Welcome to the Industrial Automation website!

NameDescriptionContent
XING-Automation
E-mail  
Password  
  
Forgot password?
  Register
当前位置:

Eaton Freedom NEMA Contactor Starter Complete Guide

F: | Au:FANS | DA:2026-05-28 | 886 Br: | 🔊 点击朗读正文 ❚❚ ▶ | Share:

Eaton Freedom NEMA Contactor Starter Complete Guide

Chapter 1 Introduction: NEMA Standards and Eaton Freedom Series

In the field of industrial automation in North America, contactors and starters defined by NEMA (National Electrical Manufacturers Association) standards have long dominated. Compared with IEC standard products, NEMA devices are known for their higher mechanical strength, larger overload margin, and longer electrical life, especially suitable for frequent start stop, high impact loads, and harsh environments such as dust, moisture, and corrosive gases. Eaton's Freedom Series ™ Full voltage starters and contactors are representative product lines in this field, becoming the preferred choice for many OEMs and equipment maintenance engineers due to their compact design, high-strength insulation materials, flexible accessory systems, and excellent short-circuit coordination capability (Type 2 coordination).

However, faced with hundreds of models, dozens of optional codes, and diverse overload protection technologies (bimetallic heater pack, C440 solid-state electronic), even experienced engineers often feel confused. This article aims to systematically review the selection logic, installation points, common failure modes, and solutions of Freedom NEMA contactors and starters based on Eaton's official technical documentation, to help practitioners quickly locate problems and make correct decisions.


Chapter 2 Overview of Product Family

2.1 Freedom Full Voltage Control (Section 2.1)

This is the core part of the Freedom series, including:

Non Reversing Contactor: Class ECN01, 2-pole, 3-pole, 4-pole, 5-pole optional, NEMA size 00 to 9, continuous current 9A~2250A, maximum motor power from 1-1/2 HP (120V/size 00) to 900 HP (460V/size 9).

Reversing Contactor: Class ECN02, 3 poles, also covering sizes 00~9.

Non Combination Starter: Class ECN05 (non reversing), ECN06 (reversing), ECN07 (with control transformer CPT). Built in contactor+overload relay, but without short-circuit protection device. Users need to configure additional fuses or circuit breakers.

Combination Starter: Integrated with short-circuit breaking device (fuse type isolating switch, non fuse type isolating switch or circuit breaker) and starter. Including Class ECN16 (fused/non fused, non reversed), ECN17 (fused/non fused, reversed), ECN22 (circuit breaker, non reversed), ECN23 (circuit breaker, reversed). The combination launcher also offers versions with CPT (ECN18, ECN24).

2.2 A200 Full Voltage Control (Section 2.2)

The A200 series is another NEMA starter product line from Eaton, mainly covering NEMA sizes of 00~6 and rated voltage of 600V. Its features include straight through wiring, front terminals, environmental temperature compensation overload relays, etc. The selection code is similar to Freedom, but the model prefix is EC222 (non reversing circuit breaker type), EC224 (non reversing circuit breaker type with CPT), etc.

2.3 Freedom Multi speed Starter (Section 2.3)

Used to control dual speed motors, supporting separate winding and single winding pole changing motors. Provide two forms of non combination and combination, as well as three load characteristics: constant torque (CT), variable torque (VT), and constant horsepower. The models include ECN33/36 (two windings), ECN34/37 (single winding CT/VT), ECN35/38 (single winding constant power), and ECN39/40/41 (circuit breaker type combination multi speed).


Chapter 3: In Depth Interpretation of Model Coding

3.1 Taking ECN05 non combination non reversal initiator as an example

A typical model such as ECN0511AAA can be decomposed into:

Example values of location meaning

1-3 Product Series ECN (Eaton Contactor NEMA)

4 starter types: 0=non combination non reversal, 1=non combination reversal, 6=combination fuse type, 2=combination circuit breaker type, etc

5 NEMA dimensions 0=00, 1=0, 2=1, 3=2, 4=3, 5=4, 6=5, 7=6, 8=7, 9=8, A=9

6 shell types 1=Type1, 2=Type3R, 4=Type4/4X stainless steel, 8=Type12

The voltage/number of poles of the 7 motors are shown in the table below (A=120V/60Hz, B=240V/60Hz, C=480V/60Hz, D=600V/60Hz, E=208V/60Hz, etc.)

8 coil voltage codes A=120/60-110/50, B=240/60-220/50, C=460/60-440/50, D=575/60-550/50, etc

9 panel control codes such as J=HOA switch with red running indicator light, default A is no panel device

10-11 Special modifications such as R63/64 for solid-state overload, E3 for oversized casing, etc

3.2 Coil Voltage Code Table (Some Commonly Used)

Code coil voltage

A 120V 60Hz / 110V 50Hz

B 240V 60Hz / 220V 50Hz

C 460V 60Hz / 440V 50Hz

D 575V 60Hz / 550V 50Hz

E 208V 60Hz

H 277V 60Hz

P 12V DC

Q 24V DC

R 48V DC

S 125V DC

T 24V 60Hz

U 24V 50Hz

3.3 Shell type code

Code type description

1 Type 1 Universal, indoor, prevents finger contact with live parts

2 Type 3R Rainproof Type, Outdoor

3 Type 4 Waterproof, Carbon Steel Spray Coating

4 Type 4X waterproof and corrosion-resistant, 304 stainless steel (can be changed to 9=316 stainless steel)

5 Type 4X Non Metallic

8 Type 12 Dustproof Industrial Type with External Reset

3.4 Solid state overload modification code (R63/R64)

To use C440 solid-state electronic overload relay, add - R63 (without ground fault protection) or - R64 (with ground fault protection) after the base model, and specify the current range code:

Code current regulation range (A) applicable to NEMA size

A 0.33–1.65 00,0,1

B 1–5 00,0,1

C 4–20 00,0,1

D 9–45 0,1,2

E 20–100 2,3,4

F 28–140 4

G 60–300 5

H 120–600 6

Chapter 4 Key Selection Points and Engineering Techniques

4.1 Select NEMA size based on motor power

NEMA size does not correspond linearly to current, but is based on typical motor power. The following is the maximum HP reference at 460V/60Hz:

NEMA size continuous current (A) maximum HP (460V)

00 9 2

0 18 5

1 27 10

2 45 25

3 90 50

4 135 100

5 270 200

6 540 400

7 810 600

8 1215 900

9 2250 1600 (for consultation)

When selecting, it is necessary to check the full load current (FLA) and locked rotor current (LRA) on the motor nameplate, and ensure that the current rating of the contactor and overload relay is not lower than FLA. For high inertia loads or frequent starts and stops, a larger size should be selected.

4.2 Overload Relay Selection: Bimetallic vs Solid State

Bimetallic OL overload

Using interchangeable heater packs, each size corresponds to a set of heater selection tables (see sample Tab 15).

Advantages: Low cost, resistance to electrical noise, no need for external power supply.

Disadvantages: The environmental temperature has a significant impact (although there is environmental compensation), the setting range is narrow (usually 3:1), and the disengagement level is fixed (usually Class 20).

Attention should be paid when selecting: Non combination starters do not include heater packs and must be ordered separately (3 per box, corresponding to three phases). For dual speed starters, two sets of heater packs (one set per speed) need to be ordered.

C440 Solid State Overload (Solid State OL)

Wide tuning range (5:1), for example, code C for 4-20A can cover 4-20A, significantly reducing inventory.

Adjustable release level (Class 10/20/30) to adapt to different load characteristics.

Built in phase loss, phase imbalance, and ground fault protection (R64 should be selected).

Support remote communication (optional I/O module), capable of real-time reading of three-phase current RMS values, thermal memory, and fault records.

Self powered (no external power supply required), but requires an auxiliary power supply for communication.

Attention: Solid state overload is optional in starters of size 00~2 (modify code), and size 3 and above are also optional.

4.3 Short circuit protection devices in combination starters

Fusible type

Use Dual Element Time Delay Fuses, typically Class R, J, or H.

Rated short-circuit current: 100000 rms symmetrical current (480V and below), compatible with fuses to achieve Type 2 coordination - i.e. contactors and overload relays can still be used after a short-circuit fault.

When selecting, the current level of the fuse clip should be specified (30A, 60A, 100A, 200A, 400A, 600A, etc.), and the fuse itself should be provided by the user separately.

Circuit Breaker

Usually Eaton's HMCP (molded case circuit breaker) or MCP (motor protection circuit breaker) is used.

Short circuit rating: 100000 rms @ 480V, 25000 rms @ 600V.

The setting current of the circuit breaker needs to be adjusted according to the motor FLA setting.

For sizes 5 and above, the FLA and design code (such as Design B/E) of the motor need to be provided in order to correctly select the circuit breaker.

Non Fusible

Only provide isolation switch, no overcurrent protection. Short circuit protection must be provided upstream (such as fuses or circuit breakers on the distribution panel).

4.4 Selection of Control Transformer (CPT)

For situations where the voltage of the control circuit needs to be different from that of the main circuit (such as 480V for the main circuit and 120V for the control circuit), models with CPT (such as ECN07, ECN18, ECN24) can be selected. The CPT code example is as follows:

Code primary voltage (wiring method) secondary voltage

B 240/480 connected to 240V 120V

C 240/480 connected to 480V 120V

D 600V 120V

E 208V 120V

Q 208V 24V

Connect R 240/480 to 240V 24V

S 240/480 connected to 480V 24V

CPT capacity typically ranges from 50VA (small size) to 400VA (large size), sufficient to drive contactor coils and a few indicator lights.


Chapter 5 Installation and Wiring Practice

5.1 Precautions for Mechanical Installation

All Freedom contactors and starters can be installed horizontally or vertically on upright panels.

Adopting straight through wiring: the incoming terminal is at the top and the outgoing terminal is at the bottom. The screw type power terminal is equipped with a self lifting pressure plate, which can accommodate AWG 22~18 (0.3~0.75mm ²) wires.

Terminal screw torque: 0.5~0.6 N · m (control terminal), power terminal according to product label.

For combination starters, please note that the fuse clip of the fuse type model is only suitable for Class R fuses. If Class H or J is required, the modified code must be specified.

When safety door interlocking is required, the Type 12 enclosure needs to add modification code E11 (otherwise, standard Type 12 does not have door interlocking).

5.2 Coil replacement and wiring

The 45mm contactor magnetic circuit coil adopts dual voltage/dual frequency packaging (such as 120/60-110/50), and the coil terminals are located at the top for easy wiring.

When replacing the coil, first disconnect the power supply, loosen the coil fixing screw, pull out the old coil, and insert the new coil (note that the voltage code must match).

The DC coil has polarity (+/-), and should not be wired in reverse.

5.3 Auxiliary contacts and timers

Snap on auxiliary contact modules can be used for top or side installation. Up to 2 modules can be installed (each module containing 1NO+1NC or 2NO/2NC).

Solid state timers (connection delay, disconnection delay) can also be mounted on coil terminals without additional wiring.

5.4 Reset Mode Settings

Default manual reset for bimetallic overload (requires pressing the blue reset button). It can be changed to automatic reset by modifying the code (note security risks).

External Reset is a standard configuration (Type 12 casing), and the reset lever extends from the casing. Internal Reset requires specifying the modification code R5.

Short circuit fault: same as the fuse part.

Chapter 6 Common Troubleshooting Guide

6.1 Motor cannot start, contactor does not engage

Possible causes and troubleshooting steps:

Missing or insufficient coil voltage: Use a multimeter to measure the terminal voltage of the coil. Compare the coil code (e.g. A=120V ± 10%). Check if the secondary fuse of the control transformer is blown.

Overload relay tripped: Observe whether the overload reset button pops up (bimetallic) or the LED status of C440 (red flashing indicates a fault). Before pressing the reset button, it is necessary to confirm that the motor is not overheated.

Control circuit wiring error: For models with CPT, check if the primary and secondary wiring of the transformer meets the selected voltage. For forward and reverse control, check if the interlock contacts are stuck.

Emergency stop or safety door lock circuit disconnection: The door interlock of the combination starter (if any) will disconnect the control circuit when the door is opened.

6.2 Contactor engages but motor buzzes and rotates slowly

Possible reasons:

Phase loss: Check if there is an open circuit in one phase of the fuse, circuit breaker, or wiring terminal. C440 solid-state overload will detect phase loss and delay tripping, but the contactor may have already been engaged.

Severe erosion or poor contact of contactor contacts: Disconnect the power supply and check the surface of the main contacts. If the contact pits are too deep or the silver dots are worn to a thickness of less than 1mm, the contactor or contact kit needs to be replaced.

Load mechanical jamming: Disconnect the motor coupling and conduct a no-load test.

6.3 Frequent tripping of overload relay

Bimetallic overload:

Heater selection too small: Check the motor FLA and the rated current of the heater. The heater should be selected at 100%~110% of the motor FLA.

Excessive ambient temperature: Although bimetallic materials have undergone environmental compensation, they still need to be corrected if they exceed the range of -10~40 ℃. The heater should be increased by one step every time it exceeds 10 ℃.

Frequent start stop: The motor starting current (usually 6 times FLA) will cause the heater to accumulate heat. If the start stop cycle is shorter than the cooling time, a larger heater or Class 30 solid-state overload should be used instead.

C440 solid-state overload:

Check if the setting current knob is aligned with the motor FLA (± 1% repeatability).

Check the trip level settings: Class 10 is suitable for light load starting, Class 20 is used for heavy load, and Class 30 is used for high inertia load. Setting too low can cause false jumps.

View fault records: Read the reason for the last trip (overload, phase loss, phase imbalance, grounding fault) through the communication interface. If it is phase imbalance, check whether the three-phase voltage is balanced (allowable difference ≤ 2%).

Ground fault protection (R64 only) misoperation: Check the insulation resistance of the motor and cable, as well as the set value of the ground fault current (adjustable).

6.4 Combination starter fuse frequently blows

Short circuit fault: Check for motor insulation and cable damage. Measure the relative ground and phase to phase resistance with a megohmmeter.

The rated value of the fuse is too low: Refer to the NEMA size selection table to ensure that the correct grade of dual element fuse is used (for example, a 60A fuse clip should be used for size 2, but the rated current of the fuse itself needs to be selected according to the motor FLA × 1.25~1.5 times).

Phase loss operation: After one phase fuse is blown, the increase in current in the other two phases can also cause the fuse to melt. At this point, the cause of the missing phase should be investigated first.

6.5 Unexpected tripping of circuit breaker

Instantaneous trip setting value too high or too low: HMCP's thermal magnetic release is set according to the motor FLA for long delay, and the instantaneous setting value is usually 13 times FLA (used for motor startup). If the trip occurs during startup, the instantaneous value can be appropriately increased (not exceeding 17 times).

Short circuit fault: same as the fuse part.

6.6 Control transformer overheating or smoking

Secondary load overload: Check whether the total current of the control circuit (contactor coil, indicator light, PLC input, etc.) exceeds the CPT capacity (usually indicated in the model). For example, CPT is 50VA, and the maximum secondary current of 120V is 0.42A. If multiple contactors are simultaneously closed, it may exceed.

Primary voltage error: For example, if the CPT primary tap is connected to 240V and the actual power supply is 480V, it will cause the iron core to saturate and severely heat up. Be sure to wire correctly according to the CPT code.


Chapter 7 Maintenance and Replacement Guide

7.1 Maintenance of contactor contacts

For NEMA size 00~4 contactors, the contacts can be inspected and replaced. Remove the arc extinguishing cover after power failure and observe the main contact:

Slight erosion (surface gray or slightly pitted): Use fine sandpaper (400 grit) to gently polish, do not use files or grinding wheels.

Severe erosion (silver dot melting, unevenness) or wear to less than 1/2 of the original thickness: the contact kit should be replaced (Eaton part number see Tab 16).

Check every 6 months or 100000 operations.

7.2 Overload Relay Replacement

Replacement of bimetallic heater package:

Disconnect all power sources.

Open the overload relay cover and manually remove the old heater element (one for each phase).

Insert the new heater (pay attention to the direction) and ensure it is securely fastened.

Record the replacement date on the device label.

C440 solid-state overload replacement:

No need to replace the heater, just readjust the setting current knob.

If C440 is damaged, the entire module needs to be replaced (C440 in non combination starters is an independent component that can be unplugged). Pay attention to maintaining the same current code (A~H).

7.3 Coil replacement steps

Disconnect the power supply and remove the wires from the coil terminals (marked as excellent).

Remove the coil fixing spring or screw.

Slide the old coil out of the magnetic yoke.

Before installing the new coil, check if the magnetic pole surface is clean (without rust or foreign objects).

Install a new coil, tighten the fasteners, and rewire.

Power on test for suction status (no abnormal noise).

7.4 Combination starter fuse/circuit breaker replacement

Fuse type: Open the outer cover and use a fuse puller to remove the fuse link. Be sure to use dual element fuses of the same model and current level. Ordinary fuses or copper wires shall not be used as substitutes.

Circuit breaker type: operate the handle to the OFF position, release the circuit breaker terminal, and remove the faulty circuit breaker. Before installing a new circuit breaker, confirm that the setting scale matches the motor FLA.


Chapter 8 Safety Regulations and Coordination

8.1 Importance of Type 2 Coordination

According to UL/CSA and IEC 60947-4-1, Type 2 coordination means that after a short circuit fault, the contactor and overload relay will not damage personnel or equipment and can continue to be used without replacement (slight contact fusion welding is allowed, but must be able to separate). The Eaton Freedom combination starter (correctly configured with fuses or circuit breakers) can meet Type 2 coordination under symmetrical current of 100kA.

Engineers must ensure that the brand and model of the fuses used are consistent with Eaton's certified series when selecting. Common certified fuses include Bussmann's LPJsP, JKS, etc. Using non certified fuses may cause Type 2 failure.

8.2 Motor Branch Circuit Protection (NEC 430)

According to Article 430 of the National Electrical Code (NEC), short-circuit protection devices (fuses or circuit breakers) for motor branch circuits can be selected based on the following percentage of motor FLA:

Dual element delay fuse: up to 175% (but not exceeding 225% for certain situations).

Instantaneous circuit breaker: maximum 800% (used for designing B motor).

The fuse clip or circuit breaker in the combination starter is configured according to typical values when it leaves the factory, and the final setting value should be adjusted by the on-site engineer based on the actual motor nameplate.

8.3 Manual operation in emergency situations

For combination starters with isolation switches, the external handle can directly cut off the power supply in the locked state. Some models are equipped with door interlock: the door cannot be opened when the handle is in the ON position to prevent live maintenance. If it is necessary to inspect the interior when powered on, the upstream power supply must be disconnected first and LOTO procedures must be followed.

  • BONFIGLIOLI W63 U P80 B5 Gearbox 2G20012741
  • Bonfiglioli BE80B4 Motor with A202 Gearbox
  • BONFIGLIOLI VECTRON KEYPAD 179675500 KP500
  • Bonfiglioli RA0 60/00 Gear Reducer i182
  • Bonfiglioli C212 F P90 VV Gearbox i=9.6
  • Bonfiglioli MP105 Servomotor Gear
  • Mannesmann Demag 4APB71-4-G08-PR Getriebemotor with Bonfiglioli MVF 63/f
  • Bonfiglioli Vectron ACT401-12 FA Inverter
  • Bonfiglioli BN 80A4 COD.830820106 Motor 0.55 kW IMB5
  • Bonfiglioli TR060 Gearbox
  • Silectron Bonfiglioli FT1000-0.75S RFI Filter
  • Trasmital Bonfiglioli 710C3B50F177G34W1A52VAG Drive
  • Bonfiglioli MAC800-D1 Motorreductor
  • Bonfiglioli VF 63 V HS Worm Gearbox
  • Bonfiglioli BN90LA4 Adjustable Gear Motor 1.5kW
  • Bonfiglioli ACT 400-018 FA Frequency Inverter
  • Bonfiglioli RAO50DNP90B5-I220 Gear Unit i=200
  • Bonfiglioli ACT 401-13FA Frequency Inverter SIACT513010001
  • Bonfiglioli ACU210-18 3 FA Active Inverter 4kW
  • Trasmital Bonfiglioli 709C3B50F177G34W1A52VAG Drive
  • Bonfiglioli BN27C4 Gear Motor 0.09 kW
  • Bonfiglioli BN71A4 Electric Motor
  • Bonfiglioli Vectron VCB400-370 Inverter
  • Bonfiglioli Vectron ACU401-18FA Inverter
  • Bonfiglioli LC120 2 40 STD Gearbox
  • Bonfiglioli BN63B6 Gear Motor 0.12 kW
  • Bonfiglioli T56BN/4 Asynchronous Motor
  • AEB Atlant D712-4B5 Motor with Bonfiglioli MVF 49F1 Gearbox
  • Bonfiglioli VF110 A P100B14 Worm Gear
  • Trasmital Bonfiglioli Raupengetriebe i 1:122 2174688 2T705C3122002 Travel Drive
  • Bonfiglioli ACT 401-21A Frequency Inverter
  • Bonfiglioli VF44 U14 Worm Reducer B03181367918
  • Bonfiglioli VF49 L1 P1 P63B5 Worm Gear i=45
  • Bonfiglioli S2U230S-03F Inverter 0.4kW
  • Ferag 5690512 Uiker TR90L4 Motorreductor with Bonfiglioli C212 F9.6
  • Bonfiglioli LC120250STD80A1CD14KE Gearbox
  • Bonfiglioli W63U38 P80 B14 V5 Gearbox
  • Bonfiglioli VF49A-28-P80-B14 Worm Gearbox
  • Bonfiglioli BN71B4 W63U64P75 Gearmotor
  • Alpha VDS 063-MF1-10-141-BE Planetary Gearbox
  • Bonfiglioli BN71B4 MVF49 F1 Gearmotor i=36
  • Bonfiglioli BN 63 B6 Gear Motor 0.12kW
  • Bonfiglioli SPL400 17F SynPlus Drive 3.7kW
  • Bonfiglioli ACU 401-25A Frequency Inverter
  • Esa 3M2209B5 M71Q Motor with Bonfiglioli MVF49 Gearbox
  • Ferag 5690512 UIKER TR90L4 Gear Motor with Bonfiglioli C212
  • Bonfiglioli A302 UH35 P90 Bevel Gearbox
  • Bonfiglioli GVX1000-1.5-S Inverter Drive 1.5kW
  • Bonfiglioli W63 U 15.0 P80 B14 B Worm Drive
  • Bonfiglioli KP500 Control Panel
  • Bonfiglioli C302PP71 Speed Reducer
  • Bonfiglioli BN71B4 Motor con MVF49 Reductor
  • Bonfiglioli BN71B4 Motor with MVF49 Gearbox i36
  • Bonfiglioli SYN10S 22001AF Inverter 0.2 kW
  • Motor Power Esa 3M2209B5/M71Q with Tachometer and Bonfiglioli MVF49 Gearbox
  • Bonfiglioli SYN10 S 220 01 AF Inverter
  • MEZ UD 1104 2.5 kW BONFIGLIOLI Trasmittal 300L19 Gear Motor 300L19.00HZP90AW0A
  • Bonfiglioli Vectron ACT W 401-39 D Inverter
  • Bonfiglioli BN27C4 Gear Motor 0.09 kW
  • Bonfiglioli A302 UH40 P90 Gear Reducer
  • Bonfiglioli ACT410-193FA Frequency Inverter 5.5kW
  • Bonfiglioli VFR49 P1 240 P63 B5 B3 Gearbox
  • Bonfiglioli BN 63A 6 Motor with VF30 Combination
  • Bonfiglioli VF44 FA1 P63B14 Reducer i=60
  • Bonfiglioli BN 80 B6 FD Electric Motor
  • Bonfiglioli MVF 49F1 Reducer with ICME T 71 B4 Motor
  • Bonfiglioli BN 27 C 4 Gearmotor 0.09kW
  • Bonfiglioli MP 080 Servomotor MPC2012S000F
  • Bonfiglioli S101 1 P P71 Gear Reducer i=4.7
  • Bonfiglioli 301L251.8-HC-P90 Gearbox
  • Bonfiglioli RFI Filter F1060800-SEFL-E9S
  • GE Aviation 9410M37P01 Motor Drive Core
  • Bonfiglioli VF44 FA1 P63B14 Gearbox 60 to 1
  • Bonfiglioli K63A4 Motor 8D09020032
  • Demag 4APB71-4-G08-PR Gear Motor 0.37 kW
  • Bonfiglioli BN90LA4 Gear Motor 1.5 kW
  • Bonfiglioli VF49A-28-P80-B14 Gearbox
  • Bonfiglioli MP053 Planetary Gearbox MPA2028S000D
  • Bonfiglioli C312 P P100 Gearbox
  • Bonfiglioli S1011PP71 Gearbox 4.7 to 1
  • Bonfiglioli VF 44 V 7 P63 B5 B3 with V 0.25 F D11
  • Bonfiglioli DW3000210 AX160 Motor Gearbox
  • Bonfiglioli ACT 401-13 FC Frequency Inverter 2.2kW
  • Bonfiglioli C222 P 7.1 P90 B3 Gearbox
  • Bonfiglioli BN90S4 Motor with C212 Gearbox
  • Bonfiglioli MP130.2.9.15.24.50.130.165.S1 Gearbox
  • Bonfiglioli VF110 V HS Worm Gearbox
  • Bonfiglioli BN7IA4 Electric Motor
  • Bonfiglioli ACU 401-23A Frequency Converter
  • Bonfiglioli BN63B4 Gearmotor
  • Bonfiglioli LC12210S490002 Gear Reducer
  • Bonfiglioli BN63A4 Geared Motor with VF49
  • Bonfiglioli WR86U120P80B5B3 Gear Reducer
  • Bonfiglioli MPB1006S000C Planetary Gearbox
  • Bonfiglioli GC000011 Frequency Inverter
  • Bonfiglioli VF44 FA1 P63B14 Gearbox 60 to 1
  • Bonfiglioli BN63B6 Gear Motor 0.12 kW
  • Trasmital Bonfiglioli 301 L2 Gear Reducer
  • Bonfiglioli BN71B4 Motor with MVF49 Gearbox
  • Bonfiglioli MVF62/A Worm Gear Motor 7 to 1
  • Bonfiglioli VF W30 63UFC2 Gear Reducer
  • Bonfiglioli S1011PP71 Gearbox 4.7 to 1
  • Bonfiglioli W63 U7 P90B14 V6 Gear Reducer
  • Bonfiglioli BN63B6 FD Geared Motor with VFR49F1P63B5 Reducer
  • Bonfiglioli T56BN/4 Three Phase Motor
  • Bonfiglioli MVF62/A Worm Gearbox 7 to 1
  • Bonfiglioli VF44 FA1 P63B14 Gearbox 60 to 1
  • ICME T71B4 Motor with Bonfiglioli MVF49F1
  • Bonfiglioli BN71B4 Motor with MVF49 Gearbox
  • Bonfiglioli C31 3P P63 PV V5 Gear Reducer
  • Bonfiglioli BN80B4 Electric Motor 8F31020004
  • Bonfiglioli VF/W30/63UFC2 Gear Reducer i=168
  • Bonfiglioli MPD1006S0006 In-Line Planetary Gearbox
  • Bonfiglioli LC 120 2 40 STD 80A1 CD Gearbox
  • Bonfiglioli Vectron ZBA400-010FC Brake Unit
  • Bonfiglioli VF44 U14 Worm Gearbox B03181367918
  • Bonfiglioli 8XNC63040004 Electric Motor IP55
  • Bonfiglioli W110U P100B5 Worm Gearbox
  • Bonfiglioli VF63/FC1 P80 Gearbox 203160152 i=15
  • Bonfiglioli VMN JB00017191 Gear Unit
  • Bonfiglioli AGL202-031FC Inverter 0.37 kW
  • Bonfiglioli BN71B2 Geared Motor with VF44
  • Bonfiglioli S1011PP71 Gearbox 4.7:1
  • Bonfiglioli VF W30 63UFC2 Gear Reducer
  • Bonfiglioli VF44FA146HSB3 Gear Reducer
  • Bonfiglioli MP105 Planetary Gearbox 18:1
  • Bonfiglioli VF49 L1 P1 P63B5 Worm Gearbox
  • Bonfiglioli 55aN-4 Electric Motor