Welcome to the Industrial Automation website!

NameDescriptionContent
XING-Automation
E-mail  
Password  
  
Forgot password?
  Register
当前位置:

Bonfiglioli Vectron EM-IO-01 Expansion Module Installation and System Bus Configuration Guide

F: | Au:FANS | DA:2026-09-08 | 25 Br: | 🔊 点击朗读正文 ❚❚ | Share:

Bonfiglioli Vectron EM-IO-01 Expansion Module Installation and System Bus Configuration Guide

In modern frequency converter drive systems, the scalability of functions and the flexibility of communication have become the core considerations for equipment selection and system integration. The Bonfiglioli Vectron ACTION and ACTION Cube series inverters provide users with rich I/O expansion capabilities and powerful CAN system bus communication functions through the EM-IO-01 expansion module, enabling seamless integration of inverters into distributed control architectures and achieving efficient data exchange and collaborative control.

This article is based on the EM-IO-01 expansion module technical manual and provides a systematic technical operation guide for the core concerns of on-site engineers in installation, configuration, and system integration processes. It covers hardware installation, electrical connections, system bus configuration, PDO/SDO communication mechanisms, and I/O parameterization applications.

Overview and Preparation Before Installation of EM-IO-01 Expansion Module

1.1 Module Function Positioning

EM-IO-01 is an optional hardware expansion component designed by Bonfiglioli Vectron for the ACTION and ACTION Cube series frequency converters, supporting software versions 4.1.0 and higher for the ACTION series and all ACU series devices. This module achieves the following functional extensions by inserting it into the expansion slot at the bottom of the frequency converter:

CAN system bus interface: compliant with ISO-DIS 11898 (CAN High Speed) standard, supporting a maximum communication rate of 1 MBaud

Second bipolar analog input: 12 bit resolution, configurable for ± 10V voltage or ± 20mA current input

Second bipolar analog output: ± 10V voltage output, overload and short circuit protection

Three channel digital input: PLC compatible, 24V level, supports up to 150kHz frequency signal

Two relay outputs: normally open contacts, 24V AC/DC, 1A (resistive load)

1.2 Safety confirmation before installation

Danger Warning: The installation and removal of the EM-IO-01 expansion module must be carried out with the frequency converter completely powered off. The main power supply, DC bus, and motor terminals of the frequency converter may still carry dangerous voltage even after a power outage, and must wait for the DC bus capacitor to discharge completely (several minutes) before operation can be carried out.

Anti static precautions: The module is pre installed in a dedicated housing when it leaves the factory. During installation, do not touch the PCB board on the back of the module to avoid electrostatic discharge damaging sensitive electronic components.


Mechanical installation steps

2.1 Disassemble the lower cover plate

Confirm that the frequency converter has been completely powered off and discharged.

Find the plastic cover plate under the frequency converter (position 1) and carefully remove it.

After removing the cover, the expansion slot (position 3) is exposed.

2.2 Inserting Expansion Modules

Take out the EM-IO-01 expansion module (position 2), be careful to hold only the housing part and avoid touching the back PCB.

Align the module with slot (position 3) and apply even force to fully insert it.

Reinstall the lower cover plate (position 1) to complete the mechanical installation.

Attention: The module insertion direction has a foolproof design. If insertion is difficult, do not apply force forcefully and check if the direction is correct.


Definition of Electrical Connections and Terminals

3.1 Overview of Terminal Layout

The EM-IO-01 module provides two sockets: X410A and X410B.

Socket X410A (terminals 1-7):

Engineering Description of Terminal Signal Technical Parameters

1 20V output Imax=180mA to power external sensors

2 20V ground - corresponding to terminal 1 ground

3-digit input 1 (EM-S1IND) Umax=30V, 10mA@24V , PLC compatible response time is about 16ms

4-digit input 2 (EM-S2IND) can be used as the speed sensor Track A as above

5 digital inputs 3 (EM-S3IND) can be used as the speed sensor Track B as above

6-7 Relay Output 1 (EM-S1OUTD) 24V AC/DC, 1A normally open contact

Socket X410B (terminals 1-7):

Engineering Description of Terminal Signal Technical Parameters

1-2 relay output 2 (EM-S2OUTD) 24V AC/DC, 1A normally open contact

3 Analog inputs (EM-S1INA) ± 10V (Ri=100k Ω)/± 20mA (Ri=250 Ω) 12 bit resolution

4 Analog Output (EM-S1OUTA) ± 10V, Imax=2mA Overload and Short Circuit Protection

5 CAN_Low - System Bus CAN Low Line

6 CAN-High - System Bus CAN High Line

7 CAN_SND - System Bus Ground

Key Tip: The maximum load current for the 20V output of terminal X410A. 1 is 180mA, and this current shares the total capacity with other control outputs of the inverter body. When designing external circuits, power budgeting is required.

3.2 Analog Input Voltage/Current Mode Switching

The module is equipped with a dip switch S3 for configuring the analog input signal type:

S3=OFF (right side): The analog input is configured as a voltage signal (± 10V)

S3=ON (left side): Analog input configured as current signal (± 20mA)

Note: S1 and S2 switches are used for configuring the terminal resistance of the system bus (see System Bus chapter for details).


CAN system bus configuration

4.1 Bus topology and terminal resistance

The system bus of EM-IO-01 adopts CAN High Speed physical layer, which complies with ISO-DIS 11898 standard. The bus topology is a linear structure (daisy chain), and terminal resistors must be set at the first and last physical nodes.

The module is configured with terminal resistors through dip switches S1 and S2

Passive terminal (S1=ON, S2=OFF): Conventional terminal matching

Active terminal (S1=ON, S2=ON): Active terminal, can improve the shape of CAN signal edges, suitable for long-distance buses

Factory default: S1 and S2 are both OFF (terminal resistance not activated).

Important note: Active terminals can only be activated on one node of the bus, and other nodes must use passive terminals. Improper configuration of terminal resistors will result in bus communication errors.

4.2 Node ID Setting

The system bus supports up to 63 slave nodes (frequency converters), and each node must have a unique Node ID. Node ID is set through parameter 900:

Parameter Description Minimum Value Maximum Value Factory Value

900 Node-ID -1 63 -1

Node ID=-1: The system bus disables this frequency converter

Node ID=0: Define this frequency converter as the bus master station (only one master station is allowed)

Node ID=1~63: Slave address

4.3 Baud rate and bus length

All bus nodes must be set to the same baud rate. The baud rate is set through parameter 903 and determines the maximum bus length:

Maximum line length for operating mode baud rate

3 50 kBaud 1000 meters

4 100 kBaud 800 meters

5 125 kBaud 500 meters

6 250 kBaud 250 meters

7500 kBaud 100 meters

8 1000 kBaud 25 meters

Engineering Tip: Baud rates below 50 kBaud are not recommended for low data throughput on the system bus. The actual maximum line length needs to be calculated and verified based on cable parameters and bus driver (PCA82C250T).

System bus communication mechanism

The system bus of the EM-IO-01 module is based on the CANopen protocol framework (CiA DS 301), which enables communication between Network Management (NMT), Process Data Objects (PDO), and Service Data Objects (SDO).

5.1 Network Management (NMT) and Startup Sequence

The node state machine on the system bus contains three main states:

Pre Operational: Only SDO communication (parameter read/write) is allowed, PDO (process data) is prohibited

Operational: Both SDO and PDO are allowed

Stopped: Both SDO and PDO are prohibited

Typical startup sequence:

After power on, all slave stations complete initialization and enter Pre Operational state

Send Boot Up message from the slave station (identifier=1792+Node-ID, data byte=0x00)

The master station switches the slave station to Operational state through the NMT command "Start Remote Node" (command code=1)

After initialization is completed, the master station periodically sends the Start Remote Node command with the delay time set by parameter 904 (Boot Up Delay) to ensure that the slave stations that are delayed online or temporarily disconnected can resume normal communication

Main station fault response: When the main station receives an Emergency Message from the slave station, its response is set by parameter 989 (Emergency Reaction):

989=0 (Error): The master station shuts down simultaneously and reports the fault to the slave station through fault code F21nn (nn is the hexadecimal of the slave station Node ID)

989=1 (No Error): The main station only reports a warning (Sysbus 0x2000)

5.2 SDO Channel (Parameter Data)

Each frequency converter has two SDO channels for parameter data exchange:

SDO1: Used for parameterized access of slave stations by the master station (PLC/PC or frequency converter master station)

SDO2: Reserved for parameterization by visualization tools (such as VPlus software)

The SDO channel adopts the CANopen SDO Segment Protocol Expedited service, which supports read and write of uint/int/long type data. Complete parameterization can be achieved through the system bus.

SDO1 identifier allocation (Predefined Connection Set):

Rx-SDO1=1536+Node ID (identifier range 1537~1599)

Tx-SDO1=1408+Node ID (identifier range 1409~1471)

Fixed allocation of SDO2 identifiers:

Rx-SDO2 = 1600 + Node-ID

Tx-SDO2 = 1472 + Node-ID

Note: In CANopen systems, SDO2 must be disabled to avoid compatibility issues. The activation state of SDO2 can be controlled through parameter 923 (SDO2 Set Active).

5.3 PDO channel (process data)

Each frequency converter has three PDO channels (three Rx/Tx each) for high-speed process data exchange. The PDO channel can operate in two modes: time control or SYNC control.

PDO identifier allocation (Predefined Connection Set):

Channel Rx identifier Tx identifier

PDO1 512 + Node-ID 384 + Node-ID

PDO2 768 + Node-ID 640 + Node-ID

PDO3 1024 + Node-ID 896 + Node-ID

Operation mode setting:

TxPDO Function (parameters 930/932/934): 0=disabled, 1=time control, 2=SYNC control

RxPDO Function (parameters 936/937/938): 0=time control (immediate forwarding), 1=SYNC control

Attention: The identifier range of 129~191 is reserved for emergency messages and cannot be used for PDO allocation.

5.4 Virtual Links

The most distinctive feature of the system bus is the virtual link mechanism. By linking the source data to the sending byte of TxPDO and linking the receiving byte of RxPDO to the target parameter, horizontal data transmission between frequency converters can be achieved.

TxPDO byte mapping parameters:

Channel data type parameter number (bytes 1-4/5-8)

TxPDO1 Boolean 946, 947, 948, 949

TxPDO1 Word 950, 951, 952, 953

TxPDO1 Long 954, 955

TxPDO2 Boolean 956, 957, 958, 959

TxPDO2 Word 960, 961, 962, 963

TxPDO2 Long 964, 965

TxPDO3 Boolean 966, 967, 968, 969

TxPDO3 Word 972, 973, 974, 975

TxPDO3 Long 976, 977

Example of Source Number:

Boolean source: 740=control word, 161=running status

Word source: 9063=percentage reference value 11133=output percentage

Long source: 900=output frequency, 62=reference frequency value

RxPDO receiving source number: The data received by RxPDO is presented through source numbers 700~729 (RxPDO1), 710~719 (RxPDO2), and 720~729 (RxPDO3), which can be used locally through parameter links.


Detailed configuration of analog input/output

6.1 Analog input characteristic curve

The analog input signal is mapped to a frequency or percentage reference value through a two-point linear characteristic curve. Two characteristic points are set through parameters 564-567:

Parameter Description Range Factory Value

564 characteristic point X1-1000.00%~100.00% -98.00%

565 characteristic point Y1-1000.00%~100.00% -1000.00%

566 characteristic point X2-1000.00%~100.00% 98.00%

567 characteristic point Y2-1000.00%~100.00% 100.00%

Calculation formula for characteristic curve:

Y=twoone twoone(XXone)+one

Y= X2−X1 Y2−Y1⋅(X−X1)+Y1

Operation mode (parameter 562):

1. Bipolar: Complete mapping according to characteristic points

11- Unipolar: Mapping negative X-axis value to reference value 0

21- Monopolar 2... 10V/4... 20mA: Limit the input range to 20%~100%

101- Bipolar absolute value: negative Y-axis value mapped to positive reference value

6.2 Tolerance bands and hysteresis

For applications that require switching the direction of rotation, the tolerance band (parameter 560) is used to expand the range of the reference value crossing zero, avoiding frequent direction switching near zero and causing system oscillation. The parameter range is 0.00%~25.00%, and the factory value is 2.00%.

6.3 Fault/Warning Behavior (Parameter 563)

Mode function

0-OFF does not monitor input signals

When the warning signal is less than 1V/2mA, a warning will be issued

When the shutdown signal is less than 1V/2mA, slow down and stop the machine according to the shutdown mode

When the fault shutdown signal is less than 1V/2mA, the machine can stop freely and report a fault

6.4 Analog Output Configuration

Simulate output by selecting the output signal source through parameter 584 (operating mode), and adjusting the application level through parameters 585 (offset) and 586 (amplification factor). Set the zero offset as a percentage of the simulated output full range (10V); The amplification factor is set to the signal gain as a percentage of the full scale, ranging from 5% to 1000%.


Digital input as speed sensor (EM-ENC)

The three digital inputs of EM-IO-01 can be configured as an incremental speed sensor interface through parameter 493 (Operation mode speed sensor 2):

Mode Function Description

Four fold frequency evaluation of dual channel speed sensor, identifying direction through A/B phase signals, evaluating 4 edges per turn

On the basis of the fourth harmonic inversion, the velocity value is inverted (equivalent to exchanging A/B signals)

1004- Four fold increase in reference pulse with reference pulse for sensor monitoring

1104- with reference pulse reverse fourth harmonic as above, the velocity value is taken in reverse

Index mark (parameter 494): Set according to the number of pulses per revolution of the speed sensor, ranging from 1 to 8192, with a factory value of 1024.

Maximum division mark calculation:

Smax=one hundred and fifty thousand Hz×sixty max

max=150000Hz× max sixty 

Among which

max For the maximum speed (RPM) of the motor, 150kHz is the maximum frequency limit for digital input.

Actual speed source selection (parameter 766): 1=speed sensor 1 (body), 2=speed sensor 2 (EM-IO-01).


Bus load planning

The capacity planning of the system bus is crucial for reliable communication. Each PDO message contains 8 bytes of user data, and in the worst case scenario, the total message length is 140 bits.

Single PDO message transmission time at different baud rates:

Baud rate (kBaud) message transmission time (μ s)

1000 140

500 280

250 560

125 1120

100 1400

50 2800

Bus load calculation formula:

Load=TelegramRunTime

TransmissionInterval×one hundred%

Load= TransmissionInterval

TelegramRunTime×100%

Load assessment criteria:

≤ 80%: Normal

80%~90%: critical

90%: unacceptable

Note: The sum of the total loads of all TxPDOs determines the overall load rate of the system bus. A margin must be reserved for message retransmission during design.


Common fault codes and troubleshooting

Fault code description and troubleshooting suggestions

F1402 Analog Input EM-S1INA Signal Fault Check Signal Source and Wiring, Confirm Signal is within Effective Range

F30 speed sensor 2 signal fault check sensor wiring and power supply

F31 speed sensor 2 phase loss signal check whether the A or B phase signal is lost

F32 Speed Sensor 2 Direction Error Check A/B Reverse Connection or Parameter Setting

F33 speed sensor 2 division mark error check parameter 494 whether the setting matches the sensor

F21nn system bus slave fault (nn is Node ID hexadecimal) check the corresponding node status and communication link

F2200 SYNC message timeout check whether the SYNC generation of the main station is normal

F2201~03 RxPDO1-3 timeout check corresponding to the TxPDO configuration and communication of the sending node

F2210 CAN bus BUS-OFF check for bus physical connection, terminal resistance, and baud rate consistency

  • Lauer LCA 200.202.2 Mini Control Unit Display
  • Pulsotronic 8450-00 Power Supply for Lauer Systems
  • Lauer Starline Midi LCA300.0 Text Display Console
  • Lauer PCS9000 035/27C Operator Panel HMI Display Unit
  • Lauer PCS900 PG900.202.6 Operator Panel Control Console
  • Lauer PCS090 PG090.000.4 Operator Panel Control Console
  • Lauer LCA265 Text Display Industrial Information Console
  • Lauer PCS 200FZ Control Panel Industrial Operator Console
  • Lauer PCS810-3 Interface Module Communication Board
  • Lauer PCS009 009.204.2 Operator Panel HMI Control Console
  • Lauer A-110-C6FBXP Industrial Display Monitor
  • Lauer VPCM 310 Key Control Panel Industrial Keyboard Interface
  • Lauer PCS830.0 Operator Panel – Mid-Range HMI for Versatile Applications
  • Lauer PCS950 PG 950.100.6 Operator Panel – High-End HMI for Complex Systems
  • Lauer LCA041 Text Display – Compact Alphanumeric Terminal
  • Lauer VT215B.II VPC Control Panel – Compact Versatile HMI
  • Lauer LCA 245 Text View 245.100.1 – Alphanumeric Display for Simple Control
  • Lauer PCS600FZ Operator Panel – Enhanced HMI with Extended Features
  • Lauer PCS600 PX 600.002.1 Operator Panel – Compact HMI with High Performance
  • Lauer VPC VK212b.II.LAU Control Panel – Robust HMI for Heavy Industry
  • Lauer PCS 810-1 Operator Terminal – Advanced HMI for Mid-Size Systems
  • Lauer 07182-F5 Control Panel LCA 245 – Industrial HMI for Complex Automation
  • Lauer PSC830-31 Interface Module Industrial Communication Board
  • Lauer PCS806.0 Interface Module Industrial Automation Component
  • Lauer LCA 200.102.1 Text Display LCA Starline Mini Console
  • Lauer Panel VPCT MT215L Industrial Touch Panel Display
  • Lauer Suetron Panel TP21AM/731030 Teach Pendant Industrial Touch Panel
  • Lauer PG090.000.4 120592 Control Panel PCS090 Topline Operator Panel
  • Lauer PCS 830 Interface Module Industrial Communication Board
  • Lauer PCS830-1 Interface Module TTY Communication Board
  • Lauer PCS9000 035/27C Operator Panel HMI Display Unit
  • Lauer EPC-PM-1500tc Industrial PC Embedded Computer Specifications
  • Lauer PCS804.1 Operator Terminal – Compact Industrial HMI
  • Lauer VPC VK212b.II.LAU Control Panel – Rugged Operator Interface
  • Lauer PCS090 PG090.208.E Topline Mini – Compact HMI Panel
  • Lauer PCS090 PG090.205.B Topline Operator Panel – High Performance HMI
  • Lauer P090b/L033/00a Interface Module – Reliable Automation I/O
  • Lauer P090b/L033/01 Interface Module – Compact Automation Component
  • Lauer LCA 180 Textmonitor – Compact Text Display for Industrial Control
  • Lauer 200-V02366 System Panel – Advanced Industrial Display Unit
  • Lauer LCA 200 Operator Panel – Industrial HMI Touch Screen
  • LAUER PCS 095 PG095.508.C Operator Panel | Compact HMI
  • Systeme Lauer PCS100 Operator Console | Durable HMI Terminal
  • Lauer P090b/L033/00 Industrial Module | Replacement Part
  • LAUER PCS-220FZ Operator Panel | Advanced Control Interface
  • Lauer EPC-PM03032 Control Terminal | Power Interface Panel
  • Lauer GENE-4312 Industrial Motherboard | Embedded Computing
  • Lauer EPC X 550 Controller | Advanced Automation CPU
  • Lauer EPC-PM-1200tr Industrial PC Panel | Rugged Touch Display
  • Lauer AIOvision AVTCE210.2 MPI Vision System Controller
  • Lauer LCA 200 V03907 Control Console Operator Interface
  • Lauer PCS 095 PG095.507.A Operator Panel Industrial HMI
  • Lauer 035/24 Industrial Control Module Automation Component
  • Systeme Lauer PCS830-31 Interface Module Industrial Automation
  • Lauer PCS090.M 190.203.3 Operator Panel Industrial Control
  • Systems Lauer LCA045 Text Display Operator Terminal
  • Lauer EPC-PM-1200TC Industrial PC Panel
  • Lauer PCS095 Topline Mini Operator Panel 095.506.8
  • Lauer PCS 8010 Expansion Module
  • Lauer PCS950Q PLUS Membrane Keypad
  • Lauer Tele Service TSN 110 Module
  • Lauer PCS950C User Interface Trepko 95C.201.0
  • Lauer PCS 200FZ Control Console XX2.1031.SHX
  • Lauer PCS950 Operator Panel Wifag 950.000.5
  • Lauer PCS 950 Topline Midi Control Panel 950.000.05
  • Lauer LHT-T40m-P Control Panel V15-10-10
  • Lauer Operator Panel PCS Light PG080.308.F
  • Lauer LCA Starline Mini 200.102.1
  • Lauer VPC Take Off Line VK212B.II.LAU
  • Lauer Grießbach Printing Machine Operating Terminal BAB34098
  • BS Lauer LP 056/02 Operator Panel
  • Lauer AVTCE212.3 HMI Panel
  • Lauer PCS950 Operator Panel 950.000.5 Wifag
  • Lauer PCS095 Topline Mini 095.508.B Operator Panel
  • Lauer PCS 811 Interbus-S Module Fieldbus Communication Interface
  • Systeme Lauer 035/18F Industrial Control Module Automation
  • LAUER PCS090 090.202.7 Operator Panel Industrial Control
  • Lauer PCS 600 Control Console Industrial Operator Panel
  • Lauer PCS095 Topline PG095.505.8 Operator Panel HMI
  • Systeme Lauer PCS830-3 Control Module Industrial Automation
  • Lauer EPC-PM-1200TR Industrial PC Panel Touch Display Computer
  • Lauer PCS090 PG090.208.E Operator Panel Industrial Terminal
  • Lauer PCS 804 Interbus Interface Module Fieldbus Adapter
  • Lauer PCS 802 Control Console Industrial Operator Panel
  • Lauer Operator Panel PCS950 with PCS808
  • Lauer PCS950Q Topline Midi 950.000.5
  • Lauer LCA 320 300.001.0 Text Display
  • Lauer Operator Panel PCS090 PG090.207.D
  • Lauer PCS PCS095.1 Operator Panel Skinetta
  • Lauer PCS8010 035/28B Expansion Module
  • Lauer Topline Mini Operator Panel PCS 090 PG090.208.E
  • Systeme Lauer PCS830-1 Interface Board 830.1-00124-H6
  • Kuttler Lauer PCS090.M PG190.203.3 Operator Panel
  • Lauer PCS 090 Control Console Operator Terminal Industrial
  • Lauer PCS 804.1 Interbus Adapter Module Fieldbus Interface
  • Lauer LCA 300.0 Starline Midi Text Display Control Panel
  • Systems Lauer PCS811 GEB Interbus-S Slave Module Fieldbus
  • Lauer PCS 811 Interbus-S Module PG 811.000.1 Fieldbus Interface
  • LAUER WOP-IT-X-550-KTC Industrial Touch Panel HMI Terminal
  • Lauer PCS609 Topline Micro Panel Operator Interface Industrial
  • Lauer PCS 090 Topline Mini PG 090.207.D Operator Panel Industrial HMI
  • Lauer AIO Automation in One PC Unit 24V DC
  • Lauer WOP-IT-X-640TC UMP
  • Systeme Lauer LCA 265 Text Display 24V
  • Lauer VPC Take Off Line MT215.LAU
  • Systeme Lauer SIMATIC S5 Serial Interface Board PCS 810-1
  • Lauer PCS WIN Profibus DP PCS 090b/L033/03
  • Lauer LCA200 Starline Mini
  • Lauer DJ432 Control Panel EPC 1200tc Eltex ESC2/EBE
  • Lauer LK2438 Control Panel Branson PCS095
  • LAUER PCS LIGHT PG 080.308.E Operator Panel PLC HMI
  • Lauer LCA 200 Starline Mini Control Console Operator Interface
  • LAUER LCA300 Starline Midi Operator Console Panel Industrial
  • LAUER PCS 009 Topline Micro Operator Panel 24VDC Industrial
  • LAUER LCA320.1 Text Display Operator Terminal Industrial
  • LAUER PCS812 Operator Panel Control Interface Industrial
  • LAUER PCS LIGHT 00190 K4 Operator Panel Industrial Display
  • Lauer PCS 8100 Memory Module Control Panel Industrial Storage
  • Lauer PSC095.5 A Operator Interface Panel Industrial HMI
  • LAUER PCS 9100 LCD Display Module Industrial Replacement Screen HLD0909-010050
  • Lauer Systeme LCA620.1 Operating Terminal Industrial HMI Keypad Panel
  • LAUER LXT-K10m Beijer EXTER-K10m Operator Interface Keypad HMI Panel
  • LAUER EPC-PM-1500tc Embedded PC 15 Inch TFT Touch Screen Industrial Computer
  • Lauer Industrial VPC Color Panel Control ID64680
  • Lauer PCSsmart PCS-10TVD-102 Touchscreen Panel
  • Lauer EPC 1200TC Embedded Industrial PC
  • Lauer Control Console PCS 095
  • Lauer PCS-090 Topline Mini Operator Panel PG090.208.D