Welcome to the Industrial Automation website!

NameDescriptionContent
XING-Automation
E-mail  
Password  
  
Forgot password?
  Register
当前位置:

Basler VR63-4C/UL Voltage Regulator

F: | Au:FANS | DA:2026-06-26 | 471 Br: | 🔊 点击朗读正文 ❚❚ ▶ | Share:


Basler VR63-4C/UL Voltage Regulator: Technical Depth Analysis and Engineering Application

Product positioning and technical overview

VR63-4C/UL is a single-phase input, DC output voltage regulator suitable for small and medium-sized synchronous generator sets equipped with brushless excitation systems. Its design goal is to provide stable and precise terminal voltage control for generators in a wide temperature range (-40 ° C to+60 ° C) and harsh vibration environments.

Core functional highlights:

Frequency Compensation: Suppresses premature voltage recovery during sudden load increases and assists the prime mover in smoothly receiving loads.

Overexcitation Shutdown: Monitor the excitation voltage, automatically cut off the output when abnormal high excitation is detected, and protect the excitation winding.

Solid state excitation circuit: It can achieve reliable voltage building when the residual magnetism of the generator is as low as 6 Vac.

Built in EMI filter: meets industrial electromagnetic compatibility requirements.

The product has passed UL 6200:2019 certification and CSA certification, and is suitable for industrial power generation applications in North America and international markets.


In depth interpretation of technical specifications

1. DC output capability

Parameter values

Maximum continuous output 4 Adc @ 63 Vdc (252W)

One minute strong excitation output 7 Adc @ 100 Vdc (700W, input 120Vac)

The output capability determines the adaptation range of the matching excitation winding. The manual specifies that the DC resistance of the excitation winding must be between 15 Ω and 100 Ω. If the resistance is lower than 15 Ω, a current limiting resistor must be connected in series to avoid output overload; If it is higher than 100 Ω, sufficient excitation current may not be provided.

2. Communication input and detection

Power input: 85-139 Vac, single-phase, 50/60Hz ± 5%, maximum capacity 450VA

Voltage detection: Shared terminals with power input (terminals 3 and 4), with a detection range of 85-139 Vac

Voltage regulation range: 85-139 Vac (corresponding to the generator terminal voltage setting range)

Important engineering reminder: The power input and detection input share the same terminal, which means that the control power of the regulator is taken from the generator terminal voltage or auxiliary winding. The advantage of this self powered design is that it does not require an independent external power source, but the disadvantage is that when the voltage at the generator terminal drops severely, the regulator may lose control due to insufficient power supply.

3. Adjust accuracy and response speed

Steady state accuracy: better than ± 1.0% within the range of no load to full load

Response time: When detecting a ± 5% step change in voltage, the response time is less than 1.5 power frequency cycles (i.e.<25ms @ 60Hz)

4. Overexcitation shutdown characteristics

Overexcitation shutdown is the core safety function that distinguishes VR63-4C/UL from ordinary AVR. The action logic is:

When the excitation voltage exceeds 95 Vdc ± 5 Vdc, the shutdown delay is inversely proportional to the overvoltage amplitude (the higher the voltage, the faster the action).

When the excitation voltage exceeds 140 Vdc ± 5 Vdc, the excitation output is forcibly cut off within 0.2 seconds.

After shutdown, the input voltage needs to be reduced to below 6 Vac (if the power is turned off for at least 2 seconds) before resetting.

This feature can effectively prevent rotor winding overheating and damage in the event of excitation circuit failure or regulator loss of control.

5. Environmental and physical specifications

Working temperature: -40 ° C to+60 ° C, storage temperature: -65 ° C to+85 ° C

Vibration tolerance: 5-26Hz/1.2g, 27-52Hz/0.036 "dual amplitude, 53-1000Hz/5g

Impact tolerance: 20g (three-axis)

Weight: Only 283g (10 oz), lightweight design, can be directly installed in the generator control box.


Frequency compensation mechanism and tuning method

The frequency compensation function aims to improve the dynamic response of the generator when there is a sudden increase in load. When the load suddenly increases, the speed of the prime mover will briefly decrease, and the frequency of the generator will also decrease accordingly. If there is no frequency compensation, the AVR will fully maintain the voltage setting value, which may cause the prime mover to overload or even stall.

The frequency compensation characteristic curve of VR63-4C/UL is shown in Figure 3 (manual):

When the frequency is higher than the inflection point frequency, the regulator works normally and maintains the set voltage.

When the frequency drops below the inflection point frequency, the voltage setting value linearly decreases at a fixed slope to assist the prime mover in restoring speed.

The factory preset inflection point frequency is 45Hz (50Hz system).

On site frequency adjustment operation:

If used in a 60Hz system, the inflection point frequency needs to be adjusted to 55Hz.

Operation method: Cut off the external HZ jumper and wrap the cut ends with insulation to ensure that they are not exposed.

This operation is simple but crucial - if the 60Hz system does not cut the jumper and the inflection point is still 45Hz, frequency compensation will not intervene during normal operation (above 50Hz), but may act too early or too late in low-frequency events.

Installation and Wiring Engineering Guide

1. Installation location

The regulator can be installed in any direction without affecting performance. The size of the panel opening is shown in Figure 1 of the manual (inches/millimeters double labeled). Due to its weight of only 283g, it can be directly fixed on the inner wall of the control box or in the generator junction box.

2. Wiring topology

Figure 2 of the manual provides four typical wiring diagrams, covering common generator wiring methods:

208/240Vac three-phase four wire: used for common industrial power distribution

120/240Vac single-phase with neutral wire: used for single-phase or phase separated power generation

240Vac three-phase three wire: used for three-phase systems without neutral wires

Solution with remote voltage regulator potentiometer: Remote control is achieved by cutting off the VAR line and connecting it to a 1k Ω potentiometer

Excitation output wiring:

The F+end is connected to the positive pole of the excitation machine magnetic field, and the F - end is connected to the negative pole.

It is strictly prohibited to connect switches in series in the F+and F - circuits - the excitation shutdown function is achieved through internal control of the regulator, rather than external contacts.

Fuse configuration:

It is recommended to install high breaking capacity fuses in the power input circuit to protect the circuit from short-circuit faults.

Important: The fuse must be installed according to the wiring diagram to avoid accidentally cutting off the excitation current circuit.


Principles of Regulation and Control

1. Voltage regulation

Internal potentiometer: Rotate clockwise to increase the voltage at the generator terminal, and counterclockwise to decrease.

Remote adjustment: When remote voltage adjustment is required, the VAR wire on the regulator can be cut and connected in series with a 1k Ω± 10%/0.5W potentiometer. Refer to Figure 2 for the wiring method. The remote potentiometer works in series with the internal potentiometer, and when the remote is placed in the middle position, the internal potentiometer can be used for coarse adjustment.

2. Stability adjustment

The stability potentiometer (STAB) affects the dynamic response of the generator to load changes:

Clockwise: Slow response speed and reduced overshoot (more stable) - suitable for situations with low response requirements.

Counter clockwise: response speed increases, overshoot increases (more sensitive) - suitable for situations where high voltage recovery speed is required.

Actual tuning suggestion: Switch the load slightly under rated load and observe the voltage waveform. If there is excessive damping (slow recovery), rotate counterclockwise appropriately; If there is insufficient damping (oscillation), rotate clockwise until critical stability is reached.


Complete process of operation and debugging

1. Check before startup

Confirm that the regulator specifications match the generator (voltage, frequency, excitation resistance)

Confirm that the wiring is correct (compare Figure 2)

Confirm that the fuse has been installed correctly

Turn the voltage regulator potentiometer counterclockwise to the lowest position; If there is a remote potentiometer, place it in the middle position

2. System startup

Start the prime mover to the rated speed

The generator should automatically build voltage (residual voltage ≥ 6Vac can start excitation)

Slowly adjust the voltage potentiometer clockwise until the output voltage reaches the rated value

If using a remote potentiometer, use it for fine adjustment

3. Failure handling of excitation

If the voltage building fails after the first operation or long-term shutdown (residual voltage below 6Vac), field flashing operation should be performed:

In the shutdown state of the prime mover, take a DC power supply (such as a battery) of ≤ 12Vdc, connect it in series with a 3-5 Ω current limiting resistor to the F+and F - terminals, hold for about 3 seconds, and then disconnect.

Restart the prime mover and measure the voltage between terminals 3-4. If>6Vac, the pressure building should be successful.

If it still fails, check the excitation circuit and residual magnetic polarity; If multiple attempts fail, consider replacing the regulator.

Safety warning: When starting excitation, it is necessary to use a current limiting resistor, otherwise it may damage the regulator output stage or excitation winding.

4. Operational testing (bench validation)

Before installation or during troubleshooting, the basic function of the regulator can be verified using the test circuit in Figure 5 of the manual:

Connect 120Vac power supply and indicator light (bulb)

The light bulb should flash briefly when starting

Slowly adjust the voltage potentiometer, the bulb should smoothly brighten and reach maximum brightness at a certain position (indicating that the adjustment point has been reached)

Fine tune the potentiometer near this adjustment point, and the light bulb should be able to switch on/off steadily

This test does not require a generator to be connected, and can quickly determine whether the regulator is intact.

Typical on-site troubleshooting

Priority investigation direction for fault phenomena

Measure whether the residual voltage at terminals 3-4 is ≥ 6Vac due to failed voltage building; Check the resistance of the excitation winding (15-100 Ω); Check if F+/F - are reversed

Is the voltage potentiometer not adjusted to a sufficient position due to low voltage after voltage building; Is the remote potentiometer in the low resistance position; Check if the input voltage is below 85Vac

Is the uncontrollable potentiometer stuck or open circuit due to high voltage after voltage building; Is the wiring of the remote potentiometer broken, causing a high resistance state; Possible malfunction of regulator output stage

Voltage oscillation (traveling car): The TAB potentiometer is too counterclockwise; Fluctuations in the prime mover speed regulator; Excitation winding resistance approaching upper limit

Is the excitation voltage normal for frequent actions of over excitation shutdown (normal should not exceed 95Vdc); Is there a short circuit fault causing a surge in excitation demand; Is the voltage detection circuit abnormal

Confirm if the HZ jumper has been correctly cut/retained according to the system frequency if the frequency compensation does not work; Measure whether the actual frequency is below the inflection point


Maintenance and spare parts management

1. Preventive maintenance

The regulator is a fully solid-state structure with no vulnerable mechanical components. The focus of maintenance is to regularly check the tightness and cleanliness of the wiring.

It is strictly prohibited to use Megger or voltage tester for insulation testing of regulators, otherwise semiconductor devices may be broken down.

2. Suggestions for spare parts

It is recommended to keep at least one VR63-4C/UL regulator on site as a cold backup to shorten downtime due to faults.

If using a remote voltage regulation solution, store a 1k Ω/0.5W potentiometer and matching knob.

Original factory optional remote voltage regulator potentiometer with locking function (Basler P/N 17727), suitable for situations where misoperation prevention is required.

3. Attention to Replacement and Upgrade

VR63-4C/UL is a classic and mature product. When the original model is discontinued or requires performance upgrades, Basler technical support can be consulted for alternative model recommendations. When replacing, it is necessary to focus on checking the suitable range of the excitation resistor (15-100 Ω) and the output power capacity (continuous 4A).

  • Bonfiglioli ACT401-19A Frequency Inverter
  • Bonfiglioli C102PP71 Gear Motor 13.4:1
  • Bonfiglioli C312 P P90 Speed Reducer
  • VEM K21R 71 G 4 Motor with Bonfiglioli VF44
  • Bonfiglioli C31 3 P P63 PV Bevel Gear Reducer V5
  • Bonfiglioli WR75UD28150P71B5B3 Gearbox
  • Bonfiglioli ACT401-13FA Frequency Inverter
  • Bonfiglioli VF62/P Worm Gearbox 38:1
  • Bonfiglioli ME210124001Y C Helical Gearbox
  • Bonfiglioli VF63PIP90BI4 Gearbox
  • Bonfiglioli ACT 401-19A Frequency Inverter
  • Bonfiglioli C102PP71 Variable Speed Gearmotor
  • Bonfiglioli C312 P P90 Reducer with Clutch
  • Bonfiglioli VF44 F1 10 Gearmotor with VEM Motor
  • Bonfiglioli C31 3 P P63 PV V5 Reducer
  • Bonfiglioli WR75UD28150P71B5B3 Gearbox
  • Bonfiglioli ACT401-13FA Frequency Inverter
  • Bonfiglioli VF 62/P Worm Gearmotor 38 to 1
  • Bonfiglioli ME210124001Y Inline Gearbox
  • Bonfiglioli VF63PIP90BI4 Worm Gearbox
  • Bonfiglioli VF86FC256 Worm Gearbox 1010B03004
  • Bonfiglioli VF44F1 Gearmotor 0.43kW 460V
  • Bonfiglioli W 75 UF1 D30 P80 B14 Gearbox i=100
  • Bonfiglioli VF63NP80B5 Worm Gearbox
  • Bonfiglioli 300R3133FPP80POG0A Gear Reducer
  • Bonfiglioli VF49F1N56C Gearbox
  • Bonfiglioli Trasmittal 300L19 Gearmotor with MEZ UD 1104 Motor
  • Bonfiglioli BCS30 Permanent Magnet Motor with Encoder
  • Bonfiglioli BN56B4 Gearmotor with VF30 Reducer
  • Bonfiglioli VF44 Gearbox 100480150
  • Bonfiglioli VF63PIP90B14 Gearbox
  • Bonfiglioli 830420150 BN63A4 230/400-50 IP55 CLF B14 with VF30F2 P63B14B3-I40
  • Bonfiglioli BN63A2 Motor
  • Bonfiglioli VF44 ALP63B5 Gearbox
  • Bonfiglioli A102 UR P80 Gearbox
  • Bonfiglioli MP 105 2 16 STD 95A1 CD 19 S1 OR SB KE Planetary Gearbox
  • Bonfiglioli T56BN/4 Motor
  • Bonfiglioli 8E20020594-M285018 Motor
  • Bonfiglioli VF49 V P71 B5 Gearbox
  • Bonfiglioli X VFR49 L1 FA1 180 P63B5 B3 Gearbox
  • Bonfiglioli W63U7P90B14V6 Right Angle Gear Reducer
  • Bonfiglioli VF/W30/63UFC2 Gear Reducer i=168
  • Bonfiglioli VF44 Gear Reducer 100480150
  • Bonfiglioli ACU 201-07 FA Frequency Converter
  • Bonfiglioli BN-80B-4 Motor with VF63 Gearbox 38:1
  • Bonfiglioli MVF 49 Gear Reducer for Servo Motor
  • Bonfiglioli ACT 400-034 A Frequency Inverter 11kW
  • Bonfiglioli SYN10-S-220-03-AF AC Drive 0.5HP
  • Bonfiglioli LC 090 1 7 STD FM CD 19 KE Gearbox
  • Bonfiglioli TQFK070350GR80A1CD Gear Unit
  • Bonfiglioli BN 80 B6 FD Three Phase Motor
  • Bonfiglioli W63U Worm Gear Reducer
  • Bonfiglioli 830G2310M-B048052 Gear Motor
  • Bonfiglioli VF49P128P71B5B3 Worm Gearbox
  • Bonfiglioli W75UD30719/140B3 Worm Gearbox
  • Bonfiglioli VF49F17HSB3 Worm Gearbox
  • Bonfiglioli C12 2P 20.6 P90 B3 Gearbox
  • Bonfiglioli BN80B4 623136 Geared Motor
  • Bonfiglioli 4APC3-4 9142882 Geared Motor 0.18 kW
  • Bonfiglioli W86 80/90-B5 Worm Gear Reducer 20:1
  • Bonfiglioli ACU 210-07 1 FA PLC Peripheral Module
  • Bonfiglioli MVF44/F Worm Gearbox
  • Bonfiglioli W63U Worm Gear Reducer
  • Bonfiglioli BN63A2 Electric Motor
  • Bonfiglioli BN 132 M B 4 Electric Motor 9.2kW
  • Bonfiglioli VF49 L1 P1 P63B5 Worm Reducer i=45
  • Bonfiglioli C413 P S2 7717/1000 Gearmotor 1.5kW
  • Bonfiglioli VF49F1P63B5B3 Worm Gearbox
  • Bonfiglioli BTD5-1870-05-400-ENC8A Servo Motor
  • Bonfiglioli ACU401-03FA Frequency Inverter
  • Bonfiglioli MVF63/N Gearbox with AEG Servomotor
  • Bonfiglioli BN80A4 Gearmotor VF49L1P1P80B14
  • Bonfiglioli VFR 72/FC2 Gear Reducer
  • Bonfiglioli W R 86 U 120 Gearbox Assembly
  • Bonfiglioli W 75 U 30 Gear Reducer
  • Bonfiglioli W R 86 U 120 P80 B5 V5 Gearbox
  • Bonfiglioli RAO 50/DC Gearbox
  • Bonfiglioli VF49 F1 P63B5 Gearmotor with SPZ MS6324
  • Bonfiglioli X_LC 090 Planetary Gearbox
  • Bonfiglioli A302 UH35 P90 Gearbox
  • Bonfiglioli VF63FCHS Worm Gearbox 103100390
  • Bonfiglioli VF 44 P63 B14 Gearbox M00480210008
  • Bonfiglioli MPD1006S0006 Precision Planetary Gearbox
  • Bonfiglioli VF49F1N56C Worm Gearbox
  • Bonfiglioli TR G 105 3 20 STD Planetary Reducer
  • Bonfiglioli VFR49P1P63B5 Worm Gearbox
  • Bonfiglioli WR 86 U 120 P80 B5 V5 Gearbox 2G30013944
  • Bonfiglioli BRA 400-060 BF2 Brake Chopper
  • Bonfiglioli VF49P P71B5 Worm Gearbox
  • Bonfiglioli C402 P VG1 Gear Speed Reducer 31.4:1
  • Bonfiglioli ISMET LCVT050 DK308/50 Line Reactor
  • Bonfiglioli C 22 2 F GR063 Gearbox
  • Bonfiglioli C31 3 P P63 PV V5 Reducer
  • Bonfiglioli CM-485 T Communication Module
  • Bonfiglioli W75UF1D30P90B5 Gearbox
  • Bonfiglioli BN63 B4 VF49 Gearmotor 0.18kW
  • Bonfiglioli ACT 400-004 FA Frequency Inverter
  • Bonfiglioli W110U100P90B5B3 Worm Gearbox
  • Bonfiglioli SYN10 T 400 05 AF Inverter
  • Bonfiglioli MP080.1.4.15.16.40.80.100 Gearbox
  • Bonfiglioli SYN10S Inverter
  • Bonfiglioli VF44L2P160 Gearmotor
  • Bonfiglioli W 86 U 40 P90 B5 B3 Gear Reducer
  • Bonfiglioli BTD5-1870-05-400 Servomotor
  • Bonfiglioli MP 080 2 2C Gearbox with BLDC Motor
  • Bonfiglioli MP080.1.10 Planetary Gearbox
  • Bonfiglioli C212PHS Reducer
  • Bonfiglioli MVF 49F1 Gearbox with ICME T71B4
  • Bonfiglioli VF 49 v P71 B5 Gearbox
  • Bonfiglioli VF 44 P1 Gearmotor
  • Bonfiglioli C 22 2 NP 6.1 Helical Gearbox
  • Bonfiglioli F203 316.9 Gearbox with Kaiser Motor
  • Bonfiglioli SYN10 S 220 07 AF Frequency Inverter
  • Bonfiglioli 301L251.8-HC-P90 Gearbox 1/51.8
  • Bonfiglioli ACT401-25A Frequency Inverter
  • Bonfiglioli W75 U D30 30 P90B14 B3 Worm Drive
  • Bonfiglioli 830G2310M-307638 Motor
  • Bonfiglioli C112-P-P90 Inline Gearbox i=6.2
  • Bonfiglioli SYN10-S-220-03-AF AC Drive
  • Bonfiglioli VFR49 A HS Worm Drive i=180 B3
  • Bonfiglioli ACT 401-29 A AC VFD Drive 22kW
  • Bonfiglioli VF49PIP63B14 Gearbox
  • Bonfiglioli ANG 410-18 2 FA Inverter
  • Bonfiglioli GVX2000-7.5-T Converter
  • Bonfiglioli EM-ENC-02-24 Optical Module
  • Bonfiglioli ACT 401-33 A VFD Drive
  • Bonfiglioli MVF 49F1 Gearbox with ICME T71B4
  • Bonfiglioli BN112M4 Motor