Introduction: A Reliable Choice for High Performance Static Excitation Control
In the field of excitation control for generator sets, Basler Electric's SSR series static voltage regulators have become the preferred solution for many power generation projects due to their robust packaging design, excellent regulation accuracy (± 0.25%), and wide power coverage range. This series includes three models with different power levels - SSR 32-12 (32 Vdc/12 A), SSR 63-12 (63 Vdc/12 A), and SSR 125-12 (125 Vdc/12 A), which are compatible with brushless generator sets of different capacities.
One of the most prominent technical features of the SSR series is the provision of selectable V/Hz or 2V/Hz underfrequency compensation characteristics. The 2V/Hz characteristic is specifically designed for large motor starting and sudden load scenarios - a larger voltage drop means that the prime mover can withstand a smaller kW load, resulting in faster speed recovery. This design concept reflects Basler's profound accumulation in optimizing the dynamic performance of generator sets.
This article will be based on the official technical manual, providing a complete and professional practical guide for on-site engineers from hardware installation, frequency configuration, parallel compensation to systematic troubleshooting.
1. Product Overview and Technical Specifications
1.1 Model and Power Level
The core difference between the three models in the SSR series lies in the output power level:
Model Continuous output Strong excitation output (1 minute) Minimum magnetic field resistance Input power
SSR 32-12 32 Vdc / 12 A 50 Vdc / 20 A 2.5 Ω 700 VA
SSR 63-12 63 Vdc / 12 A 100 Vdc / 20 A 5.0 Ω 1,200 VA
SSR 125-12 125 Vdc / 12 A 200 Vdc / 20 A 10.0 Ω 2,400 VA
Output topology difference: SSR 63-12 and SSR 125-12 use full wave rectification output, while SSR 32-12 uses half wave output. This difference needs special attention when selecting an external power isolation transformer - the transformer matched with SSR 32-12 must be compatible with its half wave DC output characteristics.
1.2 Key Performance Parameters
Adjustment accuracy: from no load to full load, ± 0.25%
Thermal stability: within a temperature range of 50 ° C, ± 0.5%
Voltage building: SSR 32-12/63-12 can build voltage from a residual voltage of 6 Vac; SSR 125-12 requires 12 Vac
Frequency range: Input power 50-240 Hz; Sensor 50/60 Hz
Working temperature: -40 ° C to+70 ° C
Storage temperature: -40 ° C to+85 ° C
1.3 Overexcitation protection characteristics (Figure 1-3)
The SSR series is equipped with two-stage overexcitation shutdown protection:
Inverse time limit overexcitation: When the regulator output reaches 95% or more of the rated strong excitation voltage and lasts for more than 60 seconds, it triggers shutdown
Instantaneous overexcitation: When the output exceeds 130% of the rated strong excitation voltage, it will turn off instantly (<1 second)
This protection mechanism effectively prevents damage to the generator and exciter due to long-term overexcitation.
2. Key technical points for installation and wiring
2.1 Physical Installation
The SSR regulator can be installed in any direction, but for optimal heat dissipation, it is recommended to install it vertically. Its sturdy packaging design allows for direct installation on the generator set (capable of withstanding 5G vibrations and 15G impacts). The installation hardware should be selected based on the expected vibration and impact levels during transportation and operation.
2.2 Spike Suppression Module
This is a crucial but easily overlooked step in the installation process. When the input power comes from a high impedance source (such as a power isolation transformer or PMG), its inductance may generate voltage spikes sufficient to damage the output stage of the regulator. The peak suppression module is provided with the regulator and must be installed in these application scenarios.
2.3 Induction voltage tap setting (extremely important)
The SSR internal induction transformer provides multiple tap positions of 120/240/480/600 Vac, which must match the actual generator voltage.
Three phase sensing wiring:
TB2-E1 → Phase A
TB2-E2 → B phase (select corresponding voltage tap)
TB2-E3 → C phase (select the same tap as E2)
The jumper between TB1-21 and TB1-22 must be removed
Single phase sensing wiring:
Jumper must be installed between TB1-21 and TB1-22
TB2-E1 → Phase A
TB2-E3 → C phase (select corresponding voltage tap)
Engineering Tip: Incorrect induction tap settings are the most common cause of high or low voltage. Before wiring, it is necessary to confirm the actual output voltage of the generator and select the correct tap.
2.4 Frequency selection and compensation slope (core function)
The SSR series offers two frequency compensation slopes and two frequency ranges:
Frequency range selection:
50 Hz system (48-53 Hz underfoot): Install jumper between TB1-27 and TB1-30
60 Hz system (54-63 Hz underfoot): Remove the jumper between TB1-27 and TB1-30
Compensation slope selection:
V/Hz (1x slope): Install jumper between TB1-29 and TB1-30
2V/Hz (2x slope): Remove the jumper between TB1-29 and TB1-30
The engineering value of 2V/Hz mode: At the moment of starting the large motor, the generator voltage drops significantly, and the 2V/Hz characteristic makes the voltage drop faster and more, thereby reducing the kW load perceived by the prime mover and accelerating speed recovery. This is particularly crucial for generator sets operating on isolated islands.
2.5 Input power wiring (pay attention to polarity and phase)
SSR 32-12/63-12:90-153 Vac, Terminal TB2-3 is connected to phase C, and TB2-4 is connected to phase B
SSR 125-12:170-305 Vac, Terminal TB2-3 is connected to phase C, and TB2-4 is connected to phase B
Key safety warning: Without using a power isolation transformer, any grounding point in the magnetic field circuit and another grounding point in the generator output may cause damage to the regulator.
Frequency matching:
Direct connection to 50/60 Hz generator output: Install jumper between TB1-25 and TB1-30
Connect special power sources such as PMG (120-240 Hz): Remove the jumper between TB1-25 and TB1-30
2.6 Remote Voltage Regulating Potentiometer
Use the 5 k Ω, 2 W potentiometer provided by the regulator
If only internal voltage regulation is used, install jumper wires between TB1-6 and TB1-7
In high noise environments, the shielding layer should be connected to TB1-30

3. Parallel compensation: detailed explanation of Droop and Cross Current
3.1 Reactive Droop Compensation
Parallel CT installation in phase B (for three-phase sensing) or non sensing phase (for single-phase sensing)
CT should provide 3-5 A secondary current at rated load
Adjust the droop amount through DROOP ADJUST control on the front panel
When running alone, the UNIT/PARALLEL switch should be short circuited to the CT secondary to prevent the injection of droop signals
3.2 Reactive Differential/Cross Current Compensation
Connect the CT secondary of all parallel units in series to form a closed loop (see Figure 2-6 in the manual)
When the currents of each generator are proportional and in phase, the CT signals cancel each other out, and the system voltage does not sag
Key limitation: Cannot be used in parallel with an infinite power grid (Utility)
3.3 CT polarity (key factor determining the success or failure of parallel connection)
CT polarity errors can lead to:
When parallel connected, the reactive power distribution is severely uneven, resulting in circulating current
Excessive current surge during parallel connection may cause tripping
ABC phase sequence: Connect according to Figure 2-3 to 2-5 in the manual
ACB phase sequence: CT secondary leads must be interchanged
4. Debugging and initial operation process
4.1 Pre operation inspection
Confirm that all wiring is correct and secure (refer to manual figures 2-3 to 2-5)
Confirm that the induced voltage tap matches the actual voltage
Confirm that the frequency selection and compensation slope jumper are correct
Confirm that the input power voltage is correct and the fuse is intact
Confirm that the voltage shutdown switch (if any) is in the off position
4.2 No load start-up debugging
Start the prime mover to the rated speed
Close the voltage cutoff switch (if any) and apply excitation
Observe the generator voltage - the following situations may occur:
Possible causes and measures for handling the phenomenon
Overvoltage (+20% or more): If the induction tap is too low or the regulator fails, immediately disconnect the excitation and check the tap
Without voltage, insufficient residual magnetization is established to execute field strength flashing (see section 4.3)
Under voltage (-15% or more), if the induction tap is too high or the speed is insufficient, check the tap and speed
After the voltage is established, the external potentiometer circuit will collapse. Check the TB1-6/7 jumper or potentiometer for an open circuit
Improper adjustment of voltage oscillation (Hunting) STAB (see section 4.4)
Adjust the front panel VOLT control to the rated voltage
Apply load and verify adjustment accuracy ± 0.25%
4.3 Field Flashing
When the residual voltage of the generator is below 6V (SSR 125-12 is below 12V):
The prime mover is stationary
Connect a non grounded DC power supply (not exceeding 12V) to F+(positive pole) and F - (negative pole) through a 25-30 Ω current limiting resistor
Hold for about 3 seconds before disconnecting
Disconnect the input power of the regulator, start the prime mover, and measure the output voltage of the generator
If it is greater than 6V, the voltage should be able to establish itself; Stop the prime mover and reconnect the input power supply
Safety warning: Do not perform flashing operations while the generator is rotating.
4.4 Stability adjustment of STAB
The default position for the STAB factory is clockwise (CW), which ensures stability but has a slow response:
Counter clockwise (CCW) rotation → response acceleration
Excessive CCW → voltage oscillation
Correct method: Rotate CCW until it starts oscillating, then adjust CW until it just crosses the oscillation point
System voltage instability is most likely to occur when there is no load.

5. Troubleshooting: Systematic diagnostic process
5.1 Fault 1: Voltage cannot be established
Corrective measures for step inspection items
Perform field strength flashing when residual voltage<6V (or 12V)
2. Voltage shutdown switch open/fuse blown close switch/replace fuse
3. The prime mover does not reach the rated speed and adjusts the speed
4 Generator output short circuit or overload elimination short circuit/load reduction
5 External R1 (TB1-6/7) wiring or device fault repair/replacement wiring or potentiometer
6. Short circuit TB1-6 and TB1-7 with jumper wires for testing. If normal, replace the external potentiometer; If the pressure is still not built, replace the regulator
5.2 Fault 3: Voltage too high and R1 cannot be controlled
Safety warning: Running in this state for more than 5-10 seconds may damage the generator and exciter, and a shutdown switch should be used to shorten the power on time.
Rotate VOLT to the maximum CCW - if the voltage drops to normal, recalibrate
Check if TB2-E1/E2/E3 has sensing voltage and if the tap is correct
Replace the internal induction transformer (BE21755001)
Replace electronic module
5.3 Fault 4: Voltage too high but R1 can be controlled
Rotate VOLT to the most CCW position
Check the sensing voltage and tap
Single phase sensing: Confirm that a jumper has been installed between TB1-21 and TB1-22
Check if the voltmeter is functioning properly
Replace the internal induction transformer
Replace electronic module
5.4 Fault 5: Voltage too low but R1 can be controlled
Confirm that the prime mover has reached the rated speed
Check the sensing voltage and tap
Three phase sensing: Confirm that there are no jumper wires between TB1-21 and TB1-22
Check the voltmeter
Key inspection: Observe the front panel indicator light of the ENER FREQ - if it lights up and the frequency is correct, adjust the FREQ control counterclockwise until the indicator light goes out, and then adjust it to normal voltage
Replace electronic module
5.5 Fault 6: Poor adjustment accuracy
Confirm that the regulator output limit has not been exceeded when fully loaded (see Table 1-1)
Confirm that the input power supply of TB2-3/4 is correct
Confirm that the voltmeter is connected to the same sensing point of the regulator
Check waveform distortion (regulator measures average value, instrument may measure RMS)
Confirm that the position of the UNIT/PARALLEL switch is correct
Three phase sensing: check if the load is balanced
Check if the indicator light of the Underer FREQ lights up when unloaded/fully loaded - if it lights up, adjust the FREQ or increase the speed
Replace electronic module
5.6 Fault 10: Uneven distribution of reactive power
Confirm that the parallel CT can provide 3-5A secondary current under rated load
Confirm that TB2-1 and TB2-2 are not short circuited
Check CT polarity and wiring according to Section 3 (polarity errors are the most common cause)
6. Maintenance and operational testing
6.1 Preventive Maintenance
Regularly check if the wiring is secure
Keep the heat sink and casing clean and free from dust accumulation
6.2 Operation verification test (see Figure 4-1 in the manual)
Using a light bulb as a simulated load to quickly verify the function of the regulator:
Rotate the TAB to the most CCW position
Connect according to Figure 4-1, the bulb is 120V/≤ 300W
Adjust the voltage regulator potentiometer to the maximum resistance
Connect the power - the light bulb may flash instantly
Slowly reduce resistance - the bulb should reach full brightness
Near the adjustment point, a slight change in R1 should cause the bulb to turn on/off
STAB adjustment should affect the on/off time of the light bulb
