If 235 is a positive value, increase Offset.
If 235 is a negative value, reduce Offset.
Repeat the adjustment until 235 approaches 0 (ideal target).
Recheck and fine tune Offset at 50% rated frequency.
Engineering tip: If there is no significant change in the value of 235 during the adjustment of Offset, it indicates that the step size is too small and should be increased (such as 10 °) and tried again. The maximum effective adjustment range of Offset is 360 °/(number of motor poles/number of rotating transformer poles).
4.6 Offset setting completed
After setting the offset:
Restore parameter 417 (Switch Off Limit) to the normal operating frequency limit.
Restore parameter 728 (Current Limit) to its rated value.
Perform SETUP guided debugging (allowing the frequency converter to automatically optimize the current loop parameters).
Please note: SETUP will reset some parameters, and after completion, it is necessary to confirm again whether Offset remains at the set value.
Analog input configuration
EM-RES-01 retains the same analog input functionality as the EM-IO series (EM-S1INA, located in X410B. 4):
Voltage/current switching: selected through dip switch S3
S3=OFF (downward): ± 10V voltage input
S3=ON (up): ± 20mA current input
Resolution: 12 bits
Characteristic curve: Set the two-point linear characteristic through parameters 564-567
Operation mode: Parameter 562 selects bipolar/unipolar/absolute value mode
Tolerance band: Parameter 560 (0%~25%, factory 2%) is used for zero crossing anti shake
Filtering: Parameter 561 selects a time constant of 0-5000ms
Analog input can be used as a frequency reference source, percentage reference source, or limit source.
Engineering application of repetitive frequency output
The repetition frequency output (EM-RFOUT) of EM-RES-01 converts the speed signal of the rotary transformer into an incremental encoder signal (A+/A -/B+/B -), which has the following engineering value:
PLC speed monitoring: The actual motor speed can be fed back to the PLC high-speed counting module without the need for an additional encoder
Master slave synchronization: serving as a speed reference source for the slave frequency converter
Diagnostic tool: Monitor the quality of the Resolver signal during debugging
Technical Specifications:
The division mark is fixed at 1024
Maximum output frequency 512kHz
TTL/RS-422 level, can be directly connected to standard differential encoder receiving equipment