Welcome to the Industrial Automation website!

NameDescriptionContent
XING-Automation
E-mail  
Password  
  
Forgot password?
  Register
当前位置:

Mitsubishi FX Series PLC Data Communication Practical Manual

F: | Au:FANS | DA:2026-06-23 | 626 Br: | 🔊 点击朗读正文 ❚❚ ▶ | Share:


Mitsubishi FX Series PLC Data Communication Complete Guide: Practical Technical Analysis from N: N Network to Remote Maintenance

Mitsubishi Electric FX series programmable logic controllers (PLCs) occupy an important position in the field of industrial automation due to their flexibility and powerful communication capabilities. Its data communication function covers multiple network protocols and interface standards, which can meet various needs from simple device interconnection to complex remote monitoring. This article is based on the FX series PLC data communication manual, systematically sorting out its communication types, system configurations, parameter settings, and troubleshooting methods, providing engineers with a comprehensive and practical technical reference.

The FX series PLC supports multiple physical interfaces such as RS-232C, RS-485/RS-422, USB, and Ethernet, and provides various communication protocols including CC Link, N: N network, parallel link, computer link, inverter communication, non protocol communication, MODBUS communication, programming communication, and remote maintenance. Each communication method is designed for specific application scenarios, and engineers can flexibly choose based on system size, transmission distance, number of devices, and real-time requirements.

Analysis of Core Communication Types

1. N: N network

N: N Network is a small data link system that allows up to 8 FX series PLCs to automatically exchange data via RS-485 bus. This network supports three data link modes (mode 0, 1, 2), corresponding to different device point configurations:

Mode 0: 4-point device (D register) per station, only suitable for small PLCs such as FX0N and FX1S

Mode 1: 32 point devices (M relays) and 4-point devices per station

Mode 2: 64 point devices and 8-point devices per station (applicable to FX1N, FX2N, FX3 series)

N: The total extension distance of N network can reach 500 meters (when using 485ADP), and the communication baud rate is fixed at 38400bps. The master station completes configuration by setting special registers such as D8176 (station number), D8177 (number of slave stations), D8178 (refresh range), etc. The slave station only needs to set its own station number, and other parameters are automatically obtained from the master station.

2. Parallel linking

Parallel link is dedicated to high-speed data exchange between two PLCs of the same series, providing two options: regular mode and high-speed mode:

Normal mode: Transmission of 100 point devices and 10 point devices (FX0N/FX1S for 50 point M and 10 point D)

High speed mode: only transmits 2-point devices, but the link cycle is significantly shortened

In high-speed mode, the link time of FX3 series PLC is only "5ms+master station scanning cycle+slave station scanning cycle", which is suitable for situations with high real-time requirements. Parallel links are initiated through M8070 (master declaration) and M8071 (slave declaration), with M8162 used to switch high-speed mode.

3. Computer connection

The computer link adopts a dedicated protocol (format 1 or format 4), allowing the upper computer (or personal computer) to serve as the master station and connect up to 16 FX or A-series PLC slave stations. This communication supports two physical layers: RS-232C (1:1 connection, distance of 15 meters) and RS-485 (1: N connection, distance of 500 meters).

The core instructions for computer connectivity include:

BR/BW: Read/Write Bit Devices

WR/WW: Read/write word devices or 16 bit devices by word

QR/QW: Extended word read/write (applicable to FX3 series)

BT/WT: Random Test Write (bits/word)

RR/RS: Remote RUN/STOP Control

PC: Read PLC model code

GW: Global command (simultaneously controls all slave stations)

TT: Loop Test

The communication format is set through D8120 (ch1) or D8420 (ch2), including data length (7/8 bits), parity check (none/odd/even), stop bit (1/2 bits), baud rate (300~38400bps), and whether to add header/terminator/checksum. The station number is designated by D8121 (ch1) or D8421 (ch2).

4. Communication of frequency converter

The FX series PLC can communicate with Mitsubishi FR-E700, D700, A800, F800 and other series frequency converters through RS-485 to achieve operation monitoring, frequency setting, parameter reading and writing, and start stop control. For FX2N/FX2NC, use the EXTR instruction (K10~K13); For the FX3 series, more specialized IVCK, IVDR, IVRD, IVWR, IVBWR, and IVMC instructions are used.

The IVMC instruction (multifunctional inverter control) is particularly powerful, as it can simultaneously write operation commands and set frequencies in a single communication, and read the inverter status and output frequency, greatly improving communication efficiency. This instruction supports FX3S (V1.00 or above), FX3G/FX3GC (V1.40 or above), and FX3U/FX3UC (V2.70 or above).

The parameter settings for frequency converter communication include station number (Pr.117 or Pr.331), baud rate (Pr.118 or Pr.332), data format (Pr.119/Pr.333), parity check (Pr.120/Pr.334), etc. The operation mode of the frequency converter needs to be set to "network operation mode" (Pr.79=0 or Pr.340=1), and the communication timeout and retry times should be configured correctly.

5. Non protocol communication (RS/RS2 instructions)

Non protocol communication is the most common data exchange method, allowing PLC to freely format data transmission and reception with any device with RS-232C/RS-485 interface (such as printers, barcode scanners, instruments).

The RS instruction (applicable to all FX series) supports half duplex communication, with a maximum data length of 256 bytes (early models) or 4096 bytes (FX2N/FX3 series). By switching between 16 bit/8-bit processing modes through M8161, D8124 and D8125 respectively define the header and terminator.

The RS2 instruction (only applicable to FX3S/FX3G/FX3GC/FX3U/FX3UC) has more powerful functions:

Supports headers and terminators of up to 4 bytes

Automatic calculation and checksum

Can specify communication channel (ch0/ch1/ch2)

Support full duplex communication

The maximum data length is 4096 bytes

The communication format of the RS2 instruction is set by D8370 (ch0), D8400 (ch1), or D8420 (ch2), and the header and terminator are stored in registers such as D8380~D8381 and D8382~D8383 (ch0), respectively. By setting M8372/M8402/M8422 (send request) and M8373/M8403/M8423 (receive completion flag), reliable data transmission and reception control can be achieved.

6. Programming communication and remote maintenance

Programming communication allows programming software (GX Works2, GX Developer) to be connected through standard RS-422 ports, USB ports, or Ethernet adapters for online monitoring, program upload/download, and debugging. Remote maintenance utilizes modems and telephone lines (or cellular networks) to achieve remote access to PLCs from different locations. In the FX3 series, the initialization settings of the modem can be simplified through the "PP modem mode (CH1/CH2)", without the need for users to input AT commands themselves.

System configuration and hardware selection

Proper selection of communication equipment is the foundation for stable system operation. The following table summarizes the available communication extension modules for each FX series:

Communication interface supports models and typical distances

RS-232C FX3U-232-BD, FX3G-232-BD, FX2N-232-BD, FX3U-232ADP(-MB), FX2NC-232ADP 15 rice

RS-485 FX3U-485-BD, FX3G-485-BD(-RJ), FX2N-485-BD, FX3U-485ADP(-MB), FX2NC-485ADP 50 Meter (BD)/500m (ADP)

RS-422 FX3U-422-BD, FX3G-422-BD, FX2N-422-BD 50 meters

USB FX3U-USB-BD (or standard built-in USB port) 5 meters

Ethernet FX3U-ENET-ADP 100 meters (segment length)

When using multiple communication channels (FX3G/FX3U/FX3UC can support ch1 and ch2), attention should be paid to the limitations of functional combinations. For example, when ch1 sets parallel links, ch2 cannot set N: N networks; But when setting up the computer link in ch1, ch2 can set the N: N network.


Communication parameter setting method

The communication parameters of FX series PLC can be set in two ways:

1. Parameter method (recommended)

In GX Works2, open the [Parameters] → [PLC Parameters] → [PLC System (2)] tab, check the "Run Communication Settings", and then configure the protocol type, data length, parity check, stop bit, baud rate, and header/terminator. This method is applicable to computer links, frequency converter communication, and non protocol communication. For N: N networks and parallel links, do not check 'Run Communication Settings', but configure them through special registers in the program.

2. Procedural Law

Write the set value to a special data register (D8120, D8400, D8420, etc.) using the MOV instruction. For example, setting the RS instruction communication format to "8-bit data, even parity, 1 stop bit, 9600bps, no header/terminator" can execute MOV H0086 D8120. The programming method needs to take effect after the PLC is powered on or when the mode is switched, and its priority is lower than the parameter method.


Troubleshooting Guide

Communication failures typically originate from the following aspects:

1. LED indicator status

SD/RD flashing: normal data transmission and reception

SD flashing, RD constantly off: only sending without receiving a response, check the slave address and wiring

RD flashing, SD constantly off: only receiving but not sending, check the send request flag

All out: No physical connection established, check power supply, cables, and terminal resistance

2. N: N Network Common Error Codes

Direction for troubleshooting the meaning of error codes

01H monitoring timeout, slave station not responding, check wiring and power supply

02H station number error. Duplicate station number or non consecutive number

03H counter error communication data abnormality, check for line noise

04H message format error, invalid data returned from the station

11H main station timeout. The main station did not poll on time. Check the scanning cycle of the main station

3. Parallel link error code

6312/3812: Character error

6313/3813: Checksum error

6314/3814: Format error

4. Computer link error (NAK response)

02H: checksum error

03H: Protocol error (command or format mismatch)

06H: Character area error (illegal device address)

0AH: PLC number error (should be fixed as FFH)

18H: Remote control error (RUN/STOP mode mismatch)

5. General troubleshooting steps

Confirm PLC version: Read the last three digits of D8001 and refer to the applicable version table in the manual.

Check hardware installation: Ensure that the expansion module is securely connected and the terminal resistance is set correctly (110 Ω or 330 Ω).

Validation parameters: Confirm that the communication format matches the device by monitoring D8120/D8400/D8420.

Check program conflicts: Avoid using RS, RS2, EXTR, or inverter instructions simultaneously on the same channel.

Clear error flag: Some errors require restarting the PLC or switching RUN/STOP to clear.


Practical suggestions

For new systems, the FX3 series PLC is preferred as it supports richer communication instructions (such as RS2, IVMC) and higher baud rates (38400bps).

N: The N network is suitable for small distributed control, but it should be noted that the link period increases with the number of stations (in Mode 2, the link time for 8 stations is about 131ms).

If computer links require frequent reading and writing of large amounts of data, it is recommended to use QW/QR commands (FX3 series) to improve efficiency.

In frequency converter communication, reasonable response waiting time (D8150/D8155) and communication retry times should be set to avoid timeouts caused by processing delays in the frequency converter.

When performing remote maintenance, it is necessary to correctly configure the modem initialization parameters (AT command) on the PLC side and register the corresponding AT command on the personal computer side.

  • Sigmatek MDD111-1 DIAS Drive Axis Module
  • Sigmatek DKL042 05-024-042 Terminal Module
  • Sigmatek DM822 Control Module
  • Sigmatek CDM167 12-008-167-O Module
  • Sigmatek TAE151 Touch Display Unit
  • Sigmatek DCC041 SLIDES Module 05-700-041-D
  • Sigmatek AKM65M-ANC2GBB0 PM Servo Motor
  • Sigmatek ETT221 01-230-221 Operator Terminal
  • Sigmatek SLIDES DAM 124 Analog Module
  • Sigmatek AKM31C-ANCNGBB0 Servo Motor
  • Mannesmann Demag Sigmatek CP626 Central Unit
  • SIGMATEK 0332.554.03 Board 371071000154
  • SIGMATEK 12-250-021 Base Plate Back Panel CM5V020
  • SIGMATEK DM162 S-DIAS Digital Mix Module
  • DEMAG ERGOTECH 061 381 66 Sigmatek 9842.243.02 Circuit Board
  • SIGMATEK CP313-1 PLC Module
  • Sigmatek ETV0551-2 VARAN Touch Terminal
  • Sigmatek SDM 081 FS S-Dias Safety Module
  • DEMAG 05-250-023 Ergotech Motherboard with Sigmatek TMS012
  • Sigmatek CM5V020 12-250-023-K Wiring Base
  • Sigma Tek 5000B-37 Attitude Gyro Indicator
  • Sigmatek SDD120-2 DIAS Drive
  • Sigmatek CME221 Memory Module
  • Sigmatek DCP640 DIAS Central Unit
  • Sigmatek STO040 Safety Output Module
  • Sigmatek CET281 Control Panel
  • Sigmatek CIPC LX800 Demag NC5 CPU
  • Sigmatek DKL093 05-024-093 Terminal Module
  • Sigmatek AI088 20-009-088 Analog Input Module
  • Sigmatek CAI888 Analog Input Module
  • SIGMATEK CCA021 12-025-021 Analog Output Module
  • SIGMATEK 1104.579.05 Control Module
  • SIGMATEK SDI100 Digital Input Module
  • SIGMATEK C-IPC 256MB LX800 Compact Dias
  • SIGMATEK 9423.090.02 Control Module
  • SIGMATEK C-IPC 256 Power Supply 148498
  • SIGMATEK CAI025 Analog Input Module
  • SIGMATEK CTO166 Digital Output Module
  • SIGMATEK CP112 20-004-112 Processor Module
  • SIGMATEK CAI887 12-009-887 Safety Module
  • Sigma-Tek 4000B-31 Directional Gyro 1U262-002-42
  • Sigmatek C-IPC 256MB LX800 IPC Controller
  • Sigmatek C-IPC 01-450-031 Industrial PC LX800
  • Sigmatek C-IPC 256 Industrial PC Controller
  • Sigmatek CCP-531 PLC Processor Module
  • Sigmatek CDI163 Digital Input Module
  • Sigmatek ETV0501 VARAN Terminal 12-230-0501
  • Sigmatek CTMS020 C-DIAS Technology Module
  • Sigmatek CIV512 VARAN Switch Module
  • Sigmatek HU011 20-080-011 Interface Module
  • SIGMATEK SLIDES DAM 124 Module
  • SIGMATEK C-IPC 161 01-450-161L Industrial PC
  • SIGMATEK C-IPC 128MB VIA 733MHz 01-450-024-K
  • SIGMATEK 12-780-012 R8-IPC Geode LX800 Module
  • SIGMATEK CAM124 Analog Module
  • SIGMATEK S1 032-8AF61-R4 EZ Servo Motor
  • SIGMATEK CTO163 Digital Output Module
  • SIGMATEK CCP082 12-004-082 Processor Module
  • SIGMATEK CRCH081 C-DIAS Temperature Module
  • SIGMATEK PC322-K 01-310-322-K Industrial PC
  • SIGMATEK SDD310-2 Servo Drive
  • SIGMATEK AI084 Analog Input Module
  • SIGMATEK CRCH081 12-752-081 Temperature Module
  • Sigma-Tek 5000L-4 Attitude Gyro 1U284-001-3
  • SIGMATEK CM5V020 12-250-023-K Wiring Module
  • Sigma-Tek 4000H-6 Directional Gyro IU262-035-7
  • SIGMATEK Dias DCP160 05-004-160 Processor Module
  • SIGMATEK 0147.395.02 Control Module
  • SIGMATEK A1084 Control Module
  • SIGMATEK DI200 20-006-2000 Digital Input Module
  • Sigmatek DNC115 Encoder Module
  • Sigmatek DAM122 05-017-122 Analog Module
  • Sigmatek 9802.289.01 Control Board TA71 Display
  • Sigmatek TO127 20-007-127 Digital Output Module
  • Sigmatek DNC031 05-011-031 Digital Module
  • Sigmatek VI022 20-003-022 Interface Module
  • Sigmatek CAI085 Analog Input Module
  • Sigmatek CP111 S-DIAS CPU Module
  • Sigmatek CTMS030 Krauss Maffei Module
  • Sigmatek CAM123 Control Module
  • Sigmatek TAE732-P 01-240-732-P Touch Display Unit
  • Sigmatek MDM021 Digital Mixed Module
  • Sigmatek DCP642 DIAS Central Unit
  • Sigmatek CST022 12-014-022 C-DIAS Module
  • Sigmatek SRO021 20-893-021 Safety Relay Output
  • Krauss Maffei MC5 Control System Sigmatek
  • Sigmatek DC061 Module 18-24VDC 300mA
  • Herrmann EVT0855 Ultrasonic Welder Touch Panel
  • Sigmatek CIV521 Control Module 1.4A 2W
  • Sigmatek DDI61 05-006-161 Digital Input Module
  • SIGMATEK ETT312-E Touch Terminal 01-230-312
  • Cessna S3326-1 Sigma Tek 5000B-67 Gyro 1U149-015-9
  • SIGMATEK PS101 Power Supply Module
  • SIGMATEK 0332.554.03 Control Module 371071000154
  • SIGMATEK ETT312-E Touch Terminal 01-230-312
  • SIGMATEK CDM163 Control Module
  • SIGMATEK VSV046 16-023-046 Module
  • SIGMATEK AM221 20-017-221 Analog Module
  • SIGMATEK CTS051 12-053-051 Control Module
  • SIGMATEK AM221 20-017-221 Analog Module
  • Sigmatek CSDI161 12-891-161 Safety Input Module
  • Sigma Tek 4000C-1 Directional Gyro Indicator
  • Sigmatek ETV0501 12-230-0501 VARAN Terminal
  • Sigmatek DDM165 SLIDES Module
  • Sigmatek N100 20-011-100 Control Module
  • Sigmatek AKM54K-ANC2R-B0 PM Servo Motor
  • Sigmatek CTO166 Digital Output Module
  • Sigmatek CP212-K 20-004-212-K CPU Module
  • Sigmatek CDI161 Digital Input Module
  • Sigmatek DCC080 05-700-080-2 Control Module
  • SIGMATEK SCP011 S-DIAS Safety CPU
  • SIGMATEK SCP011 S-DIAS Safety CPU
  • SIGMATEK SRO022 Relay Output Module
  • SIGMATEK MDD 121 Drive Axis Module
  • SIGMATEK DSI021 SLIDES Siemens Interface
  • SIGMATEK DIAS DCP161 Module 05-004-161
  • Sigmatek ETT312 Built-in Touch Terminal
  • SIGMATEK DCP 643 DIAS Controller System
  • SIGMATEK CIO021 Multi I/O Module
  • SIGMATEK CTMS020 Control Module
  • Sigmatek CME 221 Memory Module
  • Sigmatek 0420.615.01 Control Board
  • Sigmatek CP111 20-004-111 CPU Module
  • Sigmatek 9405.065.03 Control Board
  • Sigmatek ETEK 01-450-032-K C-IPC 256MB Industrial PC
  • Sigmatek CTO163 12-007-163 Safety Output Module
  • Sigmatek TO081 20-007-081 Digital Output Module
  • Sigmatek SI021 20-022-021 Safety Input Module