Welcome to the Industrial Automation website!

NameDescriptionContent
XING-Automation
E-mail  
Password  
  
Forgot password?
  Register
当前位置:

Eaton Freedom NEMA Contactor Starter Complete Guide

F: | Au:FANS | DA:2026-05-28 | 413 Br: | 🔊 点击朗读正文 ❚❚ | Share:

Eaton Freedom NEMA Contactor Starter Complete Guide

Chapter 1 Introduction: NEMA Standards and Eaton Freedom Series

In the field of industrial automation in North America, contactors and starters defined by NEMA (National Electrical Manufacturers Association) standards have long dominated. Compared with IEC standard products, NEMA devices are known for their higher mechanical strength, larger overload margin, and longer electrical life, especially suitable for frequent start stop, high impact loads, and harsh environments such as dust, moisture, and corrosive gases. Eaton's Freedom Series ™ Full voltage starters and contactors are representative product lines in this field, becoming the preferred choice for many OEMs and equipment maintenance engineers due to their compact design, high-strength insulation materials, flexible accessory systems, and excellent short-circuit coordination capability (Type 2 coordination).

However, faced with hundreds of models, dozens of optional codes, and diverse overload protection technologies (bimetallic heater pack, C440 solid-state electronic), even experienced engineers often feel confused. This article aims to systematically review the selection logic, installation points, common failure modes, and solutions of Freedom NEMA contactors and starters based on Eaton's official technical documentation, to help practitioners quickly locate problems and make correct decisions.


Chapter 2 Overview of Product Family

2.1 Freedom Full Voltage Control (Section 2.1)

This is the core part of the Freedom series, including:

Non Reversing Contactor: Class ECN01, 2-pole, 3-pole, 4-pole, 5-pole optional, NEMA size 00 to 9, continuous current 9A~2250A, maximum motor power from 1-1/2 HP (120V/size 00) to 900 HP (460V/size 9).

Reversing Contactor: Class ECN02, 3 poles, also covering sizes 00~9.

Non Combination Starter: Class ECN05 (non reversing), ECN06 (reversing), ECN07 (with control transformer CPT). Built in contactor+overload relay, but without short-circuit protection device. Users need to configure additional fuses or circuit breakers.

Combination Starter: Integrated with short-circuit breaking device (fuse type isolating switch, non fuse type isolating switch or circuit breaker) and starter. Including Class ECN16 (fused/non fused, non reversed), ECN17 (fused/non fused, reversed), ECN22 (circuit breaker, non reversed), ECN23 (circuit breaker, reversed). The combination launcher also offers versions with CPT (ECN18, ECN24).

2.2 A200 Full Voltage Control (Section 2.2)

The A200 series is another NEMA starter product line from Eaton, mainly covering NEMA sizes of 00~6 and rated voltage of 600V. Its features include straight through wiring, front terminals, environmental temperature compensation overload relays, etc. The selection code is similar to Freedom, but the model prefix is EC222 (non reversing circuit breaker type), EC224 (non reversing circuit breaker type with CPT), etc.

2.3 Freedom Multi speed Starter (Section 2.3)

Used to control dual speed motors, supporting separate winding and single winding pole changing motors. Provide two forms of non combination and combination, as well as three load characteristics: constant torque (CT), variable torque (VT), and constant horsepower. The models include ECN33/36 (two windings), ECN34/37 (single winding CT/VT), ECN35/38 (single winding constant power), and ECN39/40/41 (circuit breaker type combination multi speed).


Chapter 3: In Depth Interpretation of Model Coding

3.1 Taking ECN05 non combination non reversal initiator as an example

A typical model such as ECN0511AAA can be decomposed into:

Example values of location meaning

1-3 Product Series ECN (Eaton Contactor NEMA)

4 starter types: 0=non combination non reversal, 1=non combination reversal, 6=combination fuse type, 2=combination circuit breaker type, etc

5 NEMA dimensions 0=00, 1=0, 2=1, 3=2, 4=3, 5=4, 6=5, 7=6, 8=7, 9=8, A=9

6 shell types 1=Type1, 2=Type3R, 4=Type4/4X stainless steel, 8=Type12

The voltage/number of poles of the 7 motors are shown in the table below (A=120V/60Hz, B=240V/60Hz, C=480V/60Hz, D=600V/60Hz, E=208V/60Hz, etc.)

8 coil voltage codes A=120/60-110/50, B=240/60-220/50, C=460/60-440/50, D=575/60-550/50, etc

9 panel control codes such as J=HOA switch with red running indicator light, default A is no panel device

10-11 Special modifications such as R63/64 for solid-state overload, E3 for oversized casing, etc

3.2 Coil Voltage Code Table (Some Commonly Used)

Code coil voltage

A 120V 60Hz / 110V 50Hz

B 240V 60Hz / 220V 50Hz

C 460V 60Hz / 440V 50Hz

D 575V 60Hz / 550V 50Hz

E 208V 60Hz

H 277V 60Hz

P 12V DC

Q 24V DC

R 48V DC

S 125V DC

T 24V 60Hz

U 24V 50Hz

3.3 Shell type code

Code type description

1 Type 1 Universal, indoor, prevents finger contact with live parts

2 Type 3R Rainproof Type, Outdoor

3 Type 4 Waterproof, Carbon Steel Spray Coating

4 Type 4X waterproof and corrosion-resistant, 304 stainless steel (can be changed to 9=316 stainless steel)

5 Type 4X Non Metallic

8 Type 12 Dustproof Industrial Type with External Reset

3.4 Solid state overload modification code (R63/R64)

To use C440 solid-state electronic overload relay, add - R63 (without ground fault protection) or - R64 (with ground fault protection) after the base model, and specify the current range code:

Code current regulation range (A) applicable to NEMA size

A 0.33–1.65 00,0,1

B 1–5 00,0,1

C 4–20 00,0,1

D 9–45 0,1,2

E 20–100 2,3,4

F 28–140 4

G 60–300 5

H 120–600 6

Chapter 4 Key Selection Points and Engineering Techniques

4.1 Select NEMA size based on motor power

NEMA size does not correspond linearly to current, but is based on typical motor power. The following is the maximum HP reference at 460V/60Hz:

NEMA size continuous current (A) maximum HP (460V)

00 9 2

0 18 5

1 27 10

2 45 25

3 90 50

4 135 100

5 270 200

6 540 400

7 810 600

8 1215 900

9 2250 1600 (for consultation)

When selecting, it is necessary to check the full load current (FLA) and locked rotor current (LRA) on the motor nameplate, and ensure that the current rating of the contactor and overload relay is not lower than FLA. For high inertia loads or frequent starts and stops, a larger size should be selected.

4.2 Overload Relay Selection: Bimetallic vs Solid State

Bimetallic OL overload

Using interchangeable heater packs, each size corresponds to a set of heater selection tables (see sample Tab 15).

Advantages: Low cost, resistance to electrical noise, no need for external power supply.

Disadvantages: The environmental temperature has a significant impact (although there is environmental compensation), the setting range is narrow (usually 3:1), and the disengagement level is fixed (usually Class 20).

Attention should be paid when selecting: Non combination starters do not include heater packs and must be ordered separately (3 per box, corresponding to three phases). For dual speed starters, two sets of heater packs (one set per speed) need to be ordered.

C440 Solid State Overload (Solid State OL)

Wide tuning range (5:1), for example, code C for 4-20A can cover 4-20A, significantly reducing inventory.

Adjustable release level (Class 10/20/30) to adapt to different load characteristics.

Built in phase loss, phase imbalance, and ground fault protection (R64 should be selected).

Support remote communication (optional I/O module), capable of real-time reading of three-phase current RMS values, thermal memory, and fault records.

Self powered (no external power supply required), but requires an auxiliary power supply for communication.

Attention: Solid state overload is optional in starters of size 00~2 (modify code), and size 3 and above are also optional.

4.3 Short circuit protection devices in combination starters

Fusible type

Use Dual Element Time Delay Fuses, typically Class R, J, or H.

Rated short-circuit current: 100000 rms symmetrical current (480V and below), compatible with fuses to achieve Type 2 coordination - i.e. contactors and overload relays can still be used after a short-circuit fault.

When selecting, the current level of the fuse clip should be specified (30A, 60A, 100A, 200A, 400A, 600A, etc.), and the fuse itself should be provided by the user separately.

Circuit Breaker

Usually Eaton's HMCP (molded case circuit breaker) or MCP (motor protection circuit breaker) is used.

Short circuit rating: 100000 rms @ 480V, 25000 rms @ 600V.

The setting current of the circuit breaker needs to be adjusted according to the motor FLA setting.

For sizes 5 and above, the FLA and design code (such as Design B/E) of the motor need to be provided in order to correctly select the circuit breaker.

Non Fusible

Only provide isolation switch, no overcurrent protection. Short circuit protection must be provided upstream (such as fuses or circuit breakers on the distribution panel).

4.4 Selection of Control Transformer (CPT)

For situations where the voltage of the control circuit needs to be different from that of the main circuit (such as 480V for the main circuit and 120V for the control circuit), models with CPT (such as ECN07, ECN18, ECN24) can be selected. The CPT code example is as follows:

Code primary voltage (wiring method) secondary voltage

B 240/480 connected to 240V 120V

C 240/480 connected to 480V 120V

D 600V 120V

E 208V 120V

Q 208V 24V

Connect R 240/480 to 240V 24V

S 240/480 connected to 480V 24V

CPT capacity typically ranges from 50VA (small size) to 400VA (large size), sufficient to drive contactor coils and a few indicator lights.


Chapter 5 Installation and Wiring Practice

5.1 Precautions for Mechanical Installation

All Freedom contactors and starters can be installed horizontally or vertically on upright panels.

Adopting straight through wiring: the incoming terminal is at the top and the outgoing terminal is at the bottom. The screw type power terminal is equipped with a self lifting pressure plate, which can accommodate AWG 22~18 (0.3~0.75mm ²) wires.

Terminal screw torque: 0.5~0.6 N · m (control terminal), power terminal according to product label.

For combination starters, please note that the fuse clip of the fuse type model is only suitable for Class R fuses. If Class H or J is required, the modified code must be specified.

When safety door interlocking is required, the Type 12 enclosure needs to add modification code E11 (otherwise, standard Type 12 does not have door interlocking).

5.2 Coil replacement and wiring

The 45mm contactor magnetic circuit coil adopts dual voltage/dual frequency packaging (such as 120/60-110/50), and the coil terminals are located at the top for easy wiring.

When replacing the coil, first disconnect the power supply, loosen the coil fixing screw, pull out the old coil, and insert the new coil (note that the voltage code must match).

The DC coil has polarity (+/-), and should not be wired in reverse.

5.3 Auxiliary contacts and timers

Snap on auxiliary contact modules can be used for top or side installation. Up to 2 modules can be installed (each module containing 1NO+1NC or 2NO/2NC).

Solid state timers (connection delay, disconnection delay) can also be mounted on coil terminals without additional wiring.

5.4 Reset Mode Settings

Default manual reset for bimetallic overload (requires pressing the blue reset button). It can be changed to automatic reset by modifying the code (note security risks).

External Reset is a standard configuration (Type 12 casing), and the reset lever extends from the casing. Internal Reset requires specifying the modification code R5.

Short circuit fault: same as the fuse part.

Chapter 6 Common Troubleshooting Guide

6.1 Motor cannot start, contactor does not engage

Possible causes and troubleshooting steps:

Missing or insufficient coil voltage: Use a multimeter to measure the terminal voltage of the coil. Compare the coil code (e.g. A=120V ± 10%). Check if the secondary fuse of the control transformer is blown.

Overload relay tripped: Observe whether the overload reset button pops up (bimetallic) or the LED status of C440 (red flashing indicates a fault). Before pressing the reset button, it is necessary to confirm that the motor is not overheated.

Control circuit wiring error: For models with CPT, check if the primary and secondary wiring of the transformer meets the selected voltage. For forward and reverse control, check if the interlock contacts are stuck.

Emergency stop or safety door lock circuit disconnection: The door interlock of the combination starter (if any) will disconnect the control circuit when the door is opened.

6.2 Contactor engages but motor buzzes and rotates slowly

Possible reasons:

Phase loss: Check if there is an open circuit in one phase of the fuse, circuit breaker, or wiring terminal. C440 solid-state overload will detect phase loss and delay tripping, but the contactor may have already been engaged.

Severe erosion or poor contact of contactor contacts: Disconnect the power supply and check the surface of the main contacts. If the contact pits are too deep or the silver dots are worn to a thickness of less than 1mm, the contactor or contact kit needs to be replaced.

Load mechanical jamming: Disconnect the motor coupling and conduct a no-load test.

6.3 Frequent tripping of overload relay

Bimetallic overload:

Heater selection too small: Check the motor FLA and the rated current of the heater. The heater should be selected at 100%~110% of the motor FLA.

Excessive ambient temperature: Although bimetallic materials have undergone environmental compensation, they still need to be corrected if they exceed the range of -10~40 ℃. The heater should be increased by one step every time it exceeds 10 ℃.

Frequent start stop: The motor starting current (usually 6 times FLA) will cause the heater to accumulate heat. If the start stop cycle is shorter than the cooling time, a larger heater or Class 30 solid-state overload should be used instead.

C440 solid-state overload:

Check if the setting current knob is aligned with the motor FLA (± 1% repeatability).

Check the trip level settings: Class 10 is suitable for light load starting, Class 20 is used for heavy load, and Class 30 is used for high inertia load. Setting too low can cause false jumps.

View fault records: Read the reason for the last trip (overload, phase loss, phase imbalance, grounding fault) through the communication interface. If it is phase imbalance, check whether the three-phase voltage is balanced (allowable difference ≤ 2%).

Ground fault protection (R64 only) misoperation: Check the insulation resistance of the motor and cable, as well as the set value of the ground fault current (adjustable).

6.4 Combination starter fuse frequently blows

Short circuit fault: Check for motor insulation and cable damage. Measure the relative ground and phase to phase resistance with a megohmmeter.

The rated value of the fuse is too low: Refer to the NEMA size selection table to ensure that the correct grade of dual element fuse is used (for example, a 60A fuse clip should be used for size 2, but the rated current of the fuse itself needs to be selected according to the motor FLA × 1.25~1.5 times).

Phase loss operation: After one phase fuse is blown, the increase in current in the other two phases can also cause the fuse to melt. At this point, the cause of the missing phase should be investigated first.

6.5 Unexpected tripping of circuit breaker

Instantaneous trip setting value too high or too low: HMCP's thermal magnetic release is set according to the motor FLA for long delay, and the instantaneous setting value is usually 13 times FLA (used for motor startup). If the trip occurs during startup, the instantaneous value can be appropriately increased (not exceeding 17 times).

Short circuit fault: same as the fuse part.

6.6 Control transformer overheating or smoking

Secondary load overload: Check whether the total current of the control circuit (contactor coil, indicator light, PLC input, etc.) exceeds the CPT capacity (usually indicated in the model). For example, CPT is 50VA, and the maximum secondary current of 120V is 0.42A. If multiple contactors are simultaneously closed, it may exceed.

Primary voltage error: For example, if the CPT primary tap is connected to 240V and the actual power supply is 480V, it will cause the iron core to saturate and severely heat up. Be sure to wire correctly according to the CPT code.


Chapter 7 Maintenance and Replacement Guide

7.1 Maintenance of contactor contacts

For NEMA size 00~4 contactors, the contacts can be inspected and replaced. Remove the arc extinguishing cover after power failure and observe the main contact:

Slight erosion (surface gray or slightly pitted): Use fine sandpaper (400 grit) to gently polish, do not use files or grinding wheels.

Severe erosion (silver dot melting, unevenness) or wear to less than 1/2 of the original thickness: the contact kit should be replaced (Eaton part number see Tab 16).

Check every 6 months or 100000 operations.

7.2 Overload Relay Replacement

Replacement of bimetallic heater package:

Disconnect all power sources.

Open the overload relay cover and manually remove the old heater element (one for each phase).

Insert the new heater (pay attention to the direction) and ensure it is securely fastened.

Record the replacement date on the device label.

C440 solid-state overload replacement:

No need to replace the heater, just readjust the setting current knob.

If C440 is damaged, the entire module needs to be replaced (C440 in non combination starters is an independent component that can be unplugged). Pay attention to maintaining the same current code (A~H).

7.3 Coil replacement steps

Disconnect the power supply and remove the wires from the coil terminals (marked as excellent).

Remove the coil fixing spring or screw.

Slide the old coil out of the magnetic yoke.

Before installing the new coil, check if the magnetic pole surface is clean (without rust or foreign objects).

Install a new coil, tighten the fasteners, and rewire.

Power on test for suction status (no abnormal noise).

7.4 Combination starter fuse/circuit breaker replacement

Fuse type: Open the outer cover and use a fuse puller to remove the fuse link. Be sure to use dual element fuses of the same model and current level. Ordinary fuses or copper wires shall not be used as substitutes.

Circuit breaker type: operate the handle to the OFF position, release the circuit breaker terminal, and remove the faulty circuit breaker. Before installing a new circuit breaker, confirm that the setting scale matches the motor FLA.


Chapter 8 Safety Regulations and Coordination

8.1 Importance of Type 2 Coordination

According to UL/CSA and IEC 60947-4-1, Type 2 coordination means that after a short circuit fault, the contactor and overload relay will not damage personnel or equipment and can continue to be used without replacement (slight contact fusion welding is allowed, but must be able to separate). The Eaton Freedom combination starter (correctly configured with fuses or circuit breakers) can meet Type 2 coordination under symmetrical current of 100kA.

Engineers must ensure that the brand and model of the fuses used are consistent with Eaton's certified series when selecting. Common certified fuses include Bussmann's LPJsP, JKS, etc. Using non certified fuses may cause Type 2 failure.

8.2 Motor Branch Circuit Protection (NEC 430)

According to Article 430 of the National Electrical Code (NEC), short-circuit protection devices (fuses or circuit breakers) for motor branch circuits can be selected based on the following percentage of motor FLA:

Dual element delay fuse: up to 175% (but not exceeding 225% for certain situations).

Instantaneous circuit breaker: maximum 800% (used for designing B motor).

The fuse clip or circuit breaker in the combination starter is configured according to typical values when it leaves the factory, and the final setting value should be adjusted by the on-site engineer based on the actual motor nameplate.

8.3 Manual operation in emergency situations

For combination starters with isolation switches, the external handle can directly cut off the power supply in the locked state. Some models are equipped with door interlock: the door cannot be opened when the handle is in the ON position to prevent live maintenance. If it is necessary to inspect the interior when powered on, the upstream power supply must be disconnected first and LOTO procedures must be followed.

  • ETEL DSB2P131 & DSO-CAN111A Servo Amplifier Set
  • ETEL DSA2S211ZA-018A Digital Servo Amplifier
  • ETEL DSMAX212-111-001 568540-01 DSMAX2 Servo Controller
  • ETEL TMB+0291-150 Torque Motor Stator Assembly
  • ETEL EA-S0M-300-40/80A AccurET PSU
  • ETEL DSO-PWR112C-000B Power Supply Module
  • ETEL DSC2P141-111-000 Linear Servo Amplifier
  • ETEL DSB2S154-211-000H Servo Amplifier
  • ETEL DSCDP121-122-000 Digital Controller
  • ETEL DSCDP121-111E-000A Dual Position Controller
  • ETEL DSCDM332-111-000 Linear Servo Controller
  • ETEL DSB2P134-111E-000H Servo Amplifier
  • ETEL DSCDP132-111-000 Control Board Guide
  • ETEL DSB2S154-211E-000H Servo Amplifier
  • ETEL EA-SOM-300-40/80A Power Supply Module
  • ETEL ILM12-060-3PD-R20C Linear Motor with IWM Ways
  • ETEL P2M-300-07 AccurET Position Controller
  • ETEL DSB2P124-111E-000H Servo Amplifier
  • ETEL EA-P2M-048-05/10A Position Controller
  • ETEL EA-S0M-300-40/80A Power Supply Module
  • ETEL MWA070-0256-20B Linear Motor Magnet Guide
  • ETEL MWD070‑0128‑21A Linear Motor – Compact Ironless Linear Motor for High‑Speed Precision
  • ETEL DSB2P124‑211E‑000H Digital Servo Amplifier – 300 VDC Slave Drive for High‑Voltage Systems
  • ETEL MWD100‑0128‑00B Linear Motor – High‑Force Ironless Linear Motor for Precision Motion
  • ETEL AccurET EA‑S0M‑400 & P2M‑400‑05/10A Drive Module
  • ETEL EA‑S0M‑400‑40/80A‑0000‑00 AccurET Power Supply – High‑Power DC Supply for Motion Systems
  • ETEL MWA050‑0128‑20B Linear Motor Magnet – High‑Force Magnet Assembly for Linear Motors
  • ETEL DSB2S121‑111E‑000H Digital Servo Amplifier – High‑Current Drive for Demanding Motion
  • ETEL DSCDM332‑111C‑000B Digital Position Controller DSCDM – High‑Density Motion Module
  • ETEL EA‑P2M‑048‑2.5/5A‑0100‑01 AccurET Modular Position Controller
  • ETEL DSC2P121-111E-001A Digital Servo Controller – High‑Precision Motion Control
  • ETEL MWA050-0128-20B Linear Motor Magnet
  • ETEL DSB2P142-111E-000H Drive Specs
  • ETEL DSB2S234-111E-000H Servo Amplifier
  • ETEL EA-P2A-400-10-20A Position Controller
  • ETEL DSB2 Digital Servo Amplifier Controller DSB2P142-111E-000H SN 014661437
  • ETEL EA-S0M-400-40/80A-0000-00 AccurET Power Supply Module 650140-01
  • ETEL DSB2P131-111E-000H Servo Amplifier
  • ETEL EA-P2M-400-10/20A AccurET Controller
  • ETEL DSDP324-322F-000C Dual Motor Driver
  • ETEL DSB2S154-211E-000H Digital Servo Amplifier Drive
  • ETEL DSO-PWS111B-000C Power Supply Board 1130E-070-018
  • ETEL DSCDP324-322G-000A Servo Amplifier
  • ETEL DSB2P142-111E-000H Servo Amplifier Drive
  • ETEL EA-P2M-400-15/40A & EA-S0M-400 Drive Set
  • ETEL DSB2P142-111E-000H Digital Servo Amplifier
  • ETEL LMG15-070-3QC-H11 Linear Motor
  • ETEL TMA0140-070-3RB-S62B Torque Motor
  • ETEL DSA2S211ZA Digital Servo Amplifier
  • ETEL AccurET EA-P2M-300-4/7.5A-0100-01 Modular Position Controller
  • ETEL DSCDL332-131C-000A Servo Control Board
  • ETEL DSCDP324-322F-000C Dual Motor Driver
  • ETEL EA-P2M-400-10/20A Position Controller
  • ETEL DSC2P121 and DSO-HIO33 Servo Amplifier Set
  • ETEL EA-P2M-400-15/40A AccurET Drive
  • ETEL EA-P2M-300-07/15A Position Controller
  • ETEL EA-P2M-048-05/10A-0100-01 Servo Drive
  • ETEL EA-S0M-300-40/80A Servo Drive Guide
  • ETEL DSB2P131-111E-000H Digital Servo Amplifier
  • ETEL DSCDP334-421-000 Servo Drive Guide
  • ETEL EA-S0M-300-40 80A-0000-00 Motion Control Module
  • ETEL UltimET Light Motion Controller EU-LGP-0-0-1000-01 Multi-Axis
  • ETEL DSO-RAC601-029 Controller Rack
  • ETEL DSMAX212-121C-000C Board
  • ETEL DSCDL132-212B-000C Position Controller
  • ETEL TMB0291-050-3TDS-E82 Torque Motor
  • ETEL DSMAX212-121-000 Board
  • ETEL DSB2P131-111E-000H Digital Servo Controller Amplifier Unit
  • ETEL DSB 2S 124-211E-000H Digital Servo Amplifier
  • ETEL AccurET EA-P2M-300-4/7.5A-0100-01 Modular Position Controller
  • Beckwith Electric M-6280A Digital Capacitor Bank Control
  • Beckwith M-2355B Adapter Panel with M-2001C-6SL Tapchanger Control
  • Beckwith M-0359 Syncrocloser MOD512
  • Beckwith Electric M-2001C-6ELFA Tap Changer Controller
  • Beckwith M-3311A 4-Coil Transformer Protection Relay
  • Beckwith M-0124 Terminal Board Adapter Plate Guide
  • Beckwith Pride M-0296C 3-Phase Programmable Relay
  • Beckwith M-0388 Syncrocloser Check Relay Guide
  • Beckwith M-0170A AC Current Relay Guide
  • Beckwith M-3311 Transformer Protection Relay Guide
  • Beckwith Electric M3310 Integrated Transformer Protection Panel
  • Beckwith M-0145 First Customer Protector
  • Beckwith M-0170A AC Current Relay
  • Beckwith PRIDE M-0296C 3 Phase Programmable Relay
  • Beckwith Pride M-0296b 3-Phase Programmable Relay
  • Beckwith M-0245C High Speed Sync-Check Relay Guide
  • Beckwith M-0115A AC Parallel Balancing Module
  • Beckwith M-0389 Voltage Verifier Relay
  • Beckwith M-0115A Parallel Balancing Module
  • Beckwith M-0389 Voltage Verifier
  • Beckwith PRIDE M-0420 Multifunction Relay Protection Module 48VDC
  • Beckwith Electric M-3430 Generator Protection Relay
  • Beckwith Electric M-0067E Tapchanger Control
  • Beckwith Electric M-0420 Multifunction Relay
  • Beckwith Electric M-2001D-6L4S20C0S0X Tap Changer Control
  • Beckwith Electric M3425A-STD1 Generator Protection Relay
  • Beckwith Electric M-0245C High Speed Sync-Check Relay
  • Beckwith Electric M-3520 Intertie Protection Relay Guide
  • Beckwith Electric M-2001C-6SL Tap Changer Control
  • Beckwith Electric M-2001C Tap Changer Control Guide
  • Beckwith 35-12-635 Generator Protection Keypad Interface
  • Beckwith Electric P-2216 Generator Protection Main Board
  • Beckwith Electric M-2293 Tap Changer Control Guide
  • Beckwith M-4272-6AB1EH0 Integrated Synchronizing Motor Bus Transfer
  • Beckwith Electric M-4272 Motor Bus Transfer 60-140V 50/60Hz
  • Beckwith Electric M-2001B TapChanger Control
  • Beckwith Electric M-0193B Synchrocloser Unit
  • Beckwith Electric M-0115A AC Parallel Balancing Module
  • Beckwith Electric M-0169A Current Transformer
  • Beckwith Electric P-1939 Generator Protection Annunciator Panel
  • Beckwith Electric M-3311A Transformer Protection Relay Guide
  • Beckwith Electric M-0245B High Speed Sync-Check Relay
  • Beckwith Electric M3420 Generator Protection Relay
  • Beckwith M-0193B Syncrocloser Unit
  • Beckwith Electric M-520 Intertie Protection Relay
  • Beckwith Electric M-3425A Generator Protection Relay
  • Beckwith M-3425 Integrated Generator Protection Relay
  • Beckwith M-0115A Parallel Balancing Module
  • Beckwith Electric M-4272 Integrated Synchronizing Motor Bus Transfer
  • Beckwith Electric M-3420 Generator Protection System
  • Beckwith M-0193 Syncrocloser Unit
  • Basler Electric DECS-250-CN1SN1N Digital Excitation Control System
  • Basler Electric BE1-700 E0N2X1N Digital Protective Relay
  • Basler Electric SR4A-2B15B3A Static Voltage Regulator 120VAC 50/60Hz
  • Basler Electric 9261402111 PCB Control Board 9346000033
  • Basler Electric BE28053-002 Transformer BE28053002
  • Basler Electric BE3-25A Auto Synchronizer B1D Sync Module
  • Basler Electric BE3-GPR Generator Protective Relay