The PLC-60/75 /E2UK is a 25‑meter length of high‑flexibility shielded braided cable specifically designed for industrial automation, PLC I/O connections, servo motor power/feedback, and drag chain applications. The cable construction includes a fine‑strand copper conductor, a braided shield for EMI protection, and an oil‑resistant PVC jacket suitable for machine tools, conveyor systems, and robotic equipment. The “Braids” designation indicates a tinned copper braid providing 85% optical coverage, ensuring reliable signal integrity in electrically noisy environments.
| Parameter | Value |
|---|---|
| Product Designation | PLC-60/75 /E2UK |
| Length | 25 meters (82 feet) |
| Conductor Material | Bare copper, fine stranded (Class 6) |
| Number of Conductors | Typical 4 or 6 cores (depending on variant, often 4C × 1.5 mm²) |
| Shield | Tinned copper braid, 85% coverage |
| Jacket Material | PVC, oil‑resistant (EN 60811‑404) |
| Rated Voltage | 300/500 V (UL style 2587) |
| Temperature Range (fixed) | -40°C to +80°C |
| Temperature Range (flexing) | -5°C to +80°C |
| Minimum Bending Radius (static) | 5 × cable diameter |
| Minimum Bending Radius (dynamic) | 10 × cable diameter |
| Flame Retardancy | IEC 60332‑1‑2 |
| Approvals | CE, RoHS, UL recognized |

The cable is manufactured with a central filler to maintain roundness, fine‑strand copper conductors (IEC 60228 Class 6) for high flexibility, an extruded inner sheath, a tinned copper braid shield (drain wire optional), and an outer PVC jacket. The braid provides effective screening against electromagnetic interference, making it suitable for analog signals, encoder feedback, and communication lines (RS‑485, CAN, PROFIBUS). The jacket is resistant to mineral oils, cutting fluids, and lubricants commonly found in machine shops.
This cable is used in cable carrier (drag chain) systems for moving machine parts, such as robotic arms, CNC machining centers, and pick‑and‑place equipment. It is also suitable for fixed connections between PLC racks and remote I/O cabinets, servo motor power/brake cables, and shielded control circuits. The 25‑meter length is convenient for installing between a control panel and a remote machine station.
For drag chain applications, the cable should be installed without twisting, and the bending radius should not be exceeded. The cable has a maximum travel speed of 3 m/s and an acceleration of 5 m/s² for flexing applications. Unshielded and shielded versions exist; the “Braids” designation confirms the shielded variant. The /E2UK suffix may indicate a specific European industrial standard (e.g., VDE 0250).
Strip the jacket using a circular cutter, taking care not to nick the braid. For terminating the shield, use a metal cable gland with a 360° contact to the braid. Connect the drain wire (if present) to the functional earth (FE) terminal in the control panel. Do not allow the shield to contact the DIN rail directly unless specified. For analog signals, use a separate cable from power circuits.
Approximate outer diameter: 9–12 mm depending on core count. Weight: 120–150 kg/km. The cable is supplied on a wooden spool. The core colors follow VDE 0293‑308: brown, blue, black, grey, etc. The cable is halogen‑free upon request (not standard).
The PLC-60/75 /E2UK 25‑meter braided shielded cable provides a robust, flexible connection solution for industrial automation, offering reliable EMI protection and oil resistance for machine tool and drag chain environments.