Operation steps:
Find two small holes on the right side of the logic module and mark them as "default" and "reset".
First press the default switch (using a non-conductive needle), then press the reset switch.
The system immediately restarts and enters safe mode. At this moment:
Ignore persistent registry and use default registry.
Do not load any shortcuts in the Windows Startup folder.
The touch screen may be recalibrated.
Custom key mapping is ignored.
In safe mode, problematic applications can be fixed or deleted, and registry settings can be restored. After a normal restart, the system returns to normal.
Maintenance and Cleaning
Screen cleaning: Disconnect the power, use a soft cloth dipped in mild soapy water or 70% isopropanol to gently wipe, and then wipe dry with a cloth moistened with water. Do not use abrasives or solvents.
Anti glare protective film: It is recommended to use the 2711P-RGxx series protective film for easy cleaning and extended screen life.
Battery and backlight disposal: Mercury containing backlights and lithium batteries need to be classified and recycled according to local environmental regulations.
Frequently Asked Questions Quick Reference Table
Possible causes and solutions for the phenomenon
After powering on, there is no display on the screen, all indicator lights are off, and the power supply is not connected or there is a power failure. Check the DC/AC input voltage; Check the power cord; Replace the power module
The display screen is dim or flickering, and the backlight is aging or the temperature is too high, causing automatic dimming. Check the ambient temperature; Adjust backlight intensity; Replace backlight (700-1500)
Touch screen unresponsive, uncalibrated, or damaged. Enter configuration mode to calibrate touch screen; If ineffective, replace the display module
Keyboard keys are invalid, multi key lock is enabled or key hardware faults are detected. Multi Key Lockout is checked in Keypad settings; Test with USB keyboard, if normal, replace the display module
The application cannot start automatically. The startup option is not configured as Run Current Application; In CF card MER file missing or damaged check startup options; Reload the application; Check Storage Card Windows Startup Shortcut (CE)
Ethernet communication failure due to IP address conflict or DHCP failure; Check if the IP address starts with 169 when the network cable is damaged; Use the ping command; Replace the crossover or straight line
Frequent restarts of the terminal result in unstable power supply voltage; Insufficient memory leads to software crash and power measurement; View system event logs; Increase program memory allocation (CE)