The Schneider Electric HJA36060U43X is a PowerPact H series molded case circuit breaker (MCCB) designed for reliable protection of electrical power distribution systems. This 60 A, 3-pole breaker is rated for 600 V AC with an interrupting capacity of 25 kA at 600 V AC, making it suitable for branch and feeder protection in industrial, commercial, and institutional facilities. The breaker features an I-Line connection on the line side, which allows direct plug-in mounting to I-Line panelboards and switchboards, simplifying installation and reducing wiring time. The HJA36060U43X utilizes an electronic Micrologic 5.2A trip unit, providing adjustable long-time and short-time pickup and delay settings for selective coordination.
The Micrologic 5.2A electronic trip unit offers LSI protection functions: Long-time (overload) protection with adjustable pickup (0.4 to 1.0 x In) and time delay; Short-time (short-circuit) protection with adjustable pickup (1.5 to 10 x In) and time delay; Instantaneous protection with fixed pickup (12 x In). The trip unit includes an ammeter function for displaying real-time current values. The breaker is rated for 80% continuous loading, meaning it can carry 48 A continuously under normal conditions. The phase connection is ABC, and the breaker complies with UL 489 and IEC 60947-2 standards.
The HJA36060U43X is a Green Premium product, compliant with RoHS directives and containing reduced hazardous substances. The breaker has an insulation voltage rating (Ui) of 750 V and an impulse withstand voltage (Uimp) of 8 kV. It is suitable for isolation as per IEC 60947-2. The breaker operates in ambient temperatures from -2 to +70 °C. It includes local signaling via green, orange, and red LEDs for ready, alarm, and trip indication. The breaker has an IP40 degree of protection for the front cover and an IP20 for the enclosure. It is certified by UL, CSA, and NOM. The depth is 86 mm, and the tightening torque for line/load terminals is 14 N·m for larger conductors.
Manufacturer: Schneider Electric (Square D)
Part Number: HJA36060U43X
Series: PowerPact H
Product Type: Molded Case Circuit Breaker
Number of Poles: 3
Rated Current (In): 60 A
Rated Operational Voltage (Ue): 600 V AC, 250 V DC
Interrupting Capacity (Icu): 25 kA at 600 V AC UL; 100 kA at 240 V; 65 kA at 480 V
Trip Unit: Micrologic 5.2A electronic (LSI functions)
Line Connection: I-Line plug-in
Load Connection: Lugs, suitable for Cu/Al cable AWG 14 to AWG 3/0
Continuous Current Rating: 80%
Phase Connection: ABC
Rated Insulation Voltage (Ui): 750 V
Rated Impulse Withstand Voltage (Uimp): 8 kV
Operating Temperature: -2 to +70 °C
Dimensions (H x W x D): 247 mm x 113.8 mm x 86 mm
Certifications: UL 489, CSA, IEC 60947-2, NOM

The Micrologic 5.2A trip unit continuously monitors current through built-in current transformers. For overload conditions (long-time), it uses an I²t algorithm to trip inversely with current magnitude. For short-circuit conditions, the short-time function provides a time-delayed trip for selective coordination with downstream breakers. Instantaneous protection trips without delay for very high currents. The I-Line connection allows quick installation and removal without tools, simplifying panel assembly and replacement. The breaker visually indicates the trip condition with a center-positioned handle and a red trip indicator.
The HJA36060U43X is used as a branch circuit breaker in I-Line panelboards for lighting and power distribution, as feeder protection for industrial control panels, for motor circuit protection (when combined with overload relays), and as a main disconnect in small distribution enclosures.