4.1 Standard Wiring Comparison
For a typical Y/d1 transformer (Beckwith standard is Wye/Delta ac), if the CT is Wye wired, select the standard mode:
Transformer wiring: W1=Wye, W2=Delta ac
CT wiring: W1=Wye, W2=Wye
The relay automatically calculates a 30 ° phase shift and amplitude compensation (1/√ 3). If the CT wiring is Delta, it is necessary to select Inverse or different phase shifts accordingly.
4.2 Polarity rules
The CT secondary polarity terminal (usually marked as "·" or "S1") should be connected to the "+" polarity terminal of the relay input terminal (as shown in Figure 5-9 of the manual, if the CT polarity terminal on the generator side is facing the system, then the relay terminal should be connected according to the marking). If the polarity is reversed, you can choose "Inverse" wiring correction inside the relay or adjust the external wiring.
4.3 On site polarity verification (before commissioning)
View the phase current, differential current, and zero sequence current of each winding through the "Status" menu on the HMI
When loaded, the amplitude of the phase current of each winding should be close to the rated value (converted according to CT ratio), and the phase should comply with the wiring relationship.
Fundamental differential current should be close to zero (usually<0.05 pu). If there is a significant differential current, it indicates that the CT polarity or transformation ratio is set incorrectly.
Negative and zero sequence currents should also be close to zero (balanced load).
If the differential current is large, the CT transformation ratio, wiring settings, or waveform can be checked using waveform recording.

On site functional testing (sampling)
Chapter 6 of the manual provides detailed testing procedures, and the following are quick verification methods for commonly used functions (requiring a relay protection tester):
5.1 Differential 87T minimum operating current test
Set the CT input of one winding to zero and apply a single-phase current to the other winding, slowly increasing until 87T is activated.
The action value should match the set Pickup (pu), and attention should be paid to the influence of transformer wiring (such as multiplying Y/d by √ 3 or 1.5 times the coefficient after conversion, as explained in manual 6-45).
5.2 Slope Verification
Apply currents of varying sizes on both sides to ensure that the braking current is in different regions, and verify whether the action boundary conforms to the slope setting.
5.3 Harmonic Braking Test
Overlay the second harmonic (120Hz) on top of the fundamental current, observe whether the differential is locked, and release the action when the harmonic content reaches the set value.
5.4 Overcurrent 50/51 Test
Apply current to a certain phase, gradually increase it to the action value, record the delay, and compare it with the set value.
Attention: Non testing functions should be disabled before testing to avoid misoperation. Restore the original value after testing.
Precautions for replacing old protective devices
When replacing electromechanical or early microcomputer protection with M-3311A:
Input compatibility: Confirm that the CT rating (5A or 1A) is consistent with the relay version; The secondary voltage of VT is within the range of 60-140V.
Output contact capacity: The M-3311A contact has a small arc breaking ability (0.3A inductive). If driving a large capacity trip coil, an external intermediate relay is required.
Wiring terminals: Old cabinets may have different terminal blocks and require rewiring, pay attention to labeling.
Fixed value conversion: The electromechanical inverse time curve is different from the digital one and needs to be recalculated for coordination. The built-in IEC/IEEE curve of the relay can be used.
External input: The auxiliary contact of the circuit breaker (56a) must be connected to IN1 for circuit breaker status indication and lockout logic.
Power supply: M-3311A supports a wide range of AC/DC power supplies (such as 125VDC or 120VAC), and generally does not require replacement of the power circuit.
Common fault phenomena and troubleshooting
Possible causes and solutions for the phenomenon
Differential 87T misoperation (tripping under normal load) CT polarity reversal, wiring setting error, improper transformation ratio setting, harmonic braking not enabled. Check the differential current display. If it is not zero, check the CT polarity and wiring setting; Enable second harmonic braking (typical 15%)
Differential 87T mistakenly activates CT saturation during external faults, resulting in excessive unbalanced current and an increase in Slope2 (such as up to 80%) or delay (up to 6 cycles); Check if the CT matches
The grounding differential 87GD does not activate the directional component due to insufficient zero sequence current or incorrect CT ratio correction. Confirm the neutral point CT and phase CT ratio and input the correct correction factor; If the grounding fault current is small, the operating value can be reduced
The selection of the overcurrent 50/51 action time deviation time curve is incorrect or the calculation deviation of the current multiple is checked against the curve type (BECO/IEC/IEEE) and time dial value; Verify with a tester