SIEMENS SINUMERIK System 800 General Interface Technology Explanation and Configuration Guide

来源: | 作者:FAN | 发布时间 :2026-01-27 | 223 次浏览: | Share:

SINUMERIK System 800 General Interface Technology Explanation and Configuration Guide

The Siemens SINUMERIK System 800 is a high-performance CNC system widely used in machine tool control, and its powerful data exchange capability relies on a flexible and stable universal interface design. This article is based on the official Universal Interface Planning Guide, which systematically reviews its interface architecture, electrical characteristics, configuration methods, and actual connection cases, providing comprehensive technical references for equipment manufacturers, system integration, and maintenance personnel.


Overview of Interface System

SINUMERIK System 800 provides three main types of serial interfaces to meet the requirements of different transmission distances, environmental immunity and equipment compatibility:

V. 24 (RS232C) interface

Compliant with DIN 66020 and CCITT V.24/V.28 standards, using ± 12V voltage level, with a maximum transmission distance of 30 meters. The interface regards SINUMERIK as a data terminal equipment (DTE), equipped with complete control signal lines (DTR, RTS, DSR, CTS), supporting two transmission modes: line control and character control.

20mA current loop interface (TTY interface)

Using current signal transmission (about 20mA), it has strong anti-interference ability and a transmission distance of up to 1 kilometer. The interface supports duplex operation and can be configured as "active" (providing current) or "passive" (peripheral devices providing current) mode at the SINUMERIK end.

RS422 interface

Adopting differential signal transmission, it combines the integrity of V.24 control signals with the long-distance transmission capability of 20mA interface (up to 1 kilometer). The signal is converted through the AM26LS31 driver and AM26LS33 receiver, and supports level conversion cables to adapt from V.24 to RS422.


Interface Electrical and Pin Definition

1. Pin allocation for V.24/20mA universal interface (25 pin D-Sub socket)

Pin signal name, interface type, corresponding standard signal description

1 E1 (Protective Ground) Universal 101- Protective Ground

2 *TxD V.24 103 – Transmitted Data

3 *RxD V.24 104 – Received Data

4 RTS V.24 105 – Request to Send

5 CTS V.24 106 – Clear to Send

6 DSR V.24 107 – Data Set Ready

7 MEXT V.24 102- Signal Ground

10 TTY2 20mA data transmission+

11 T20mA 20mA transmission power supply

13 TTY4 20mA receiving data+

14 TTY3 20mA receiving data-

20 DTR V.24 108.2 – Data Terminal Ready

2. RS422 interface pin allocation (25 pin D-Sub socket)

In addition to having data and control signal lines corresponding to V.24 (such as TxD, RxD, RTS, CTS, etc.), the RS422 interface adopts differential pair transmission (such as TxD+/-, RxD+/-), significantly improving the ability to resist common mode interference.


Interface adaptation and setting data

The system provides 8 bytes of Setting Data for each interface, configuring the working parameters for input/output directions separately:

Device Code: Identify the type of device control, such as wire controlled device (00H), Xon/Xoff character controlled device (01H), specific tape reader (02H), etc.

Transmission Format: including baud rate (110-9600 baud), number of stop bits (1, 1.5, 2), parity type (even/odd/none), etc.

Special character definitions: such as Xon/Xoff characters, replacement codes for missing characters in EIA codes (such as @,:,=, [, etc.), end of transmission characters (ETX), etc.

Special function bits: such as whether to enable DSR detection, whether to output leading and trailing codes, whether to enable time monitoring, etc.

Signal timing and transmission control

1. Line control equipment (such as PT80 printer, tape reader)

Data input: NC sets RTS=1 to start transmission, pause by lowering RTS; After receiving the end character (M02/M30/ETX), RTS=0 ends.

Data output: Start sending after NC detects CTS=1; The device pauses by lowering CTS; After the output is completed, DTR=0.

2. Character control devices (such as programming workstations, disk drives)

Control data flow through Xon (DC1)/Xoff (DC3) characters.

In most cases, there is no need to connect an RTS/CTS cable, only the DSR is used to detect the device's readiness status.


Interface layout of different controllers

Controller model, interface quantity, interface location and type description

SINUMERIK 805 1-2 panel front V.24/20mA, optional rear V.24 (can be converted to RS422)

SINUMERIK 810/820 1-2 front panel is V.24/20mA, optional rear panel V.24 (GA3 supports RS422 conversion)

SINUMERIK 840 1-2 control panel front V.24/20mA, optional operation panel rear V.24 (can be converted to RS422)

SINUMERIK 850 is equipped with up to 4 front and rear panels, as well as a central controller, all of which are equipped with V.24/20mA and some can be converted to RS422

SINUMERIK 880 has up to 4 interfaces similar to 850, distributed between the control panel and the central controller


Typical I/O device connection example

1. Printer (such as Siemens PT80)

Interface: V.24 or 20mA

Set data: device code 00H, baud rate 300, 2 stop bits, even parity check

Cable: 6FC9 340-8C (V.24) or 6FC9 340-8T (20mA)

  • Eaton PW9130I3000T-XL UPS 3000VA
  • Eaton EDB3225L Molded Case Circuit Breaker
  • Eaton SLX010A1-4A1B0 Contactor
  • Eaton 2D78559G01 Control Module
  • Eaton SPD160208Y2A Surge Protective Device
  • EATON MVX001A0-4 Variable Frequency Drive
  • EATON EASY204-DP Programmable Logic Control Relay
  • EATON 99-6120-01 Industrial Control Interface Module
  • EATON MP-4000 66D2206G01 Motor Protection Relay
  • EATON 101073072-001 Industrial Control Switch Module
  • EATON EEA-PAM-523-A-32 Proportional Amplifier
  • EATON FUE-563004 Industrial Control Unit
  • EATON HJD3225 Molded Case Circuit Breaker
  • EATON FP-4000 FP4201-00 Protective Relay
  • EATON 99-6120-01 Industrial Control Component
  • Eaton MP4010 Motor Protection Relay
  • Eaton XV-102-E6-70TWRC-10 HMI Panel
  • Eaton 245U-E Industrial Wireless Ethernet Bridge
  • Eaton XV-430-10TVB-1-10 HMI Touch Panel
  • Eaton MTL 4850 RS485 Surge Protector
  • EATON 1455A-6503 Industrial Control Relay Module
  • EATON XV-230-57CNN-1-13-1 Industrial HMI Touch Panel
  • EATON XV-440-12TSB-1-10 HMI Touch Panel Operator Interface
  • EATON D100DCR40 Digital Control Relay Smart Relay Controller
  • EATON E4548 Industrial Operator Interface Panel
  • EATON HMI06CE Operator Interface
  • EATON FI3200L Molded Case Circuit Breaker
  • EATON XC-CPU201 PLC Controller
  • EATON XV-102-D8-57TVRC-10 HMI PLC
  • EATON 5P650iR Rackmount UPS
  • Eaton HMI10CE / HMI10CE02 Operator Interface
  • Eaton EEA-PAM-523-A-32 Proportional Amplifier
  • Eaton HTP-SC16M / MTL Surge Protection Device
  • Eaton XC-CPU202-EC4M-8DI-6DO-XV PLC CPU
  • Eaton XV-230-57CNN-1-13-1 HMI Panel
  • EATON XV-303-70-C00-A00-1C Industrial HMI
  • EATON XV-440-12TSB-1-50 Industrial HMI Panel
  • EATON XV-152-D6-10TVR-10 Industrial HMI Touch Panel
  • EATON CAN-16DI/P CAN16DIP Digital Input Module
  • EATON S801+N66N3S Soft Starter Motor Controller
  • EATON XV-303-70-B00-A00S07 High-Performance Touch HMI
  • EATON 92-02123-00 7600C Industrial Control Component
  • EATON HMCP150T4CBP10 Motor Circuit Protector
  • EATON EEA-PAM-553-A-32 Proportional Amplifier
  • EATON XV-102-D6-57TVR-10 Touch Panel HMI
  • Eaton 66D2032GX1 MP-3000 Motor Management Relay
  • Eaton CAN-16DO/0.5A-PK Digital Output Module
  • Eaton XV-102-B5-35TQR-10-PLC HMI with PLC
  • Eaton MP-3000 66D2032GX1 Motor Protection Relay
  • Eaton WL-35717F Circuit Breaker Accessory
  • EATON HFD3150 Molded Case Circuit Breaker
  • EATON HFD3030 Molded Case Circuit Breaker
  • EATON XV-230-57CNN-1-13-1 HMI Touch Panel
  • EATON CEAG CU CG-S 40071360300 Control Unit
  • EATON SDN90186 Industrial Power Supply Module
  • EATON HMCP150U4 Motor Circuit Protector
  • EATON 7801C57 Industrial Control Module
  • EATON HMCP400R5 Motor Circuit Protector
  • EATON MP-3000 Motor Protection Relay
  • EATON PGGLOBL1701DPRO 1785T Touch Panel
  • EATON MFD-CP8-NT CPU Module
  • EATON WL-35717F Vacuum Interrupter
  • EATON EEA-PAM-535-A-32 Amplifier
  • EATON FP5000-00 FP5200-00 66D2041G11
  • EATON Q-504A Current Monitoring Relay
  • UniOP eTOP507 Touch Screen Panel
  • UniOP EK-04 Control Panel IT2 6ZA983-7
  • UniOP ETOP33C-0050 Operator Interface Display Panel
  • UniOP Bkdr-16-0045 Operator Interface Display
  • UniOP ETOP504U101 eTOP504 Touchscreen HMI
  • UNIOP CP01F-02-0045 Industrial Control Panel
  • UNIOP MD02R-04-0045 Alphanumeric Display Terminal
  • UNIOP EXOR ERT-16-0045 Communication Module
  • UNIOP EK-04 CONTROL PANEL Alphanumeric Operator Terminal
  • UNIOP ETOP306-109 Industrial HMI Touch Panel
  • UNIOP ETOP 05-0045 5.7" HMI
  • UNIOP ECT-16-0045 Ethernet HMI Controller
  • UNIOP MD02R-04 Air Compressor HMI
  • UNIOP CP11G-04-0045 11" Graphic HMI
  • UNIOP eTOP308 8" High-Performance HMI
  • UniOP ETOP11-0050 Operator Interface Touch Panel HMI
  • UniOP ETOP307-U301 Operator Interface Touch Panel HMI
  • UniOP EPAD03-0046 Operator Interface Panel Industrial HMI
  • UniOP MD00R-04 SC 4000 Operator Panel Industrial HMI
  • UniOP MD01R-02-0045 Operator Panel Industrial HMI Interface
  • UNIOP MD00R-04-0045 Compact Alphanumeric Display Module
  • UNIOP BKDR-16T-0045 Alphanumeric Terminal
  • UNIOP ETOP515 - U2P1 15-Inch High-Performance HMI
  • UNIOP eTOP05-0045 Compact Touch HMI Specifications
  • UNIOP ER-04-0045 Industrial Operator Interface Module
  • UNIOP MDR00R-04-0045 SC4000 HMI
  • UNIOP EK-12 Operator Panel 6ZA952-7
  • UNIOP ETOP06-0050 5.6" Touch HMI
  • UNIOP MD03R-02-0045 Micro HMI
  • UNIOP eTOP507M 15" High-Performance HMI
  • UNIOP ETOP307-U301 High-Performance Touch HMI
  • UNIOP CP01F-02-0042 Industrial Control Panel
  • UNIOP CP01F-02-0021 Compact Operator Panel
  • UNIOP MKDL 16 0021 LCD Operator Terminal
  • UNIOP MD02R-04-00A6 Alphanumeric Display Module
  • UNIOP eTOP11-0050 10.1" Widescreen HMI
  • UNIOP ETOP 05-0045 5.7" HMI
  • UNIOP eTOP40C-0050 4.3" Compact HMI
  • UNIOP epad05 5" Industrial Tablet HMI
  • UNIOP CP10G-04-0045 10.4" Graphic HMI
  • UniOP EK04 Operator Panel HMI Display Keypad 6ZA983-7
  • UniOP TP-01 Touch Screen Panel Industrial HMI Interface
  • UniOP PQ5187 Operator Interface Module Industrial HMI
  • UniOP MD02R-04-0045 Operator Interface Module
  • UniOP MD03R-02-0042 Operator Interface Module Industrial HMI
  • UNIOP MD00R-04-0045 Text-Based Operator Module
  • UNIOP MKDR-16-0045 Alphanumeric Operator Terminal
  • UNIOP eTOP05-0045 Compact HMI Touch Screen
  • UNIOP EK-04 CONTROL Operator Terminal
  • UNIOP eTOP30-0050 Industrial HMI Touch Panel
  • UNIOP ETOP03-0046 3.5" Touch HMI
  • UNIOP CP01F-02-0045 Function Key HMI
  • UNIOP CP01R-04-0045 Text Display HMI
  • UNIOP eTOP06-0050 5.6" Touch HMI
  • UNIOP eTOP10B-0050 10.1" Touch HMI
  • UNIOP eTOP03-0046 Touch Screen HMI
  • UNIOP MKDR-16-TA-0045 Keypad Display Terminal
  • UNIOP MD02R-04-0042 Micro Display Module
  • UNIOP ECT-16-0045 Ethernet HMI Controller
  • UNIOP CP05R-04-0045 HMI Operator Panel
  • UniOP ETOP05-0045 Operator Panel Industrial HMI Interface
  • UniOP MD02R-04-0045 Operator Interface Module Industrial HMI
  • UniOP MD00R-02-0045 Operator Interface Module Industrial HMI