4.3 Fault 2: Relay engages after voltage establishment, voltage attenuates again
Firstly, check if R1 and its circuit are faulty
For brushed excitation machines: check if input terminals 3 and 4 have power
If ineffective, replace or repair the regulator
4.4 Fault 3: Voltage too high and R1 cannot be controlled
Common causes and troubleshooting:
Induction terminals E1/E2/E3 have no voltage → Repair wiring
External R1 short circuit → Replace R1
Induction transformer tap selection error → switch to the correct tap
K1 relay malfunction → replace
All are invalid → Replace the regulator
4.5 Faults 4&5: Voltage too high/too low but R1 can be controlled
Check if the tap of the induction transformer is correct
Check if R3 (voltage range setting) is set too high or too low
Check if R1 resistance matches (175 Ω nominal)
Check if the induction wiring is correct
Check the accuracy and connection of the voltmeter
4.6 Fault 6: Poor adjustment accuracy
Confirm that the input voltage is correct
Confirm that the voltmeter is connected to the same sensing point of the regulator
Check if the waveform is severely distorted (the regulator measures the average value, and the instrument may measure RMS)
Check if the position of the UNIT/PARALLEL switch matches the operating status
For three-phase sensing: check if the load is severely unbalanced
Check the speed of the prime mover
4.7 Fault 7: Voltage instability (oscillation)
Confirm that the generator frequency is stable (unstable speed controllers are a common cause)
Confirm that R4 has not been adjusted to an excessively counterclockwise position
Important: If the no-load magnetic field voltage is too low (SR4A<10V), a resistor can be connected in series to increase the output of the regulator and enhance the stable signal (see example in section 3.2)
4.8 Fault 8: Slow voltage recovery after load change
Confirm the correct model for application
Check R4 settings
Check the stability of the speed regulator
4.9 Faults 10&11: Parallel related issues
Reactive droop cannot be obtained:
Check if R25 sliding arm is adjusted to the minimum position
Confirm that parallel CT can provide 3-5A secondary current
Confirm that terminals 1-2 are not short circuited by the UNIT/PARALLEL switch
Uneven distribution of reactive power (with circulation):
Check R25 settings
Polarity check: CT polarity error is the most common cause of uneven reactive power distribution
Phase check: Confirm that the CT is installed on the correct phase line (three-phase sensor: the phase corresponding to E2)
All parallel units should have the same type of sensing (single-phase or three-phase), otherwise R25 compensation needs to be adjusted
All ineffective → Repair/replace regulator
5. Maintenance and operational testing
5.1 Preventive maintenance
Regularly inspect and clean the regulator to keep it dust-free and dry
Check if all wiring is securely fastened
5.2 Operational Verification Testing
A light bulb can be used as a simulated load to quickly verify the basic functions of the regulator (see Figure 5-1 in the manual):
Connect the induction transformer to the corresponding voltage (SR4A: 120V; SR8A: 240V)
R4 counterclockwise to maximum
Connect according to Figure 5-1 in the manual, the bulb is 120V/≤ 300W
Adjust R1 to maximum resistance
Power on: The light bulb should flash instantly and then turn off
Slowly reduce R1 resistance: The bulb should reach full brightness (before reaching minimum resistance)
Near the adjustment point: minor changes in R1 should cause the bulb to turn on/off
