Status monitoring and alarm:
LED indicator light: Green light constantly on indicates normal operation, red light on indicates fault (overvoltage+10%, undervoltage -25%);
Fault relay: Provides normally open (NO)/normally closed (NC) contacts for remote monitoring of module faults (such as AC input failure, module failure).
Key instructions for installation and use
1. Installation requirements
Installation method: Supports vertical installation of 3U rack or horizontal installation of 2U rack;
Environmental conditions: Indoor dry and dust-free environment, avoiding moisture (non waterproof design), preventing electric shock and equipment damage;
Wiring specification: The pins of the H15 connector are clearly divided (such as pins 10/13 for negative output, pins 16/22 for positive output, and pin 26 for grounding). The analog control version needs to be wired through the AMP 6-core modular connector (model 215-876-1), with a matching 3m analog control wire.
2. Connection and adaptation restrictions
Series parallel operation: unlimited parallel connection (passive current sharing), maximum series total voltage of 500VDC;
Attention to battery charging: If the rated output voltage of the rectifier is greater than 36VDC, its no-load DC output voltage may exceed 42.4VDC, which does not meet the EN standard 10.101 clause. Special attention should be paid to the compliance of the application scenario;
Attention to simulation control: The external control voltage should be within the range of 0-5VDC, as exceeding it may damage the module; When the control connector is unplugged, the output voltage/current automatically drops to the minimum value.
Compliance certification
The product complies with multiple international standards to ensure safety and electromagnetic compatibility:
Safety standards: IEC 60335-1:2010 (Ed4)+A1/A2, IEC 60335-2-29:2002 (Ed4)+A1/A2;
Electromagnetic compatibility (EMC): EN 61000-6-1:2019, EN 61000-6-3:2006+A1, EN 61000-3-2:2018, EN 61000-3-3:2013+A1;
Protection level: IP20 (preventing solid foreign objects from entering).