ABB NTAC-0x pulse encoder interface module
Safety instructions
Warning types: including dangerous voltage warning, general warning, electrostatic discharge warning, reminding users to have professional electricians perform electrical installation and maintenance. Drivers and related equipment must be properly grounded. After power failure, wait for 5 minutes for the intermediate circuit capacitor to discharge, and use voltage indicating instruments to confirm the completion of discharge. At the same time, be aware of the risks that may arise from the automatic reset function of the driver.
Attention: Emphasize following the manufacturer's operating instructions to avoid hazards such as electric shock.
Overview
Scope of application: Applicable to NTAC-02 (revised version C and above), NDIO-02 (revised version A and above), NAIO-03 (revised version A and above), and includes reference information from earlier versions (NTAC-01, NDIO-01, NAIO-01/02).
Module function:
NTAC-02: Provides a digital pulse encoder interface for obtaining precise speed or position feedback of the motor shaft.
NDIO-02: Provides 2 digital inputs and 2 relay outputs.
NAIO-03: Provides 2 analog inputs and 2 analog outputs, with signal resolution (12 bits) superior to standard analog I/O.
Communication link: Connected to the frequency converter through an optical DDCS protocol communication link, the module and NIOC standard I/O board usually form a circular connection on the CH1 channel of the NAMC board, which acts as the main station to cyclically poll other stations.
install
Module Node Number Setting: Different modules (NTAC, NDIO, NAIO) have their own node numbering rules set through DIP switches inside the module casing. The new settings will take effect when the module is powered on next time.
Mechanical installation: It can be installed inside or outside the drive. When installing outside, attention should be paid to wiring, space, environmental conditions, and grounding requirements. When installing inside, it should be operated by a professional electrician, following steps such as power-off, discharging, and removing the cover plate.
ACS 600 connection: Use fiber optic cables to connect to the NAMC/NDCO board of the driver, paying attention to the color coding of the connectors (blue for RXD, gray/black for TXD). Multiple modules are connected in a circular manner on the same channel, and the terminals connected to different modules vary depending on the application.
Detailed installation and configuration of each module
NTAC-02 pulse encoder interface module: introduces terminal identification, current consumption, wiring requirements (cable type, length, shielding grounding, etc.), encoder output type connection diagram (push-pull, collector open circuit, emitter open circuit), and programming method (set through driver parameters).
NDIO-02 digital I/O expansion module: including terminal identification, wiring recommendations, DI1 hardware filter suppression settings, and programming methods (activating communication through driver parameters).
NAIO-03 Analog I/O Expansion Module: Includes mode selection (unipolar/bipolar), input signal type selection (current/voltage), terminal identification, wiring requirements, programming methods (activates communication through driver parameters to ensure parameter settings correspond to module mode switches).
Appendix Information
Technical data: including detailed technical parameters such as I/O expansion links, enclosure of each module, installation, connectors, input and output.
Environmental conditions: lists the environmental requirements for temperature, humidity, vibration, impact, etc. of the module during operation, storage, and transportation.
Early version information: Introduces the differences, terminal identification, settings, and other information between NTAC-01, NDIO-01, NAIO-01/02 and their corresponding new versions.
Install and start ABB NTAC-0x module
Installation preparation
Confirm compatibility
The module needs to be used in conjunction with the ACS 600 series frequency converter, and the application version must be ≥ V5.0 (standard application) or ≥ V4.2 (system application).
Check the encoder type (push-pull, open collector or open emitter) and prepare matching connecting cables.
Safe power outage
Disconnect the main power supply of the frequency converter and wait for 5 minutes until the intermediate circuit capacitor discharges completely.
Use a voltage indicator to confirm that there is no residual voltage.
Physical installation steps
1. Node number setting
Open the module casing and set the node number (range: 1-31) through the DIP switch.
Rule:
The NTAC module number needs to be an even number (such as 2, 4, 6...).
Node numbers within the same channel cannot be duplicated.
After the setting is completed, it will take effect when powered on again.
2. Mechanical installation
Internal installation (recommended):
Remove the cover plate of the frequency converter and insert the module into the CH1 channel of the NAMC board or NDCO board.
Connect the RXD (blue interface) and TXD (gray/black interface) of the module using fiber optic cables to form a circular topology.