Node ID=1~63: Slave address
5.3 NMT State Machine and Startup
CANopen standard tri state management:
Pre Operational: SDO communication only
Operational: Both SDO and PDO are allowed
Stopped: All communication is prohibited
The master station switches the slave station to Operational through the NMT command "Start Remote Node" (command code=1). Parameter 904 (Boot Up Delay, 3500~50000ms) sets the interval for sending periodic startup commands.
5.4 Virtual Links
EM-IO-03 supports horizontal data transmission between frequency converters through TxPDO/RXPDO. Each TxPDO supports Boolean, Word, and Long data type mapping:
TxPDO channel Boolean parameter Word parameter Long parameter
TxPDO1 946~949 950~953 954~955
TxPDO2 956~959 960~963 964~965
TxPDO3 966~969 972~975 976~977
Common source number:
Boolean source: 740=control word, 161=running status, 163=target value reached
Word source: 9063=percentage reference value 1133=output percentage
Long source: 900=output frequency, 62=reference frequency value
Simulation input characteristic curve configuration
The analog input of EM-IO-03 supports two-point linear characteristic curve mapping (parameters 564~567), which is suitable for linearization of nonlinear sensor signals.
Operation mode (parameter 562):
Typical Applications of Mode Functions
1. Bipolar complete mapping according to characteristic points ± 10V bidirectional control
11- Unipolar negative X-axis value mapping to 0 unidirectional speed control
21- Unipolar 2~10V/4~20mA input range limited to 20%~100% active zero position signal
101- Bipolar absolute value negative Y-axis value mapping to positive absolute value control
Tolerance band (parameter 560): 0%~25%, factory 2%, used to expand the zero crossing range and avoid direction switching oscillation.
Quick Reference Table for Fault Codes
Fault code description and troubleshooting suggestions
F0400 motor PTC temperature over limit inspection motor load, cooling, and PTC wiring
F1402 Analog Input EM-S1INA Signal Fault Check Signal Source and Wiring
F30 speed sensor 2 signal fault check sensor wiring and power supply
F31 speed sensor 2 phase loss signal check A/B phase signal
F32 Speed Sensor 2 Direction Error Check A/B Reverse Connection
F21nn system bus slave fault check corresponding node (nn hexadecimal)
F2200 SYNC message timeout check for main station SYNC generation
F2201~03 RxPDO1-3 timeout check corresponding to TxPDO configuration
F2210 CAN bus BUS-OFF check for physical connections, terminal resistance, and baud rate
Bus load planning reference
PDO message transmission time at different baud rates:
Baud rate (kBaud) message transmission time (μ s)
1000 140
500 280
250 560
125 1120
100 1400
50 2800
Load assessment: A total load rate of ≤ 80% for all TxPDOs is normal, 80%~90% is critical, and>90% is unacceptable.