Product positioning and model identification
BE1-11g is a generator specific protection system in the Basler Electric BE1-11 series, designed to replace multiple single function protection relays, control switches, measuring instruments, and alarm indicators scattered in traditional distribution panels with a single device. It is suitable for comprehensive protection and control of synchronous generators, covering the protection range from the generator itself to the step-up transformer and even the grid connection line.
The Style Number is a unique identifier for identifying the functional configuration of BE1-11g. A typical model such as G6xxxxJxPxxxxx can be analyzed bit by bit to understand its hardware configuration:
Example values of code bit meanings
Product Series 1-2 and CT Range G6 (60Hz, 5A CT)/G1 (50Hz, 1A CT)
3rd power type x (see specification table)
4th to 5th bit I/O configuration and differential options JxP (including phase differential)/JxT (including phase differential+synchronizer)
6th communication protocol 5 (IEC 61850)/0 (Modbus/DNP)
Rear shell and installation method, etc
Engineering Tip: When ordering or on-site replacement, it is necessary to verify the complete model code read on the front label of the equipment and in the software. There are essential differences in the number of I/O points, availability of protection functions (such as 87 differential, 25A synchronizer), and communication protocol support among different models, and they cannot be mixed.
Core protection function group and technical characteristics
BE1-11g provides over 20 types of protective functional components, each of which can be independently configured, enabled, and flexibly combined through programmable logic.
1. Overexcitation protection (24) - volt/hertz protection
Overexcitation protection (ANSI 24) monitors the V/Hz ratio to prevent overheating damage caused by saturation of the generator or transformer magnetic core. The 24 elements of BE1-11g provide composite protection features:
Alarm level: Independent alarm thresholds and delays can be set.
Inverse time main protection: supports three types of curves with index n=0.5, 1, and 2, and is precisely fitted to the thermal tolerance curve of the generator/transformer through Time Dial tuning.
Fixed time backup: Provides two independent fixed time components (Definite Time # 1/# 2), which can be used to achieve dual level protection coordination.
Its linear reset characteristic simulates the cooling process of the equipment, avoiding the cumulative error of protection sensitivity under repeated overexcitation conditions. The reset time given in the manual is calculated as
TR=DR × (ET/FST) × 10, where ET is the integrated time and FST is the full-scale trip time.
2. demagnetization protection (40Z) - impedance circle criterion
After the generator loses excitation, the terminal impedance will fall into a specific area. The 40Z component of BE1-11g adopts a dual zone offset impedance circular characteristic:
Zone 1: Small diameter impedance circle, used for detecting severe demagnetization conditions, with fast action.
Zone 2: Large diameter impedance circle, used to detect slight demagnetization or near no-load conditions, with a longer time delay.
The diameter and offset of each impedance circle can be independently adjusted. The offset shifts the impedance circle downwards to consider the steady-state operating point of the generator under under under excitation conditions. The directional supervision angle can further limit the action area and prevent the load impedance from entering by mistake.
3. Out of Step Protection (78OOS) - Single Barrier Solution
When the generator loses synchronization with the system (sliding pole), the terminal impedance will cross the impedance plane along a specific trajectory. The 78OOS component of BE1-11g adopts a Single Blinder scheme:
Mho circle: Limit the action area to ensure that only impedance swings within the range of the generator and step-up transformer can trigger protection.
Blinder A/Blinder B: Two straight lines perpendicular to the R axis. When the impedance trajectory passes through Blinder B and Blinder A in sequence from right to left, and the entire process is within the Mho circle, it is determined as a sliding pole event.
Traverse timer: The traversal time from Blinder B to Blinder A must exceed the Blinder Traverse Time Delay setting to prevent system oscillation and misoperation.
4. Phase current differential protection (87) and neutral point current differential (87N)
The differential protection of BE1-11g is designed specifically for generators and step-up transformers:
87 phase differential: adopts dual slope percentage braking characteristics. The first slope (usually 5-100%) is suitable for light faults, while the second slope (15-140%) is suitable for high current transient faults. The Minimum Constrained Pickup sets the lower limit of action sensitivity.
Harmonic braking: supports independent or shared braking modes for second harmonic (used for braking excitation inrush current) and fifth harmonic (used for braking overexcitation). In shared mode, the sum of three-phase harmonic currents jointly acts on the braking of each phase, and its performance is superior to traditional cross locking schemes.