Welcome to the Industrial Automation website!

NameDescriptionContent
XING-Automation
E-mail  
Password  
  
Forgot password?
  Register
当前位置:

Eaton Freedom NEMA Contactor Starter Complete Guide

F: | Au:FANS | DA:2026-05-28 | 182 Br: | 🔊 点击朗读正文 ❚❚ | Share:

Eaton Freedom NEMA Contactor Starter Complete Guide

Chapter 1 Introduction: NEMA Standards and Eaton Freedom Series

In the field of industrial automation in North America, contactors and starters defined by NEMA (National Electrical Manufacturers Association) standards have long dominated. Compared with IEC standard products, NEMA devices are known for their higher mechanical strength, larger overload margin, and longer electrical life, especially suitable for frequent start stop, high impact loads, and harsh environments such as dust, moisture, and corrosive gases. Eaton's Freedom Series ™ Full voltage starters and contactors are representative product lines in this field, becoming the preferred choice for many OEMs and equipment maintenance engineers due to their compact design, high-strength insulation materials, flexible accessory systems, and excellent short-circuit coordination capability (Type 2 coordination).

However, faced with hundreds of models, dozens of optional codes, and diverse overload protection technologies (bimetallic heater pack, C440 solid-state electronic), even experienced engineers often feel confused. This article aims to systematically review the selection logic, installation points, common failure modes, and solutions of Freedom NEMA contactors and starters based on Eaton's official technical documentation, to help practitioners quickly locate problems and make correct decisions.


Chapter 2 Overview of Product Family

2.1 Freedom Full Voltage Control (Section 2.1)

This is the core part of the Freedom series, including:

Non Reversing Contactor: Class ECN01, 2-pole, 3-pole, 4-pole, 5-pole optional, NEMA size 00 to 9, continuous current 9A~2250A, maximum motor power from 1-1/2 HP (120V/size 00) to 900 HP (460V/size 9).

Reversing Contactor: Class ECN02, 3 poles, also covering sizes 00~9.

Non Combination Starter: Class ECN05 (non reversing), ECN06 (reversing), ECN07 (with control transformer CPT). Built in contactor+overload relay, but without short-circuit protection device. Users need to configure additional fuses or circuit breakers.

Combination Starter: Integrated with short-circuit breaking device (fuse type isolating switch, non fuse type isolating switch or circuit breaker) and starter. Including Class ECN16 (fused/non fused, non reversed), ECN17 (fused/non fused, reversed), ECN22 (circuit breaker, non reversed), ECN23 (circuit breaker, reversed). The combination launcher also offers versions with CPT (ECN18, ECN24).

2.2 A200 Full Voltage Control (Section 2.2)

The A200 series is another NEMA starter product line from Eaton, mainly covering NEMA sizes of 00~6 and rated voltage of 600V. Its features include straight through wiring, front terminals, environmental temperature compensation overload relays, etc. The selection code is similar to Freedom, but the model prefix is EC222 (non reversing circuit breaker type), EC224 (non reversing circuit breaker type with CPT), etc.

2.3 Freedom Multi speed Starter (Section 2.3)

Used to control dual speed motors, supporting separate winding and single winding pole changing motors. Provide two forms of non combination and combination, as well as three load characteristics: constant torque (CT), variable torque (VT), and constant horsepower. The models include ECN33/36 (two windings), ECN34/37 (single winding CT/VT), ECN35/38 (single winding constant power), and ECN39/40/41 (circuit breaker type combination multi speed).


Chapter 3: In Depth Interpretation of Model Coding

3.1 Taking ECN05 non combination non reversal initiator as an example

A typical model such as ECN0511AAA can be decomposed into:

Example values of location meaning

1-3 Product Series ECN (Eaton Contactor NEMA)

4 starter types: 0=non combination non reversal, 1=non combination reversal, 6=combination fuse type, 2=combination circuit breaker type, etc

5 NEMA dimensions 0=00, 1=0, 2=1, 3=2, 4=3, 5=4, 6=5, 7=6, 8=7, 9=8, A=9

6 shell types 1=Type1, 2=Type3R, 4=Type4/4X stainless steel, 8=Type12

The voltage/number of poles of the 7 motors are shown in the table below (A=120V/60Hz, B=240V/60Hz, C=480V/60Hz, D=600V/60Hz, E=208V/60Hz, etc.)

8 coil voltage codes A=120/60-110/50, B=240/60-220/50, C=460/60-440/50, D=575/60-550/50, etc

9 panel control codes such as J=HOA switch with red running indicator light, default A is no panel device

10-11 Special modifications such as R63/64 for solid-state overload, E3 for oversized casing, etc

3.2 Coil Voltage Code Table (Some Commonly Used)

Code coil voltage

A 120V 60Hz / 110V 50Hz

B 240V 60Hz / 220V 50Hz

C 460V 60Hz / 440V 50Hz

D 575V 60Hz / 550V 50Hz

E 208V 60Hz

H 277V 60Hz

P 12V DC

Q 24V DC

R 48V DC

S 125V DC

T 24V 60Hz

U 24V 50Hz

3.3 Shell type code

Code type description

1 Type 1 Universal, indoor, prevents finger contact with live parts

2 Type 3R Rainproof Type, Outdoor

3 Type 4 Waterproof, Carbon Steel Spray Coating

4 Type 4X waterproof and corrosion-resistant, 304 stainless steel (can be changed to 9=316 stainless steel)

5 Type 4X Non Metallic

8 Type 12 Dustproof Industrial Type with External Reset

3.4 Solid state overload modification code (R63/R64)

To use C440 solid-state electronic overload relay, add - R63 (without ground fault protection) or - R64 (with ground fault protection) after the base model, and specify the current range code:

Code current regulation range (A) applicable to NEMA size

A 0.33–1.65 00,0,1

B 1–5 00,0,1

C 4–20 00,0,1

D 9–45 0,1,2

E 20–100 2,3,4

F 28–140 4

G 60–300 5

H 120–600 6

Chapter 4 Key Selection Points and Engineering Techniques

4.1 Select NEMA size based on motor power

NEMA size does not correspond linearly to current, but is based on typical motor power. The following is the maximum HP reference at 460V/60Hz:

NEMA size continuous current (A) maximum HP (460V)

00 9 2

0 18 5

1 27 10

2 45 25

3 90 50

4 135 100

5 270 200

6 540 400

7 810 600

8 1215 900

9 2250 1600 (for consultation)

When selecting, it is necessary to check the full load current (FLA) and locked rotor current (LRA) on the motor nameplate, and ensure that the current rating of the contactor and overload relay is not lower than FLA. For high inertia loads or frequent starts and stops, a larger size should be selected.

4.2 Overload Relay Selection: Bimetallic vs Solid State

Bimetallic OL overload

Using interchangeable heater packs, each size corresponds to a set of heater selection tables (see sample Tab 15).

Advantages: Low cost, resistance to electrical noise, no need for external power supply.

Disadvantages: The environmental temperature has a significant impact (although there is environmental compensation), the setting range is narrow (usually 3:1), and the disengagement level is fixed (usually Class 20).

Attention should be paid when selecting: Non combination starters do not include heater packs and must be ordered separately (3 per box, corresponding to three phases). For dual speed starters, two sets of heater packs (one set per speed) need to be ordered.

C440 Solid State Overload (Solid State OL)

Wide tuning range (5:1), for example, code C for 4-20A can cover 4-20A, significantly reducing inventory.

Adjustable release level (Class 10/20/30) to adapt to different load characteristics.

Built in phase loss, phase imbalance, and ground fault protection (R64 should be selected).

Support remote communication (optional I/O module), capable of real-time reading of three-phase current RMS values, thermal memory, and fault records.

Self powered (no external power supply required), but requires an auxiliary power supply for communication.

Attention: Solid state overload is optional in starters of size 00~2 (modify code), and size 3 and above are also optional.

4.3 Short circuit protection devices in combination starters

Fusible type

Use Dual Element Time Delay Fuses, typically Class R, J, or H.

Rated short-circuit current: 100000 rms symmetrical current (480V and below), compatible with fuses to achieve Type 2 coordination - i.e. contactors and overload relays can still be used after a short-circuit fault.

When selecting, the current level of the fuse clip should be specified (30A, 60A, 100A, 200A, 400A, 600A, etc.), and the fuse itself should be provided by the user separately.

Circuit Breaker

Usually Eaton's HMCP (molded case circuit breaker) or MCP (motor protection circuit breaker) is used.

Short circuit rating: 100000 rms @ 480V, 25000 rms @ 600V.

The setting current of the circuit breaker needs to be adjusted according to the motor FLA setting.

For sizes 5 and above, the FLA and design code (such as Design B/E) of the motor need to be provided in order to correctly select the circuit breaker.

Non Fusible

Only provide isolation switch, no overcurrent protection. Short circuit protection must be provided upstream (such as fuses or circuit breakers on the distribution panel).

4.4 Selection of Control Transformer (CPT)

For situations where the voltage of the control circuit needs to be different from that of the main circuit (such as 480V for the main circuit and 120V for the control circuit), models with CPT (such as ECN07, ECN18, ECN24) can be selected. The CPT code example is as follows:

Code primary voltage (wiring method) secondary voltage

B 240/480 connected to 240V 120V

C 240/480 connected to 480V 120V

D 600V 120V

E 208V 120V

Q 208V 24V

Connect R 240/480 to 240V 24V

S 240/480 connected to 480V 24V

CPT capacity typically ranges from 50VA (small size) to 400VA (large size), sufficient to drive contactor coils and a few indicator lights.


Chapter 5 Installation and Wiring Practice

5.1 Precautions for Mechanical Installation

All Freedom contactors and starters can be installed horizontally or vertically on upright panels.

Adopting straight through wiring: the incoming terminal is at the top and the outgoing terminal is at the bottom. The screw type power terminal is equipped with a self lifting pressure plate, which can accommodate AWG 22~18 (0.3~0.75mm ²) wires.

Terminal screw torque: 0.5~0.6 N · m (control terminal), power terminal according to product label.

For combination starters, please note that the fuse clip of the fuse type model is only suitable for Class R fuses. If Class H or J is required, the modified code must be specified.

When safety door interlocking is required, the Type 12 enclosure needs to add modification code E11 (otherwise, standard Type 12 does not have door interlocking).

5.2 Coil replacement and wiring

The 45mm contactor magnetic circuit coil adopts dual voltage/dual frequency packaging (such as 120/60-110/50), and the coil terminals are located at the top for easy wiring.

When replacing the coil, first disconnect the power supply, loosen the coil fixing screw, pull out the old coil, and insert the new coil (note that the voltage code must match).

The DC coil has polarity (+/-), and should not be wired in reverse.

5.3 Auxiliary contacts and timers

Snap on auxiliary contact modules can be used for top or side installation. Up to 2 modules can be installed (each module containing 1NO+1NC or 2NO/2NC).

Solid state timers (connection delay, disconnection delay) can also be mounted on coil terminals without additional wiring.

5.4 Reset Mode Settings

Default manual reset for bimetallic overload (requires pressing the blue reset button). It can be changed to automatic reset by modifying the code (note security risks).

External Reset is a standard configuration (Type 12 casing), and the reset lever extends from the casing. Internal Reset requires specifying the modification code R5.

Short circuit fault: same as the fuse part.

Chapter 6 Common Troubleshooting Guide

6.1 Motor cannot start, contactor does not engage

Possible causes and troubleshooting steps:

Missing or insufficient coil voltage: Use a multimeter to measure the terminal voltage of the coil. Compare the coil code (e.g. A=120V ± 10%). Check if the secondary fuse of the control transformer is blown.

Overload relay tripped: Observe whether the overload reset button pops up (bimetallic) or the LED status of C440 (red flashing indicates a fault). Before pressing the reset button, it is necessary to confirm that the motor is not overheated.

Control circuit wiring error: For models with CPT, check if the primary and secondary wiring of the transformer meets the selected voltage. For forward and reverse control, check if the interlock contacts are stuck.

Emergency stop or safety door lock circuit disconnection: The door interlock of the combination starter (if any) will disconnect the control circuit when the door is opened.

6.2 Contactor engages but motor buzzes and rotates slowly

Possible reasons:

Phase loss: Check if there is an open circuit in one phase of the fuse, circuit breaker, or wiring terminal. C440 solid-state overload will detect phase loss and delay tripping, but the contactor may have already been engaged.

Severe erosion or poor contact of contactor contacts: Disconnect the power supply and check the surface of the main contacts. If the contact pits are too deep or the silver dots are worn to a thickness of less than 1mm, the contactor or contact kit needs to be replaced.

Load mechanical jamming: Disconnect the motor coupling and conduct a no-load test.

6.3 Frequent tripping of overload relay

Bimetallic overload:

Heater selection too small: Check the motor FLA and the rated current of the heater. The heater should be selected at 100%~110% of the motor FLA.

Excessive ambient temperature: Although bimetallic materials have undergone environmental compensation, they still need to be corrected if they exceed the range of -10~40 ℃. The heater should be increased by one step every time it exceeds 10 ℃.

Frequent start stop: The motor starting current (usually 6 times FLA) will cause the heater to accumulate heat. If the start stop cycle is shorter than the cooling time, a larger heater or Class 30 solid-state overload should be used instead.

C440 solid-state overload:

Check if the setting current knob is aligned with the motor FLA (± 1% repeatability).

Check the trip level settings: Class 10 is suitable for light load starting, Class 20 is used for heavy load, and Class 30 is used for high inertia load. Setting too low can cause false jumps.

View fault records: Read the reason for the last trip (overload, phase loss, phase imbalance, grounding fault) through the communication interface. If it is phase imbalance, check whether the three-phase voltage is balanced (allowable difference ≤ 2%).

Ground fault protection (R64 only) misoperation: Check the insulation resistance of the motor and cable, as well as the set value of the ground fault current (adjustable).

6.4 Combination starter fuse frequently blows

Short circuit fault: Check for motor insulation and cable damage. Measure the relative ground and phase to phase resistance with a megohmmeter.

The rated value of the fuse is too low: Refer to the NEMA size selection table to ensure that the correct grade of dual element fuse is used (for example, a 60A fuse clip should be used for size 2, but the rated current of the fuse itself needs to be selected according to the motor FLA × 1.25~1.5 times).

Phase loss operation: After one phase fuse is blown, the increase in current in the other two phases can also cause the fuse to melt. At this point, the cause of the missing phase should be investigated first.

6.5 Unexpected tripping of circuit breaker

Instantaneous trip setting value too high or too low: HMCP's thermal magnetic release is set according to the motor FLA for long delay, and the instantaneous setting value is usually 13 times FLA (used for motor startup). If the trip occurs during startup, the instantaneous value can be appropriately increased (not exceeding 17 times).

Short circuit fault: same as the fuse part.

6.6 Control transformer overheating or smoking

Secondary load overload: Check whether the total current of the control circuit (contactor coil, indicator light, PLC input, etc.) exceeds the CPT capacity (usually indicated in the model). For example, CPT is 50VA, and the maximum secondary current of 120V is 0.42A. If multiple contactors are simultaneously closed, it may exceed.

Primary voltage error: For example, if the CPT primary tap is connected to 240V and the actual power supply is 480V, it will cause the iron core to saturate and severely heat up. Be sure to wire correctly according to the CPT code.


Chapter 7 Maintenance and Replacement Guide

7.1 Maintenance of contactor contacts

For NEMA size 00~4 contactors, the contacts can be inspected and replaced. Remove the arc extinguishing cover after power failure and observe the main contact:

Slight erosion (surface gray or slightly pitted): Use fine sandpaper (400 grit) to gently polish, do not use files or grinding wheels.

Severe erosion (silver dot melting, unevenness) or wear to less than 1/2 of the original thickness: the contact kit should be replaced (Eaton part number see Tab 16).

Check every 6 months or 100000 operations.

7.2 Overload Relay Replacement

Replacement of bimetallic heater package:

Disconnect all power sources.

Open the overload relay cover and manually remove the old heater element (one for each phase).

Insert the new heater (pay attention to the direction) and ensure it is securely fastened.

Record the replacement date on the device label.

C440 solid-state overload replacement:

No need to replace the heater, just readjust the setting current knob.

If C440 is damaged, the entire module needs to be replaced (C440 in non combination starters is an independent component that can be unplugged). Pay attention to maintaining the same current code (A~H).

7.3 Coil replacement steps

Disconnect the power supply and remove the wires from the coil terminals (marked as excellent).

Remove the coil fixing spring or screw.

Slide the old coil out of the magnetic yoke.

Before installing the new coil, check if the magnetic pole surface is clean (without rust or foreign objects).

Install a new coil, tighten the fasteners, and rewire.

Power on test for suction status (no abnormal noise).

7.4 Combination starter fuse/circuit breaker replacement

Fuse type: Open the outer cover and use a fuse puller to remove the fuse link. Be sure to use dual element fuses of the same model and current level. Ordinary fuses or copper wires shall not be used as substitutes.

Circuit breaker type: operate the handle to the OFF position, release the circuit breaker terminal, and remove the faulty circuit breaker. Before installing a new circuit breaker, confirm that the setting scale matches the motor FLA.


Chapter 8 Safety Regulations and Coordination

8.1 Importance of Type 2 Coordination

According to UL/CSA and IEC 60947-4-1, Type 2 coordination means that after a short circuit fault, the contactor and overload relay will not damage personnel or equipment and can continue to be used without replacement (slight contact fusion welding is allowed, but must be able to separate). The Eaton Freedom combination starter (correctly configured with fuses or circuit breakers) can meet Type 2 coordination under symmetrical current of 100kA.

Engineers must ensure that the brand and model of the fuses used are consistent with Eaton's certified series when selecting. Common certified fuses include Bussmann's LPJsP, JKS, etc. Using non certified fuses may cause Type 2 failure.

8.2 Motor Branch Circuit Protection (NEC 430)

According to Article 430 of the National Electrical Code (NEC), short-circuit protection devices (fuses or circuit breakers) for motor branch circuits can be selected based on the following percentage of motor FLA:

Dual element delay fuse: up to 175% (but not exceeding 225% for certain situations).

Instantaneous circuit breaker: maximum 800% (used for designing B motor).

The fuse clip or circuit breaker in the combination starter is configured according to typical values when it leaves the factory, and the final setting value should be adjusted by the on-site engineer based on the actual motor nameplate.

8.3 Manual operation in emergency situations

For combination starters with isolation switches, the external handle can directly cut off the power supply in the locked state. Some models are equipped with door interlock: the door cannot be opened when the handle is in the ON position to prevent live maintenance. If it is necessary to inspect the interior when powered on, the upstream power supply must be disconnected first and LOTO procedures must be followed.

  • Mitsubishi MELSEC A2ASCPU PLC System
  • PC PMC25.2-002 PLC Module
  • B&R X20CP1382 Programmable Controller
  • Siemens C98043-A7002-L4 PC Board
  • Fanuc A16B-3300-0057 PCB Board
  • Schneider LV430403 Circuit Breaker TM160D
  • ABB CI810B 3BSE020520R1 PLC Interface
  • Omron R88D-HT10 Servo Drive
  • Omron CS1G-CPU43H CPU Unit
  • Mitsubishi QD70D4 Positioning Module
  • Siemens 6FC5110-0BB04-0AA1 Sinumerik 840C CPU
  • Siemens 3RT5045-1AC20 SIRIUS Contactor 75kW
  • Siemens 3VA2340-5HL32-0AA0 Circuit Breaker 400A
  • ABB HBS01-CJC I/O MTUS SD Series Module
  • Eberle MT42 Complete PLC Rack PLS514
  • Siemens C8451-A201-A9 PLC Card Slot Backplane
  • Cherokee ACX643 REV-B Power Supply Unit 100-240VAC
  • Schneider SSD1A320BDC1 Solid State Relay 20A
  • GE Fanuc IC694APU300 High Speed Counter Module
  • Schneider 140DA175300 Analog Output Module
  • Allen Bradley 1794-OA8I FLEX 8-Point Digital Output Module
  • Phoenix Contact PLC-BPT-24DC/1/SEN Solid State Relay Module
  • Schneider IG2000PG2 PLC Module Industrial Controller Card
  • Mitsubishi LE-40MTA-E Tension Controller Web Handling Control
  • Siemens 6FX1122-1AC02 PLC Card Industrial Interface Module
  • ABB AF210-30-11 Contactor Coil Voltage 110-240VAC
  • Mitsubishi GT2508-VTBD GT2508-VTBA HMI Touch Screen Panel
  • BPT 67200020 Touch Screen PLC Display Multifunction Terminal 50Hz
  • NORIS A1-91 PCB Rack Module A1-91-4 A1-91-5 A1-91-6 A1-91-7
  • Mitsubishi A1S61PN Power Supply Unit AnS Series 5VDC 5A
  • Pilz 312070AA PSSU H PLC1 FS SN SD Safety Module
  • Pasaban MTC-3044 PLC Rack with Power Supply Card
  • Schneider METSEPM8243 Power Meter PM800
  • Fanuc A16B-1212-0100-01 Power Supply Unit
  • Honeywell DPCB21010002 PCB IRTP-161 REV A
  • Siemens 6ES7315-2AH14-0AB0 CPU 315-2 DP
  • Omron GRT1-DA2V Analog Output Module 2 Channels
  • Mitsubishi FX3U-128MT/ESS PLC CPU Module
  • Schneider SSP05EMA12 Soft Starter Altistart 22
  • Mushroom 787602 Push Button Head 40mm
  • Hydraulik Elektronik EPM8900 91221 Proportional Module
  • ABB XZ C828 A101 Didt Dioder Snubber 3BHE039453R0101
  • ABB 3BHE032593R0001 Isolated Power Supply
  • ABB 3BHB02722R0001 single-phase charging transformer
  • ABB 3BHE006412R0101 UFC762AE101 main control board
  • ABB XVC770BE101 3BHE021083R0101 interface board
  • ABB 3BHE024747R0101 GD C801 Overvoltage Protection Motherboard
  • ABB 3BHE021887R0101 3BHB002751R0102 Variable Frequency Control Board
  • ABB SD812 power module 3BSC610023R0001
  • Automotive LC4A00010 Brushless Motor Controller
  • Doric NC500 Neuroscience Data Acquisition System
  • Honeywell X-DCS2000/EN Broadcast Manager
  • Kollmorgen S60600 servo drive 6A 480V
  • Honeywell 30751044-008 ROM Card
  • Honeywell 5SE1-12 Micro Switch Specifications
  • Schneider AS-BDAU-204 Analog Output Module
  • K93712 Expansion Kit Industrial Module
  • MGE DCHEN 3400116300 Circuit Board
  • Siemens 6SE7036-1EE85-1HA0 Rectifier Board
  • Renesas UPD70F3624GBA1 Microcontroller
  • Omron E5AC-CX4A5M-014 Temperature Controller Parameters
  • GE IS200TBCIH1BCE Contact Input Board
  • Fanuc A05B-2255-C101#EAW Teach Pendant Data
  • Rieter RMC186C RMC RIO-1 PLC Controller
  • Siemens PXC24.2-EF32.A Building Automation Controller
  • Fanuc A16B-1200-0220 PC Memory Board F3
  • Omron CJ2M-CPU33 PLC CPU Module
  • Beckhoff EL1918 Safety Input Terminal EtherCAT
  • Fanuc A16B-1212-0871 CNC PCB Board
  • GE Fanuc IC697BEM713J PLC Module
  • Mitsubishi A2ACPU-R21 PLC CPU Module
  • Programmable Relay 230V AC 16 Inputs 8 Outputs T2UK
  • Schneider F3SP71-4S Safety PLC Module
  • NEED-24DC- T2UK Programmable Relay 24V 16in 8out
  • Siemens 3RT1075-6SP36 SIRIUS Power Contactor 200kW
  • GE 1C31170G02 Printed Circuit Board Module 94V-0
  • BPT 67200020 Multifunction Touch Terminal 50Hz
  • Fanuc A16B-2200-0931 Option Board with Daughter Cards
  • Honeywell FC-SDOL-0424 I/O Module Board
  • Lenze EMF2179IB DeviceNet Communication Module
  • Yaskawa CIMR-JC4A0007BAA J1000 VFD 0.4kW
  • Yokogawa PSBCMNBN Bus Continuation Module ProSafe-PLC
  • Phoenix Contact PLC-BPT-24DC/1/SEN Solid-State Relay
  • Allen-Bradley 193-EC2AB E3 Plus Overload Relay
  • GE DS200TCTGG1AFF Turbine Control Board
  • Westinghouse 1C31170G02 Ovation Module
  • Mitsubishi A2ACPU21 Programmable Controller Review
  • 710-95045-AD PLC I/O Operation Console Cable
  • Allen-Bradley 1785-L11B PLC-5 Processor Specifications
  • BEMAC UST-202-D 1307D V08B2 Circuit Board
  • Pilz 312070 PSSu H PLC1 FS Safety Module
  • Keyence QS-MB1 Safety Network Module Overview
  • GE Fanuc IC693CPU372 CPU Module 90-30 Series
  • Mitsubishi RJ71EIP91 EtherNet/IP Module
  • Schneider LXM62DD27D21000 Lexium 62 Servo Drive
  • Mitsubishi Q13UDEHCPU Universal PLC CPU Module
  • B&R X20CP3585 Programmable Controller X20 CPU
  • Siemens 6FC5203-0AF02-0AA0 Sinumerik Operator Panel
  • IWKA PG02 VKR TEL-Z Self-Sufficient Measuring System
  • Schneider BMXCPS2010 PLC Power Supply Modicon M340
  • Mitsubishi A171SCPU Motion Servo CPU Specifications
  • PLC Board with Finder 44.52 Relay Module 6A 250V
  • Honeywell DOP 09436601 Measurex Module Data
  • Fanuc A20B-8101-0320 CNC Circuit Board
  • KUAX 680I V.24 PLC Module 68142304
  • Allen Bradley 1785-L30B PLC 5/30 Processor
  • Phoenix ILC 191 ETH 2TX 2700976 Ethernet Controller
  • Siemens 6SY7000-0AC80 PLC Power Supply Module
  • Reliance Electric MACS 804.46.20 CWW PLC Drive
  • Omron CP1E-N60DR-D PLC CPU 36 Input 24 Output
  • Mitsubishi Melsec PLC System A2ACPU A63P AY13E AX82
  • Square D PAF361600DC1680 2000A Circuit Breaker
  • MERLIN GERIN STR 58U 5000A Electronic Trip Unit
  • Omron CJ1W-SCU21-V1 Serial Communication Unit
  • SICK S30A-6011EA S3000 Safety Laser Scanner
  • Mitsubishi Q00JCPU-S8 Universal Programmable Controller
  • Allen-Bradley 20AB9P6C3AYNANC0 PowerFlex 70 AC Drive
  • SYSMELEC Handheld Robot Automation Controller
  • LG Display LB315WRM-SVA1 32 Inch 4K LCD Panel
  • Mitsubishi Kakoki E Series PLC I/O Modules
  • Allen-Bradley 1440-VST02-01RA Dynamic Measurement Module
  • Beckhoff EL5042 EtherCAT Encoder Terminal
  • Beckhoff CX5010-0112 Embedded PC Controller
  • Guardmaster 440R-D22R2 Safety Relay Specifications
  • NL12880BC20-10ND Industrial Display Panel Data
  • LFI 12X5326-S1 Slide-in Control Board Technical Data
  • Modicon AS-9370-001 Programmable Controller Data
  • Mitsubishi Kakoki E-01B-4130 PLC Module Overview