voltage. For example, when the bus voltage is 120V, the allowable voltage range for the generator is 120V ± 7.92V (i.e. 112.08V~127.92V). This value is not adjustable, unlike some relays that can be set to 5% to 10% of the model. Engineers need to evaluate whether the voltage fluctuation on site exceeds this limit. If the difference between the no-load voltage of the generator and the bus exceeds 6.6%, the relay will never issue a permission signal - at this time, the voltage regulator (AVR) setting or PT accuracy should be checked.

2.3 Phase Angle Adjustable Window

Adjustable range: 0 ° to ± 20 ° (with reference to zero crossing of bus voltage). The actual set value depends on the time delay of the circuit breaker closing mechanism. For example, if the closing coil action time is 100ms and the slip frequency is 0.2Hz (corresponding to a period of 5s), the phase angle changes by about 7.2 ° within this 100ms, so the window can be set to ± 10 °. The PDF indicates that the phase angle value is the static nominal value under "Incoming and bus 120V 60Hz, 0 ° Hz slip", and the actual forward angle under dynamic slip needs to be compensated separately.

2.4 Maximum Slip Rate Max

0.5Hz - The frequency difference between the parallel machine and the bus shall not exceed 0.5Hz. This is the maximum slip allowed to be captured by the relay. If this value is exceeded, the relay determines that the synchronization condition is not met and rejects the output. During on-site debugging, it is necessary to control the steady-state frequency difference of the governor within this range. It is usually recommended to set the target slip at 0.2-0.3Hz with margin.

2.5 Rated value of output contacts

SPDT (Single Pole Double Throw) form

DC (resistive load): 1.0A @ 125VDC

Communication: 7.5A @ 208VAC

Note that the DC rated value is significantly lower than the AC, as the DC arc is difficult to extinguish. If driving an intermediate relay (such as Mitsubishi or Omron's DC coil), it is necessary to confirm that the coil current is less than 1A, otherwise an intermediate amplifier or solid-state relay needs to be installed. If used to directly drive the closing coil (high current), an external contactor must be connected.

2.6 Environmental and Mechanical Tolerance

Working temperature: -40 ° C to+70 ° C (suitable for outdoor cabinets and extremely cold areas)

Vibration: 1.3G (5-26Hz) to 5G (52-260Hz)

Impact: 15G (in any direction)

Size: 7.12 "x 7.10" x 3.31 "(approximately 181mm x 180mm x 84mm), standard panel mounting or DIN rail (requires adapter bracket)

Weight: Net weight 6.5 pounds (approximately 2.95kg), relatively heavy, pay attention to the load-bearing capacity of the guide rail during installation.


Typical application scenarios and replacement compatibility

3.1 Replace old style electromechanical synchronous relays

Many old distribution boards use GE type IJS or Westinghouse type ANL synchronous relays, which have low precision, easy contact wear, and difficult tuning for electromagnetic products. PRS 250 provides more stable solid-state logic and adjustable phase angle and slip limits, but it should be noted that the original relay may include undervoltage/overvoltage protection function, while PRS 250 only allows voltage (6.6%) and does not have independent undervoltage lockout - if undervoltage protection is required, an additional undervoltage relay needs to be configured.

3.2 Replace Woodward 2301 series synchronization module

The synchronization check function that comes with speed controllers such as Woodward 2301 is often integrated into the control card. Once the card is discontinued, the separated synchronous relay becomes an economical alternative. At this point, it is necessary to connect the "allow" contact of PRS 250 in series into the closing circuit, and separate the "speed increase/decrease" signal of the governor from the relay, without interfering with the speed control action - PRS 250 is only used for passive verification.

3.3 Coordination with automatic quasi synchronization device

For situations where automatic quasi synchronization has been configured (such as Basler DECS-250 excitation system), PRS 250 can be used as a backup redundancy and connected in series in the closing circuit to achieve dual safety. Even if the automatic device mistakenly closes due to software failure, PRS 250 can still check again based on the hard wired parameters.

On site installation and parameter tuning steps

4.1 Key points for wiring inspection

Voltage input: Confirm that the secondary side voltage of the generator PT corresponds to the terminal (G-GEN) and the bus PT corresponds to the terminal (B-BUS). The same phase must be used (such as phase A and phase A), otherwise the phase difference remains constant at 120 ° or 240 °, and the relay will always close.

Common terminal: The voltage common terminal (COM) must be connected to the neutral points of two PTs and ensure equal potential.

Output contact: Confirm that the contact capacity is sufficient based on the type of closing circuit (AC or DC). If it is a DC operation, it is recommended to use a "normally open" terminal connected in series between the closing button and the closing coil.

Shielding and grounding: The voltage signal line uses shielded twisted pair cables, and the shielding layer is grounded at one end to the control cabinet ground bar to avoid high-frequency interference affecting zero crossing detection.

4.2 Phase angle window setting method

When there is no dedicated phase meter, the "anti synchronization" method can be used:

Make the generator and bus voltage roughly equal, with a frequency slightly higher than the bus (forward slip);

Adjust the phase potentiometer to the minimum (0 °), observe the relay indicator light (if any) or use a multimeter to measure the contact continuity;

When the frequency difference gradually decreases to near zero, if the contact is attracted near the voltage zero crossing, it indicates that the phase window is correct. If a larger advance amount (compensating for circuit breaker time) is required, gradually increase the angle until the impact current is minimized when closing.

4.3 Slip frequency verification

Measure the generator frequency fG and bus frequency fB using a frequency meter, and the difference must be less than 0.5Hz. If it is higher than this value, adjust the steady-state speed regulation rate of the prime mover governor (such as changing the integration time of the Woodward actuator). If the slip cannot be reduced on site, it can only be replaced with a relay that supports higher slip (such as 1Hz), but PRS 250 does not have this option.

4.4 Voltage matching adjustment

If the voltage difference between the generator and the bus exceeds 6.6%, the voltage setpoint of the AVR needs to be adjusted (such as the "VOLT" potentiometer of Basler DECS-100). Note that the bandwidth is a percentage based on the bus, and when the bus fluctuates, the allowed absolute deviation also changes synchronously, with good dynamic tracking.


Common fault phenomena and systematic troubleshooting

Fault 1: The relay has never closed (allowing the signal to remain disconnected)

Possible reasons:

Voltage deviation exceeds 6.6% (check two PT output values and measure with a multimeter in AC mode)

Frequency difference greater than 0.5Hz (check the speed regulator and observe the fluctuation of the frequency meter)

Phase angle window set too small (increase to ± 15 ° for trial operation)

Input common terminal not connected or PT polarity reversed (resulting in a phase difference of 180 °, theoretically exceeding the maximum ± 20 °)

Solution process: First, measure whether the bus side voltage is within the input range (such as 120V ± 10%), and then measure the generator side voltage; Use an oscilloscope to check the phase difference between the two waveforms and confirm if it is within the set window.

Fault 2: Relay frequently engages and releases (shaking)

Possible reason: The slip frequency is close to the upper limit of 0.5Hz and fluctuates, causing the relay to switch back and forth at the boundary; Or voltage fluctuations cause the difference to oscillate around 6.6%.

Countermeasure: Reduce the slip to 0.2-0.3Hz and increase the phase angle window appropriately (such as from 10 ° to 15 °) to increase the hysteresis margin. Additionally, check if the power supply is pure and add an isolation transformer if necessary.

Fault 3: A huge surge current occurs after closing the circuit

Root cause: Although the relay is closed, the actual phase angle at the moment of closing exceeds the tolerance - because there is a delay from the relay action to the closure of the main contact of the circuit breaker (including the action time of the intermediate relay and the mechanical time of the closing coil). If the total delay is 150ms and the slip is 0.3Hz (corresponding to a phase angle change of about 16.2 °), the phase angle window needs to be set to 20 ° and the slip should be kept below 0.2Hz.

Corrective measures: Use an oscilloscope to record the time difference between the relay closing contact signal and the circuit breaker auxiliary contact signal, infer the actual closing angle, and adjust the window.

Fault 4: Relay failure at low temperature (environment below -20 ° C)

PRS 250 is rated up to -40 ° C, but if moisture freezes inside the control cabinet, it may affect terminal insulation or cause potentiometer jamming. It is recommended to install a heater inside the cabinet in cold regions and set the temperature controller to+5 ° C.


Life management and spare parts replacement solutions

6.1 Normal lifespan

Solid state relays have no mechanical wear and tear, and their expected lifespan mainly depends on the aging of internal electrolytic capacitors and optocouplers. In general industrial environments, no replacement is required for 15-20 years. But it is recommended to conduct a functional test every 5 years: simulate various out of limit conditions to confirm that the relay is correctly locked; Measure whether the output voltage and phase angle setting values drift (the potentiometer may change slightly due to vibration).

6.2 Direct Replacement Models

If PRS 250 is discontinued, a new generation of synchronous inspection relays from Basler can be considered, such as Basler SCP-250 (with a wider slip range of 0.1-2Hz) or Basler BE1-25 (digital, programmable). However, when replacing, attention should be paid to:

The definition of the wiring terminal may be different and needs to be re crimped;

Digital relays require an external auxiliary power supply (PRS 250 self powered), while BE1-25 requires 24/48/125VDC power supply.

The software settings interface may increase debugging complexity, and maintenance personnel need to be trained.

6.3 Precautions for Purchasing in the Second hand Market

Considering that PRS 250 is no longer a mainstream new product, some suppliers offer "refurbished/inventory" products. When purchasing, the following should be requested:

Factory test report (including verification data for phase angle, voltage, and frequency)

Inspect the appearance for signs of erosion

Is the mechanical stop of the potentiometer intact (to avoid internal open circuit)


Safety operation and compliance reminder

CSA certification indicates that the relay complies with relevant electrical standards in Canada and the United States, but it still needs to follow local regulations (such as NFPA 70E) for live working when in use.

As the relay does not have a built-in fuse, a 1A slow melting fuse should be added to the external voltage input circuit to prevent the spread of faults in case of PT short circuit.

If the output contact is used for DC inductive loads (such as contactor coils), it must be connected in parallel with a freewheeling diode (DC) or an RC absorption circuit (AC), otherwise it may cause contact adhesion or internal semiconductor damage due to back electromotive force.

  • Bonfiglioli ACT401-19A Frequency Inverter
  • Bonfiglioli C102PP71 Gear Motor 13.4:1
  • Bonfiglioli C312 P P90 Speed Reducer
  • VEM K21R 71 G 4 Motor with Bonfiglioli VF44
  • Bonfiglioli C31 3 P P63 PV Bevel Gear Reducer V5
  • Bonfiglioli WR75UD28150P71B5B3 Gearbox
  • Bonfiglioli ACT401-13FA Frequency Inverter
  • Bonfiglioli VF62/P Worm Gearbox 38:1
  • Bonfiglioli ME210124001Y C Helical Gearbox
  • Bonfiglioli VF63PIP90BI4 Gearbox
  • Bonfiglioli ACT 401-19A Frequency Inverter
  • Bonfiglioli C102PP71 Variable Speed Gearmotor
  • Bonfiglioli C312 P P90 Reducer with Clutch
  • Bonfiglioli VF44 F1 10 Gearmotor with VEM Motor
  • Bonfiglioli C31 3 P P63 PV V5 Reducer
  • Bonfiglioli WR75UD28150P71B5B3 Gearbox
  • Bonfiglioli ACT401-13FA Frequency Inverter
  • Bonfiglioli VF 62/P Worm Gearmotor 38 to 1
  • Bonfiglioli ME210124001Y Inline Gearbox
  • Bonfiglioli VF63PIP90BI4 Worm Gearbox
  • Bonfiglioli VF86FC256 Worm Gearbox 1010B03004
  • Bonfiglioli VF44F1 Gearmotor 0.43kW 460V
  • Bonfiglioli W 75 UF1 D30 P80 B14 Gearbox i=100
  • Bonfiglioli VF63NP80B5 Worm Gearbox
  • Bonfiglioli 300R3133FPP80POG0A Gear Reducer
  • Bonfiglioli VF49F1N56C Gearbox
  • Bonfiglioli Trasmittal 300L19 Gearmotor with MEZ UD 1104 Motor
  • Bonfiglioli BCS30 Permanent Magnet Motor with Encoder
  • Bonfiglioli BN56B4 Gearmotor with VF30 Reducer
  • Bonfiglioli VF44 Gearbox 100480150
  • Bonfiglioli VF63PIP90B14 Gearbox
  • Bonfiglioli 830420150 BN63A4 230/400-50 IP55 CLF B14 with VF30F2 P63B14B3-I40
  • Bonfiglioli BN63A2 Motor
  • Bonfiglioli VF44 ALP63B5 Gearbox
  • Bonfiglioli A102 UR P80 Gearbox
  • Bonfiglioli MP 105 2 16 STD 95A1 CD 19 S1 OR SB KE Planetary Gearbox
  • Bonfiglioli T56BN/4 Motor
  • Bonfiglioli 8E20020594-M285018 Motor
  • Bonfiglioli VF49 V P71 B5 Gearbox
  • Bonfiglioli X VFR49 L1 FA1 180 P63B5 B3 Gearbox
  • Bonfiglioli W63U7P90B14V6 Right Angle Gear Reducer
  • Bonfiglioli VF/W30/63UFC2 Gear Reducer i=168
  • Bonfiglioli VF44 Gear Reducer 100480150
  • Bonfiglioli ACU 201-07 FA Frequency Converter
  • Bonfiglioli BN-80B-4 Motor with VF63 Gearbox 38:1
  • Bonfiglioli MVF 49 Gear Reducer for Servo Motor
  • Bonfiglioli ACT 400-034 A Frequency Inverter 11kW
  • Bonfiglioli SYN10-S-220-03-AF AC Drive 0.5HP
  • Bonfiglioli LC 090 1 7 STD FM CD 19 KE Gearbox
  • Bonfiglioli TQFK070350GR80A1CD Gear Unit
  • Bonfiglioli BN 80 B6 FD Three Phase Motor
  • Bonfiglioli W63U Worm Gear Reducer
  • Bonfiglioli 830G2310M-B048052 Gear Motor
  • Bonfiglioli VF49P128P71B5B3 Worm Gearbox
  • Bonfiglioli W75UD30719/140B3 Worm Gearbox
  • Bonfiglioli VF49F17HSB3 Worm Gearbox
  • Bonfiglioli C12 2P 20.6 P90 B3 Gearbox
  • Bonfiglioli BN80B4 623136 Geared Motor
  • Bonfiglioli 4APC3-4 9142882 Geared Motor 0.18 kW
  • Bonfiglioli W86 80/90-B5 Worm Gear Reducer 20:1
  • Bonfiglioli ACU 210-07 1 FA PLC Peripheral Module
  • Bonfiglioli MVF44/F Worm Gearbox
  • Bonfiglioli W63U Worm Gear Reducer
  • Bonfiglioli BN63A2 Electric Motor
  • Bonfiglioli BN 132 M B 4 Electric Motor 9.2kW
  • Bonfiglioli VF49 L1 P1 P63B5 Worm Reducer i=45
  • Bonfiglioli C413 P S2 7717/1000 Gearmotor 1.5kW
  • Bonfiglioli VF49F1P63B5B3 Worm Gearbox
  • Bonfiglioli BTD5-1870-05-400-ENC8A Servo Motor
  • Bonfiglioli ACU401-03FA Frequency Inverter
  • Bonfiglioli MVF63/N Gearbox with AEG Servomotor
  • Bonfiglioli BN80A4 Gearmotor VF49L1P1P80B14
  • Bonfiglioli VFR 72/FC2 Gear Reducer
  • Bonfiglioli W R 86 U 120 Gearbox Assembly
  • Bonfiglioli W 75 U 30 Gear Reducer
  • Bonfiglioli W R 86 U 120 P80 B5 V5 Gearbox
  • Bonfiglioli RAO 50/DC Gearbox
  • Bonfiglioli VF49 F1 P63B5 Gearmotor with SPZ MS6324
  • Bonfiglioli X_LC 090 Planetary Gearbox
  • Bonfiglioli A302 UH35 P90 Gearbox
  • Bonfiglioli VF63FCHS Worm Gearbox 103100390
  • Bonfiglioli VF 44 P63 B14 Gearbox M00480210008
  • Bonfiglioli MPD1006S0006 Precision Planetary Gearbox
  • Bonfiglioli VF49F1N56C Worm Gearbox
  • Bonfiglioli TR G 105 3 20 STD Planetary Reducer
  • Bonfiglioli VFR49P1P63B5 Worm Gearbox
  • Bonfiglioli WR 86 U 120 P80 B5 V5 Gearbox 2G30013944
  • Bonfiglioli BRA 400-060 BF2 Brake Chopper
  • Bonfiglioli VF49P P71B5 Worm Gearbox
  • Bonfiglioli C402 P VG1 Gear Speed Reducer 31.4:1
  • Bonfiglioli ISMET LCVT050 DK308/50 Line Reactor
  • Bonfiglioli C 22 2 F GR063 Gearbox
  • Bonfiglioli C31 3 P P63 PV V5 Reducer
  • Bonfiglioli CM-485 T Communication Module
  • Bonfiglioli W75UF1D30P90B5 Gearbox
  • Bonfiglioli BN63 B4 VF49 Gearmotor 0.18kW
  • Bonfiglioli ACT 400-004 FA Frequency Inverter
  • Bonfiglioli W110U100P90B5B3 Worm Gearbox
  • Bonfiglioli SYN10 T 400 05 AF Inverter
  • Bonfiglioli MP080.1.4.15.16.40.80.100 Gearbox
  • Bonfiglioli SYN10S Inverter
  • Bonfiglioli VF44L2P160 Gearmotor
  • Bonfiglioli W 86 U 40 P90 B5 B3 Gear Reducer
  • Bonfiglioli BTD5-1870-05-400 Servomotor
  • Bonfiglioli MP 080 2 2C Gearbox with BLDC Motor
  • Bonfiglioli MP080.1.10 Planetary Gearbox
  • Bonfiglioli C212PHS Reducer
  • Bonfiglioli MVF 49F1 Gearbox with ICME T71B4
  • Bonfiglioli VF 49 v P71 B5 Gearbox
  • Bonfiglioli VF 44 P1 Gearmotor
  • Bonfiglioli C 22 2 NP 6.1 Helical Gearbox
  • Bonfiglioli F203 316.9 Gearbox with Kaiser Motor
  • Bonfiglioli SYN10 S 220 07 AF Frequency Inverter
  • Bonfiglioli 301L251.8-HC-P90 Gearbox 1/51.8
  • Bonfiglioli ACT401-25A Frequency Inverter
  • Bonfiglioli W75 U D30 30 P90B14 B3 Worm Drive
  • Bonfiglioli 830G2310M-307638 Motor
  • Bonfiglioli C112-P-P90 Inline Gearbox i=6.2
  • Bonfiglioli SYN10-S-220-03-AF AC Drive
  • Bonfiglioli VFR49 A HS Worm Drive i=180 B3
  • Bonfiglioli ACT 401-29 A AC VFD Drive 22kW
  • Bonfiglioli VF49PIP63B14 Gearbox
  • Bonfiglioli ANG 410-18 2 FA Inverter
  • Bonfiglioli GVX2000-7.5-T Converter
  • Bonfiglioli EM-ENC-02-24 Optical Module
  • Bonfiglioli ACT 401-33 A VFD Drive
  • Bonfiglioli MVF 49F1 Gearbox with ICME T71B4
  • Bonfiglioli BN112M4 Motor