Welcome to the Industrial Automation website!

NameDescriptionContent
XING-Automation
E-mail  
Password  
  
Forgot password?
  Register
当前位置:

Basler BE1-40Q demagnetization relay setting test

F: | Au:FANS | DA:2026-06-24 | 383 Br: | 🔊 点击朗读正文 ❚❚ | Share:


Analysis of the entire process of setting calculation and on-site testing for Basler BE1-40Q demagnetization relay

The demagnetization protection of synchronous generators is a crucial part of the generator protection system. When the excitation system fails or operates under excitation, the generator may absorb a large amount of reactive power, resulting in rotor overheating, stator end heating, and even step loss, seriously threatening the safety of the unit. The BE1-40Q demagnetization relay of Basler Electric monitors the flow and amplitude of reactive power (var) at the generator end, and quickly acts in the early stage of demagnetization to avoid equipment damage. This article combines the technical manual of the relay to systematically analyze its principles, selection, installation and wiring, setting calculation, and on-site testing methods from an engineering application perspective, providing a practical operation guide for relay protection engineers.


1. Principle of demagnetization protection and action characteristics of BE1-40Q

When a synchronous generator operates normally, it is usually in an overexcitation state and emits reactive power (lagging power factor) to the system. When the excitation current decreases or disappears, the generator begins to absorb reactive power from the system (leading operation), and the rotor magnetic field weakens, increasing the risk of breaking the static stability limit sharply. If the reactive power reserve of the system is sufficient, the generator may enter asynchronous operation, and slip frequency current may be induced in the rotor damping winding, which can cause severe heating in a short period of time.

BE1-40Q adopts the measurement principle based on the voltage current phasor relationship, calculates the reactive power by multiplying the single-phase voltage (V_AB) and single-phase current (I2) and their phase angles, and sends out a trip signal when the reactive power exceeds the set value. The operating characteristics of this relay are manifested on the complex power plane as a straight line at an angle of 8 ° to the horizontal axis, which is placed outside the allowable operating zone of the generator (usually below the static stability limit curve or below the stator end heating limit curve). The set value is the intersection point between the line and the Q axis (reactive power axis), expressed in units (pu).

The internal circuit performs a 68 ° lag phase shift on the voltage signal, so that the relay has the highest sensitivity when the system power factor angle θ=-90 ° (pure reactive power absorption). The action equation can be expressed as:

Panel setting value=VAB ⋅ IB3 ⋅ sin (8 ∘− θ) cos8 ∘

Panel setting value=3V AB ⋅ I B ⋅ cos8 ∘ sin (8 ∘− θ)

This design ensures that the relay can accurately respond to reactive power changes during demagnetization, while being insensitive to changes in active power, avoiding misoperation caused by load fluctuations.


2. Model code interpretation and key selection points

The model code of BE1-40Q consists of multiple characters, defining options such as current/voltage input mode, output contact form, timing characteristics, power type, target indication, and housing. Taking the example model F3E-E1P-B1S2F as an example:

F: The current input is 60Hz single-phase (CT secondary 5A), with other frequency and three-phase options available.

3: The voltage input is 120 Vac line voltage, corresponding to PT secondary 120V; there are also options such as 208V, 240V, etc.

E: The main output is a normally open (NO) contact.

E1: The timing feature is a definite time, and the delay is set by dialing the panel code.

P: The control power supply is in the range of 125Vdc/120Vac, and there are also 48Vdc, 24Vdc, 250Vdc/240Vac, etc.

B: An internal motivational goal indicator.

1: Equipped with a 'Push Test' button.

S: Equipped with power status output contacts (normally closed).

2: The auxiliary output is a normally closed (NC) contact.

F: Semi embedded installation shell.

Selection precautions:

The voltage input level must be consistent with the on-site PT secondary line voltage (120/208/240V).

The rated current input is 5A, and the CT transformation ratio needs to be coordinated with the setting calculation.

If a current type target indicator is required, the main output must be normally open (NO) because the current type target needs to be connected in series in the trip circuit, and normally closed contacts cannot provide a disconnected current path.

Choose between auxiliary output and power status output. If remote signal is required, select auxiliary output. If power monitoring is required, select power status output.

3. Installation wiring and grounding specifications

BE1-40Q adopts S1 standard chassis, which can be semi embedded or protruding installed, and does not require vertical installation due to its solid-state design. The installation dimensions and panel opening diagram can be found in Chapter 4 of the manual. The opening dimensions must be precise to ensure panel sealing.

Key points of electrical wiring:

Voltage input: Connect the line voltage V_AB to the designated terminals (such as terminals 6 and 7). The voltage circuit must be protected by fuses or miniature circuit breakers of the rated voltage level.

Current input: Connect the CT secondary circuit to the current input terminal, pay attention to polarity. The internal CT of the relay has an automatic short-circuit function - when the connecting plug is pulled out, the CT input terminal automatically shorts, avoiding the danger of CT open circuit.

Control power supply: Connect DC or AC power to the power terminals (such as terminals 3 and 4), without polarity requirements, but ensure that the voltage is within the allowable range (such as at least 14V for 24Vdc startup, and can be maintained as low as 12V).

Output contacts: The main output is used for tripping, and the auxiliary output is used for signaling. The wire diameter shall not be less than 14 AWG.

Grounding: The grounding terminal of the shell must be connected to the grounding grid with a copper wire of not less than 12 AWG, and independent leads are recommended.

EMI suppression: If the output contact drives the external relay coil, it is recommended to parallel reverse diodes (DC) or impedance capacitance absorption circuits (AC) at both ends of the coil to suppress electromagnetic interference when the contact is disconnected.

Insulation test warning: Before conducting a withstand voltage test, the connecting plug must be unplugged and the relay must be removed from the chassis, otherwise high voltage may damage the internal electronic components.


4. Setting calculation method and examples

The setting basis for BE1-40Q is the Capability Curve and static stability limit provided by the generator manufacturer. The setting goal is to place an 8 ° diagonal line below the intersection point of the capacity curve and the static stability limit, and calculate the intersection point value of the line with the Q axis as a unit, and then convert it into the specific gear of the panel TAP switch.

Setting steps (example):

Known: The rated apparent power of the generator is 100 MVA, the rated line voltage is 12.8 kV, the CT ratio is 5000/5, and the PT ratio is 12800/120.

Determine the minimum allowable reactive power absorption for demagnetization protection based on the capacity curve, assuming it is 0.4 pu of rated power (i.e. the three-phase transformer absorbs 40 Mvar).

Single phase reactive power=40/3=13.33 Mvar.

Convert the corresponding single-phase current: I=(single-phase reactive power × √ 3)/line voltage=(13.33 × 10 ^ 6 × 1.732)/12800 ≈ 1804 A (primary value).

Converted to CT secondary: Isec=1804/(5000/5)=1.804 A.

If the relay voltage is 120V (PT secondary), the required setting value (single-phase var) is (V_relay/√ 3) × I2/sec=(120/1.732) × 1.804 ≈ 125 var.

Refer to Table 1-1 (120V range LOW gear), 125 var corresponds to TAP position E (LOW gear, E is 125 var). If HI mode is selected, it corresponds to different ranges, but LOW mode meets the requirements here.

In practical engineering, a margin should be left for the setting value, usually taking 90% to 95% of the calculated value, to ensure reliable operation before the static stability limit. At the same time, it is necessary to consider the errors of PT/CT and the normal reactive power fluctuations of the system.

5. Panel operation and parameter setting

Main controls of BE1-40Q panel:

RANGE switch: HI/LOW two levels, switch internal CT ratio, and use TAP switch to achieve wide range setting.

TAP switch: 10 gears (A~K), corresponding to different var values. Specific values can be found on the panel label or in Table 1-1 of the manual.

TIME DELAY DIP: Two decimal digits, set to 0.1-9.9 seconds, with a step size of 0.1 seconds. If set to 00, it is an instantaneous action (<50ms).

Target reset button: Manually reset the target indicator that has been activated.

Output test button: Press with a non-conductive rod to manually excite the output relay for circuit verification.

Setting process:

Determine the TAP value and RANGE gear based on the tuning calculation.

Set a delay according to the system's requirements for time limits (such as setting the generator to 0.5-2.0 seconds to avoid system oscillation and external fault transients).

If instantaneous action is required, set the delay code to 00.


6. On site testing and verification methods

Before production or during regular calibration, it is necessary to conduct action value and delay tests on the relay. The following steps are based on the recommended test circuit in the manual (Figure 5-2).

6.1 Action value (Pickup) verification

Test circuit: The voltage source is connected to the voltage input terminal of the relay, and the current source is connected to the current input terminal, with adjustable phase between the two.

Set RANGE=LOW, TAP=A (minimum value), and set the delay to 10 (1.0s) to prevent frequent actions.

Apply rated voltage (120V/208V/240V depending on the model), adjust the phase of the current source to lag by 60 ° (simulate reactive power absorption).

Slowly increase the current until the PICKUP LED lights up, and record the effective voltage and current values at this time.

Calculate the actual single-phase var=(V/√ 3) × I, and compare it with the nominal value of the TAP gear in Table 1-1. The error should be within ± 2% or ± 0.1 var.

Test each TAP and HI gear in sequence, and record all points.

6.2 Delay characteristic verification

Using the same wiring, set TAP to A and delay to 11 (1.1s), 55 (5.5s), and 99 (9.9s), respectively.

The current jumps from zero to twice the operating current of the TAP gear (refer to Table 5-2 in the manual).

Measure the time from current application to output contact displacement with a timer, which should match the set value with an error within ± 5% or ± 50ms (whichever is greater).

6.3 Verification of Action Characteristic Curve (optional)

For situations where the entire 8 ° diagonal line needs to be verified, the operating current can be measured at different current phase angles (simulating different power factors), the corresponding P and Q can be calculated, and plotted on the complex power plane to verify whether it matches the theoretical 8 ° straight line. This method is suitable for laboratory calibration or fault analysis.

6.4 Output Circuit and Target Verification

Use the "Output Test" button to manually excite the output relay, observe whether the main and auxiliary contacts have shifted, and whether the target indicator is lit (if it is a current type, ensure that the tripping circuit has a current of at least 200mA).

Test power status output: Disconnect the control power supply, confirm that the status contacts are closed (normally closed), and open the contacts after restoring the power supply.


7. Maintenance and Storage Suggestions

BE1-40Q is a solid-state relay with simple daily maintenance, requiring only regular (recommended annual) functional testing. If stored for a long time as a spare part, it should be powered on for 30 minutes every year to maintain the performance of the internal aluminum electrolytic capacitor and extend its service life. If a malfunction occurs, do not disassemble or repair it on site. Instead, contact the manufacturer's technical support.

  • Basler DECS-250-CGCM-LN2SA1C Digital Excitation Control System
  • Valmet Automation PLC Module A413171
  • Valmet Automation 542852-3A Rack-Mount Cross Connect Panel
  • Valmet Marine Damatic M851565 Main Keyboard
  • Valmet TIU 6 Printed Circuit Board A413110
  • Metso Valmet U4440253V1.1 RMI CPU 300
  • Metso Valmet A413016 Ver.12 NCU2
  • Valmet M851565 Damatic Keyboard
  • Valmet ATB16-4 16 Channel Relay Card
  • Valmet Metso A413331 SPU Power Supply
  • Valmet PUD 10B Automation Control Rack
  • Valmet MT917 ABMB DMU PCB I/O Module
  • Valmet M851565 Damatic Keyboard Mkb2
  • Valmet EDS-518A-MM-SC Ethernet Gateway
  • Valmet 542836-6A PCB Card
  • Valmet ATB16-4/2 Terminal Board 9144047
  • Valmet ATB16-4 Controller Board 0-50°C 4-20mA Analog Output
  • Valmet 542852-3A Slot Rack Chassis Module
  • Valmet A413026 Ver.M1 FBC Board
  • Valmet IQ Basis Weight SH Sending Assembly A418081
  • Valmet PMB 2R Monolithic Backplane 8-Slot PCB 542821-5A and -5B
  • Valmet ATB16-4 16-Channel Relay Card Controller Board 22195028
  • Valmet Diff-EL SL6NK227SF0 Pressure Transmitter 0-380 mBar
  • Valmet A413110 TIU6 Board Ver.M1
  • Neles Automation A413278 Control Module
  • Valmet BCUTB Terminal Module 10101006 11091002
  • Valmet Senso 160 Measuring Station Display 160.2
  • Valmet AIU 1A Analog Input Unit M851245
  • Valmet IQ Web Caliper Sensor A420734
  • Valmet M851040/M8510401 Memory Board
  • Valmet AN35S1MC02RA Valve
  • Valmet M851121 M2 Cross Connect Panel
  • Valmet AIU-8 Simulator Board 421522-1A
  • Metso BIU 82 D200533 Binary Input Unit
  • Valmet M851121 M2 Module Rack
  • Valmet A413383 PC Board Module
  • Valmet N0542 NO54 ABMB PCB - 545200-3A Board
  • Valmet Metso IOP304 Input Module 181503
  • Valmet PDP601 Distributed Processing Unit 181585
  • Valmet A413084 CPU Board - Processor Module for Automation Systems
  • Valmet AIU 16T Analog Input Module M8512081 M1
  • Valmet AIU 16 Analog Input Module 545100-3A and 545100-3B
  • Metso Valmet BIU4 A413146 Binary Input Unit
  • Valmet AIU-8 Simulateur Board 421522-1a Analog Simulator
  • Valmet BIU8A Binary Input Unit 542803-3B M851222 M1
  • Valmet IQ Web Color DH Photoelectric Sensor A418182 2.04
  • Valmet A413200 AIU-8 Simulator Board 191151 421522-1A
  • Valmet Automation SCU M851006 System Control Unit Module
  • Valmet 857565/851565 Damatic Keyboard IP40 5V Operator Interface
  • Valmet A413077 FBC2 Module Rev 06 Field Bus Controller
  • Valmet DMU 2 PCB Module 545142-3A DM Data Management Unit
  • Valmet AIU16T PCB Card M851208 Analog Input Module
  • Valmet A413181 PLU Board
  • Valmet m851006 SCU Module
  • Valmet Metso 181226 Digital Input Module
  • Valmet AIU16T Analog Input Module - 16-Channel 65421466-2B MT924 V1.3
  • Valmet WIN3136875 Slide Clutch
  • Metso Valmet TIU61 A413111 Temperature Input Unit
  • Valmet MC12S Slitter Motor
  • Valmet A413139 AOH4 Board - Analog Output High Module
  • Valmet A409001 BIU85 Board
  • Valmet A413063 DMU Board
  • Valmet A413325 IPU I/O Power Unit
  • Valmet M851004 M2 CPU Module
  • Valmet IOP345 Digital Input Module
  • Metso Valmet A413215 Communication Board
  • Valmet DIFF-EL 80 M1 Transmitter
  • Valmet A413001 CPU Module
  • Valmet M899520 TDC-2 Module
  • Valmet A409001 BIU85 Board
  • Metso Valmet A413005 CPU Module
  • VALMET PUD 10 B Process Automation Rack with CPU SCU Module
  • Valmet A413091 GDU1 Board
  • VALMET M851006 M2 SCU Module
  • Lyngso Valmet Marine 990.896.000 Position Loop Card
  • Valmet Cooking Liquor Measurement 3417H
  • VALMET ABMB MT831 PCB Card
  • Valmet Automation A413325 IPU I/O Power Unit
  • Valmet Metso Consistency Transmitter Smart Pulp M2
  • VALMET METSO A413274 Connection Module
  • VALMET PI33S1KSA02RSA-ELI26 Switch
  • VALMET ND9103HN-CE07-K05 Intelligent Valve Controller
  • VALMET PMB 2R 16 Slot Backplane PCB Card
  • NELES VALMET A413135 AOU 4 Output Module
  • Metso Valmet A413345 FPU Power Unit
  • VALMET A413171 PIC Module
  • VALMET A413620 Repeater Module
  • Valmet M851521 Memory Card
  • Valmet DIFF-EL 140 M1 Transmitter
  • Valmet A413064 DMU Module
  • Valmet IOP371 I/O Bus Extender Module
  • Valmet Cooking Liquor Measurement 3400 Model 3417H
  • Metso Valmet A413043 CPU Module – Industrial Processor
  • Valmet BIU4 M851221 Binary Input Module
  • Valmet PMB 1S CPU SCU Rack Module
  • Valmet A413248 Controller Module
  • Valmet PDP601 Distributed Processing Unit
  • VALMET M851004 M2 CPU Printed Circuit Board Module
  • Metso Valmet A413045 Ver.05 CPU Module
  • Valmet A413181 Ver.05 PLU1 Board
  • Lyngso Valmet ATB16 Controller Board
  • VALMET AIU 16 Analog Input Unit 545100-3A/3B
  • VALMET PUD 10 B Power Supply PCB Rack Module
  • Valmet MS-50V/120V Bearing Unit
  • Valmet PDP603 Distributed Processing Unit – DPU Module
  • Valmet A413110 TIU Board – Terminal Interface Unit
  • Valmet S420154 I/O Backplane PCB – Printed Circuit Board
  • Valmet A413173 Industrial Control Module
  • Valmet A413044 CPU Module
  • Valmet A4IU1 Analog I/O Module
  • Valmet A413325 IPU Power Unit – PLC Module
  • Valmet M851002 CPU Module – Central Processing Unit
  • Valmet PUD10B Power Supply Board
  • Valmet K00990 Master CPU Electronic Assy
  • Valmet Metso IOP345 Input Module
  • Metso Automation T545215 Board
  • Valmet Metso IOP304 Input Module
  • Valmet 542844-6A SCU Module
  • Metso A413043 Ver.11 Valmet CPU Module
  • Valmet Automation BIU 8A Input Module
  • Metso A413044 Ver05 Valmet CPU Module
  • VALMET 542821-5A Control System Rack Module
  • Metso A413005 Ver.04 Valmet CPU Module
  • Valmet M851207 AIU16 Card
  • Valmet BIU8 Binary Input Unit
  • VALMET 547070-2B CPU Printed Circuit Board Module
  • Valmet Automation A413325 Power Module
  • VALMET AUTOMATION A413135 AOU4 Module