Welcome to the Industrial Automation website!

NameDescriptionContent
XING-Automation
E-mail  
Password  
  
Forgot password?
  Register
当前位置:

Basler DGC-2020 Generator Set Controller: Integrated Control and Debugging Guide

F: | Au:FANS | DA:2026-06-25 | 646 Br: | 🔊 点击朗读正文 ❚❚ ▶ | Share:

Mains Fail Transfer

Run with Load logic input

Demand Start/Stop

3.2 Self activation logic

The self starting modes of DGC-2020 are independent of each other but have priority logic. If any starting condition is true, the unit will operate; The unit will only shut down when all start-up conditions are false. This design ensures reliable operation under various working conditions.


Circuit breaker management and automatic synchronization

4.1 Circuit Breaker Control

DGC-2020 can control both generator circuit breakers and mains circuit breakers simultaneously. Supports two contact output modes:

Pulse mode: emit pulses of the set width (0.01-0.80 seconds)

Continuous mode: Continuous output holding (applicable to circuit breakers with holding coils)

Before closing the circuit breaker, the controller will verify:

Stable voltage on the generator side

The voltage on the busbar side is stable or determined to be a dead busbar

Synchronization condition met (when closed to live busbar)

4.2 Synchronizer Operation

The automatic synchronizer of DGC-2020 supports two modes:

Phase Lock Loop mode:

The controller adjusts the generator voltage and frequency through the rise and fall signals of the speed regulator and AVR

When the voltage difference, frequency difference, and phase angle difference all meet the set values, issue a closing command

Predictive mode:

Added circuit breaker closing time compensation on the basis of PLL

The controller calculates the advance phase angle based on the measured slip frequency to ensure that the phase angle approaches zero at the moment of circuit breaker contact closure

Troubleshooting steps for synchronizer not working:

Confirm that the style number includes a synchronizer option

Check if the GEN STANBLE and BUS STANBLE status indicator lights are on

Confirm that the controller is initiating a closing request

If the synchronization stops after a brief activation, check if a Sync Fail pre alarm has been triggered


Load distribution and parallel connection of multiple machines (LSM-2020)

5.1 Load distribution principle

DGC-2020 is used in conjunction with LSM-2020 load distribution module to achieve parallel operation of multiple machines. The core mechanism is to simulate load distribution lines:

Each generator's LSM-2020 outputs a 0-10V signal, which is proportional to the actual output kW of the unit

The load distribution lines of all units are connected together, and the intersection voltage reflects the average value per unit of the total system load

Each unit adjusts its own output by using the intersection voltage as the set value for the kW controller

5.2 Parameter tuning of PID controller

Load distribution involves three PID controllers:

Speed controller: Adjust engine speed before parallel synchronization

Voltage controller: Adjust the generator voltage during synchronization before parallel connection

KW load controller: regulating active power distribution during parallel operation

Basic process of parameter tuning:

Set all gains to zero

Adjust the proportional gain (Kp) until the system approaches instability, and then reduce it to half of that value

Using one tenth of Kp as the initial value of the integral gain (Ki), gradually increase it until it becomes unstable and then halve it

If overshoot needs to be reduced, introduce differential gain (Kd) and use it in conjunction with filtering constant (Td)

5.3 Unit sorting and load management

DGC-2020 supports automatic unit start stop sorting based on the following principles:

Rotation of running time: prioritize starting based on the minimum number of running hours

Balanced running time: prioritize starting based on the maximum number of running hours

Capacity priority: Start the unit with the highest or lowest capacity first

ID sorting: Start in sequence according to the set sorting ID

The Demand Start/Stop function automatically starts and stops the unit based on the total system load, achieving economic operation.

CANbus communication and ECU integration

6.1 Supported ECU protocols

The CANbus interface of DGC-2020 supports:

SAE J1939 standard protocol: obtains oil pressure, coolant temperature, engine speed, and can read diagnostic trouble codes (DTCs)

MTU protocol: supports MTU MDEC, MTU ADEC, and MTU ECU7, and can obtain MTU specific alarm and pre alarm information

Volvo Penta Protocol: Supports EDC3 and EMS2 controllers

6.2 ECU Power Management

For ECUs that require power-off to shut down (such as some Detroit Diesel J1939 ECUs), DGC-2020 provides four timer settings:

Engine shutdown time: The time (1-60 seconds) for the ECU to remain powered off after shutdown, ensuring that the engine comes to a complete stop

Pulse cycle: The interval (1-60 minutes) between ECU re powering to obtain data

Stabilization time: The time it takes for data to stabilize after power on (5.5-30 seconds)

Response timeout: Maximum waiting time for attempting communication (1-60 seconds)

6.3 Diagnostic Trouble Code (DTC)

DGC-2020 can receive and store DTCs from ECU. Each DTC contains:

SPN (Suspicious Parameter Number): Identify the diagnostic object

FMI (Failure Mode Identifier): Define the type of fault

Number of occurrences: Record the number of fault activations

  • Bonfiglioli ACT401-19A Frequency Inverter
  • Bonfiglioli C102PP71 Gear Motor 13.4:1
  • Bonfiglioli C312 P P90 Speed Reducer
  • VEM K21R 71 G 4 Motor with Bonfiglioli VF44
  • Bonfiglioli C31 3 P P63 PV Bevel Gear Reducer V5
  • Bonfiglioli WR75UD28150P71B5B3 Gearbox
  • Bonfiglioli ACT401-13FA Frequency Inverter
  • Bonfiglioli VF62/P Worm Gearbox 38:1
  • Bonfiglioli ME210124001Y C Helical Gearbox
  • Bonfiglioli VF63PIP90BI4 Gearbox
  • Bonfiglioli ACT 401-19A Frequency Inverter
  • Bonfiglioli C102PP71 Variable Speed Gearmotor
  • Bonfiglioli C312 P P90 Reducer with Clutch
  • Bonfiglioli VF44 F1 10 Gearmotor with VEM Motor
  • Bonfiglioli C31 3 P P63 PV V5 Reducer
  • Bonfiglioli WR75UD28150P71B5B3 Gearbox
  • Bonfiglioli ACT401-13FA Frequency Inverter
  • Bonfiglioli VF 62/P Worm Gearmotor 38 to 1
  • Bonfiglioli ME210124001Y Inline Gearbox
  • Bonfiglioli VF63PIP90BI4 Worm Gearbox
  • Bonfiglioli VF86FC256 Worm Gearbox 1010B03004
  • Bonfiglioli VF44F1 Gearmotor 0.43kW 460V
  • Bonfiglioli W 75 UF1 D30 P80 B14 Gearbox i=100
  • Bonfiglioli VF63NP80B5 Worm Gearbox
  • Bonfiglioli 300R3133FPP80POG0A Gear Reducer
  • Bonfiglioli VF49F1N56C Gearbox
  • Bonfiglioli Trasmittal 300L19 Gearmotor with MEZ UD 1104 Motor
  • Bonfiglioli BCS30 Permanent Magnet Motor with Encoder
  • Bonfiglioli BN56B4 Gearmotor with VF30 Reducer
  • Bonfiglioli VF44 Gearbox 100480150
  • Bonfiglioli VF63PIP90B14 Gearbox
  • Bonfiglioli 830420150 BN63A4 230/400-50 IP55 CLF B14 with VF30F2 P63B14B3-I40
  • Bonfiglioli BN63A2 Motor
  • Bonfiglioli VF44 ALP63B5 Gearbox
  • Bonfiglioli A102 UR P80 Gearbox
  • Bonfiglioli MP 105 2 16 STD 95A1 CD 19 S1 OR SB KE Planetary Gearbox
  • Bonfiglioli T56BN/4 Motor
  • Bonfiglioli 8E20020594-M285018 Motor
  • Bonfiglioli VF49 V P71 B5 Gearbox
  • Bonfiglioli X VFR49 L1 FA1 180 P63B5 B3 Gearbox
  • Bonfiglioli W63U7P90B14V6 Right Angle Gear Reducer
  • Bonfiglioli VF/W30/63UFC2 Gear Reducer i=168
  • Bonfiglioli VF44 Gear Reducer 100480150
  • Bonfiglioli ACU 201-07 FA Frequency Converter
  • Bonfiglioli BN-80B-4 Motor with VF63 Gearbox 38:1
  • Bonfiglioli MVF 49 Gear Reducer for Servo Motor
  • Bonfiglioli ACT 400-034 A Frequency Inverter 11kW
  • Bonfiglioli SYN10-S-220-03-AF AC Drive 0.5HP
  • Bonfiglioli LC 090 1 7 STD FM CD 19 KE Gearbox
  • Bonfiglioli TQFK070350GR80A1CD Gear Unit
  • Bonfiglioli BN 80 B6 FD Three Phase Motor
  • Bonfiglioli W63U Worm Gear Reducer
  • Bonfiglioli 830G2310M-B048052 Gear Motor
  • Bonfiglioli VF49P128P71B5B3 Worm Gearbox
  • Bonfiglioli W75UD30719/140B3 Worm Gearbox
  • Bonfiglioli VF49F17HSB3 Worm Gearbox
  • Bonfiglioli C12 2P 20.6 P90 B3 Gearbox
  • Bonfiglioli BN80B4 623136 Geared Motor
  • Bonfiglioli 4APC3-4 9142882 Geared Motor 0.18 kW
  • Bonfiglioli W86 80/90-B5 Worm Gear Reducer 20:1
  • Bonfiglioli ACU 210-07 1 FA PLC Peripheral Module
  • Bonfiglioli MVF44/F Worm Gearbox
  • Bonfiglioli W63U Worm Gear Reducer
  • Bonfiglioli BN63A2 Electric Motor
  • Bonfiglioli BN 132 M B 4 Electric Motor 9.2kW
  • Bonfiglioli VF49 L1 P1 P63B5 Worm Reducer i=45
  • Bonfiglioli C413 P S2 7717/1000 Gearmotor 1.5kW
  • Bonfiglioli VF49F1P63B5B3 Worm Gearbox
  • Bonfiglioli BTD5-1870-05-400-ENC8A Servo Motor
  • Bonfiglioli ACU401-03FA Frequency Inverter
  • Bonfiglioli MVF63/N Gearbox with AEG Servomotor
  • Bonfiglioli BN80A4 Gearmotor VF49L1P1P80B14
  • Bonfiglioli VFR 72/FC2 Gear Reducer
  • Bonfiglioli W R 86 U 120 Gearbox Assembly
  • Bonfiglioli W 75 U 30 Gear Reducer
  • Bonfiglioli W R 86 U 120 P80 B5 V5 Gearbox
  • Bonfiglioli RAO 50/DC Gearbox
  • Bonfiglioli VF49 F1 P63B5 Gearmotor with SPZ MS6324
  • Bonfiglioli X_LC 090 Planetary Gearbox
  • Bonfiglioli A302 UH35 P90 Gearbox
  • Bonfiglioli VF63FCHS Worm Gearbox 103100390
  • Bonfiglioli VF 44 P63 B14 Gearbox M00480210008
  • Bonfiglioli MPD1006S0006 Precision Planetary Gearbox
  • Bonfiglioli VF49F1N56C Worm Gearbox
  • Bonfiglioli TR G 105 3 20 STD Planetary Reducer
  • Bonfiglioli VFR49P1P63B5 Worm Gearbox
  • Bonfiglioli WR 86 U 120 P80 B5 V5 Gearbox 2G30013944
  • Bonfiglioli BRA 400-060 BF2 Brake Chopper
  • Bonfiglioli VF49P P71B5 Worm Gearbox
  • Bonfiglioli C402 P VG1 Gear Speed Reducer 31.4:1
  • Bonfiglioli ISMET LCVT050 DK308/50 Line Reactor
  • Bonfiglioli C 22 2 F GR063 Gearbox
  • Bonfiglioli C31 3 P P63 PV V5 Reducer
  • Bonfiglioli CM-485 T Communication Module
  • Bonfiglioli W75UF1D30P90B5 Gearbox
  • Bonfiglioli BN63 B4 VF49 Gearmotor 0.18kW
  • Bonfiglioli ACT 400-004 FA Frequency Inverter
  • Bonfiglioli W110U100P90B5B3 Worm Gearbox
  • Bonfiglioli SYN10 T 400 05 AF Inverter
  • Bonfiglioli MP080.1.4.15.16.40.80.100 Gearbox
  • Bonfiglioli SYN10S Inverter
  • Bonfiglioli VF44L2P160 Gearmotor
  • Bonfiglioli W 86 U 40 P90 B5 B3 Gear Reducer
  • Bonfiglioli BTD5-1870-05-400 Servomotor
  • Bonfiglioli MP 080 2 2C Gearbox with BLDC Motor
  • Bonfiglioli MP080.1.10 Planetary Gearbox
  • Bonfiglioli C212PHS Reducer
  • Bonfiglioli MVF 49F1 Gearbox with ICME T71B4
  • Bonfiglioli VF 49 v P71 B5 Gearbox
  • Bonfiglioli VF 44 P1 Gearmotor
  • Bonfiglioli C 22 2 NP 6.1 Helical Gearbox
  • Bonfiglioli F203 316.9 Gearbox with Kaiser Motor
  • Bonfiglioli SYN10 S 220 07 AF Frequency Inverter
  • Bonfiglioli 301L251.8-HC-P90 Gearbox 1/51.8
  • Bonfiglioli ACT401-25A Frequency Inverter
  • Bonfiglioli W75 U D30 30 P90B14 B3 Worm Drive
  • Bonfiglioli 830G2310M-307638 Motor
  • Bonfiglioli C112-P-P90 Inline Gearbox i=6.2
  • Bonfiglioli SYN10-S-220-03-AF AC Drive
  • Bonfiglioli VFR49 A HS Worm Drive i=180 B3
  • Bonfiglioli ACT 401-29 A AC VFD Drive 22kW
  • Bonfiglioli VF49PIP63B14 Gearbox
  • Bonfiglioli ANG 410-18 2 FA Inverter
  • Bonfiglioli GVX2000-7.5-T Converter
  • Bonfiglioli EM-ENC-02-24 Optical Module
  • Bonfiglioli ACT 401-33 A VFD Drive
  • Bonfiglioli MVF 49F1 Gearbox with ICME T71B4
  • Bonfiglioli BN112M4 Motor