Beckwith M-3311A Transformer Protection Relay Configuration and Optimization Guide

F: | Au:FANS | DA:2026-07-07 | 16 Br: | 🔊 点击朗读正文 ❚❚ | Share:

Turning point: 1.0~4.0PU;

Second harmonic braking (2nd, 4th): 5%~50%, used to suppress excitation inrush current;

Fifth harmonic braking: 5%~50%, used for overexcitation suppression.

The high setting differential component 87H has a starting value of 5.0~20.0PU and an action time of less than 1.5 cycles (with a minimum delay of 1 cycle). CT ratio compensation can be achieved by setting the CT tap of each winding (1.00~100.00).

6. Grounding differential protection (87GD)

Suitable for ground fault detection of various windings, configurable as directional or non directional. The starting value is 0.2~10.00A, and the delay is 1~8160 cycles (recommended not less than 2 cycles). The zero sequence current source can be selected as the sum value or a single winding. The directional component automatically exits when the zero sequence current is extremely small.

7. IPSpeegic Programmable Logic

Provide Boolean logic combinations (AND, OR, NOT) based on component actions, control input states, output contact feedback, and other conditions, combined with timers (delay 0-65500 cycles), to construct complex interlocking and automatic switching schemes.

Optional voltage protection package

For applications that require voltage, M-3311A provides an optional voltage protection package that includes the following functions:

Overexcitation protection (24 V/Hz): using fixed time limit (starting value 100%~200%, delay 30~8160 cycles) and inverse time limit (starting value 100%~150%, multiple inverse time limit curves) components to prevent damage to transformers and generators due to overcurrent. Based on the rated secondary voltage and system frequency calculation, the accuracy is suitable for the range of 10~80Hz and 0~180V.

Undervoltage (27): Used for load shedding, with a starting value of 5-140V and a delay of 1-8160 cycles, and can be set to suppress voltage values. Provide 3 components in three winding applications and 2 components in four winding applications.

Phase overvoltage (59): 1-3 components, starting value 5-180V, can choose phase voltage, positive sequence or negative sequence components.

Grounding Overvoltage (59G): Used to detect system grounding faults, with a starting value of 5-180V. The zero sequence voltage can be taken from the VG input (open delta) or calculated as 3V0 (requiring four voltage inputs and VT configuration as LG).

Frequency protection (81O/U): 4 components each for overclocking and low-frequency, with a setting range of 45-65Hz, a delay of 2-65500 cycles, and an accuracy of ± 0.1Hz (60Hz models are within the range of 57-63Hz).


Standard hardware features and communication functions

1. Input and output

Standard I/O: 8 programmable output contacts (6 type A, 2 type C) and 6 control/status inputs (internal wet connection 24V, minimum excitation current ≥ 25mA). There is also a power failure alarm output (type B) and a self-test alarm output (type C).

Expansion I/O (optional): Add 8 A-type outputs and 12 inputs, and provide closing circuit monitoring (CCM), suitable for situations that require more switch signals.

2. Communication interface

Three serial ports: two RS-232 (one front and one back) and one RS-485.

Optional RJ-45 Ethernet port (10/100 Base-T), supporting MODBUS TCP/IP, DNP 3.0 over TCP/IP, or IEC 61850 protocol (up to 4 concurrent sessions).

Support IRIG-B time synchronization (modulation or demodulation) for precise timing of events.

Supports MODBUS and DNP 3.0 serial protocols, compatible with S-3300 IPScom ® Communication software that can perform fixed value reading and writing, real-time monitoring, waveform downloading, and other operations.

3. Recording and monitoring functions

Oscillatory waveform recording: The sampling rate is 16 times the system frequency, and the maximum storage capacity is 183-311 cycles (depending on the number of windings and partitions). The triggering method can be selected as state input, trip output, or communication command. The recorded data can be analyzed using IPSplot Plus software or exported in COMTRADE format.

Sequence of Events (SOE): Stores the last 512 events with time stamps.

Through Fault: Independently record through faults, store the duration of each fault, maximum fault current of each phase, I ² t value, and cumulative number of times (up to 256).

Target storage: Store the information of the last 8 trips, including the operating components, current values, and time scales.

Circuit breaker monitoring: Estimate the wear of each phase contact by integrating I ² t or It, and the cumulative value can set an alarm threshold (0-50000 kA · cycle), which needs to be triggered by the starting contact for timing.

Configuration options and typical application wiring

M-3311A supports multiple hardware configuration combinations to meet different main wiring methods:

Number of windings, grounding current, input voltage

2 1 0 / 2 / 4

3 2 0 / 2 / 4

4 3 0/2 (only two voltages)

For the four winding model, the two voltage inputs are phase voltage (for 59, 81, 27, 24) and open delta voltage (for 59G), and are independent of the winding.

Typical application wiring diagrams include:

Double winding transformer (Figure 3): Clearly displays the signal flow of CT connection, differential, overcurrent, and grounding protection for each winding.

  • Basler KR7FFX Static Regulator 840V
  • Basler EL200-7 Voltage Regulator 90-660VAC 7A
  • Basler PRP210-1 Reverse Power Relay 9056300102
  • Basler SSR 63-12 Static Regulator 600VAC
  • Basler 9289901106 Digital Board
  • Basler DECS100 Voltage Regulator DECS100A01
  • Basler Electric CEM-2020 Contact Expansion Module
  • Basler Electric BE3-25-1 C1 N4 Synchronizing Check Relay
  • Basler Electric ACA2000-50GM GigE Camera 2MP 50fps
  • Basler Electric ACA2240-20GMSYM GigE Camera Sony IMX264
  • Basler BE1-50G Ground Overcurrent Relay
  • Basler PRS250 Veri-Sync Relay
  • Basler MOC2199 Output Module
  • Basler UFOV 260A Underfrequency Overvoltage Module
  • Basler BE-15482-001 Control Module
  • Basler LSP4-7 Protective Relay
  • Basler SCP 250-G-60 VAR Power Factor Controller
  • Basler BE146N Negative Sequence Overcurrent Relay
  • Basler APR63-5 Automatic Voltage Regulator
  • Basler 9507900107 SR8A Retrofit Voltage Regulator
  • Basler BE1-320 Directional Power Relay
  • Basler KR7F Voltage Regulator 9116200100
  • Basler UFOV 260A Overvoltage Protective Module
  • Basler AEC63-7 Analog Excitation Controller
  • Basler 9992D90G01 Control Module
  • Basler 6966D22G01 Control Board
  • Basler 6965D40G01 Control Board
  • Basler BE1-50/51M-104 Overcurrent Relay
  • Basler BE1-BPR Programmable Breaker Relay
  • BASLER Electric SSR 125-9 1256 00 102 Static Voltage Regulator
  • Basler Electric MVC 112 Manual Voltage Control
  • Basler Electric 9321000102 Control Module
  • Basler Electric RA-70-MDCT7 Rectifier Assembly
  • Basler Electric ACA1300-60GM GigE Camera
  • Basler Electric 6427C85G01 Interface Board
  • Basler Electric 6965D05G01 Control Board
  • Basler Electric ACA2500-14UC Current Transducer
  • Basler Electric 9170206111 Protective Relay
  • Basler Electric BE1-11-G6D1M1J1P0E000 Protection Relay
  • Basler Electric BE1-50/51B-107 Overcurrent Relay
  • Basler 9121000106 Voltage Controller
  • Basler B3E-E1P-A0N0F Solid State Protective Relay
  • Basler 9121000106 Manual Voltage Control
  • Basler PRP320 Motor Pull-out Relay
  • Basler SSE-N 250-9KW Shunt Exciter Regulator
  • Basler BE1-50-51B-107 Overcurrent Relay
  • BASLER ELECTRIC MVC 108 MANUAL VOLTAGE CONTROL MODULE 9 0370 00 102
  • Basler BE1-59N-A7E-D1J-D0N0F Ground Overvoltage Relay
  • Basler BE1-46N-G1E-B8P-B0N0F Negative Sequence Overcurrent Relay
  • Basler BE1-951 Overcurrent Protection System
  • Basler Electric MOC2199 Motor Operated Potentiometer
  • Basler Electric BE1-60 Voltage Balance Solid State Relay B1FA1C1M1F
  • Basler Electric BE1-67N Directional Overcurrent Relay
  • Basler Electric PIA2400-17GM Interface Module
  • Basler Electric V6RAB Rectifier Module
  • Basler Electric BE1-32R Reverse Power Relay B2E E1R A0N1F
  • Basler Electric IFM-150 Firing Circuit Chassis 120V AC
  • Basler Electric IFM-102 Firing Circuit Chassis 120V AC
  • Basler Electric 9170206111 NSNP Control Module
  • Basler Electric SSR 63-12 Static Voltage Regulator
  • Basler UFOV 260A Overvoltage Protective Module
  • Basler SCA1300-32GM CCD Camera Lens Enclosure
  • Basler BA1-27 Under Voltage Relay
  • Basler 149D866G06 Control Board
  • Basler 9072300130 Power Supply Module
  • Basler CBS 305 Current Boost System
  • Basler BE1-60 Voltage Balance Relay
  • Basler Electric CBS 212 Current Boost System Sensing 120/240VAC 50/60Hz 10VA
  • Basler MVC-300 Manual Voltage Control Unit
  • Basler SSR125-12 Static Voltage Regulator 918500102
  • Basler SR32A2B05B3E Static Voltage Regulator
  • Basler Electric BE1-59N Ground Fault Overvoltage Relay
  • Basler Electric 9110000113 Excitation Module
  • Basler Electric 90-72300-114 Control Accessory
  • Basler Electric PRS-250 Protection Relay System
  • Basler Electric BE1-50/51M-109 Overcurrent Relay
  • Basler Electric SR4A1B10B3E Static Voltage Regulator
  • Basler Electric CBS 212 Current Boost System
  • Basler Electric SR32A2B05B3E Static Voltage Regulator
  • Basler Electric MOC2207 Motor Operated Potentiometer
  • Basler Electric SR4A1B05A3E Static Voltage Regulator
  • Basler Electric BE1-32R Power Relay B2EE1PA0N1F
  • Basler BEI-81 Underfrequency Relay
  • Basler CBS 212A Current Boost System
  • Basler SSR 63-12 Static Voltage Regulator
  • Basler DGC-2020 Digital Genset Controller
  • Basler BE1-32 Reverse Power Relay
  • Basler BE1-50/51B-207 Overcurrent Relay
  • Basler BE1-951 Overcurrent Protection System
  • Basler 9073800-103 Power Supply
  • Basler SCA1300-32FC CCD Camera
  • Basler 9073800-103 Power Supply
  • Basler SCA1300-32FC CCD Camera
  • Basler L304KC Protective Relay
  • Basler BE3-25-1S1N4 Time Overcurrent Relay
  • Basler 9032300113 Excitation Support System
  • Basler BE1-59N Ground Overvoltage Relay
  • Basler MVC-300 Manual Voltage Control Unit
  • Basler MOC2102 Potentiometer
  • Basler BE1-87G Generator Differential Relay
  • Basler Electric DECS-200 Digital Excitation Control System
  • Basler Electric DECS 125-15-B2C5 Digital Excitation System
  • Basler Electric PLA2400-12GM Power Supply
  • Basler Electric BE1-50/51B-235 Overcurrent Relay
  • Basler Electric BE1-27/59 Undervoltage Overvoltage Relay
  • Basler Electric CEM-2020 Contact Expansion Module
  • Basler Electric BE1-32R Solid State Power Relay
  • Basler Electric BE1-700 Digital Generator Management Relay
  • Basler Electric BE1-59N Ground Fault Overvoltage Relay
  • Basler Electric BE10493002 Protection Module
  • Basler Electric BEI-79A1AA5CA3M1F Digital Annunciator
  • Basler Electric SSR 32-12 Static Voltage Regulator
  • Basler Electric BE1-CDS240 Current Differential System
  • Basler Electric BE1-67 Directional Overcurrent Relay
  • Basler Electric 9121000106 DECS-100 Voltage Controller
  • Basler Electric BEI-871 Interface Module
  • Basler Electric 8650C72 Exciter Control Module
  • Basler Electric RDP-110-S1 Generator Annunciator
  • Basler Electric BE1-32O/U Directional Power Relay
  • Basler Electric BE2000E AVR Voltage Regulator
  • BASLER ELECTRIC BE1-50F2EA1PA0N0F Instantaneous Overcurrent Relay
  • BASLER ELECTRIC BE1-81T1EE1WA0N1F Underfrequency Relay
  • Basler BE1-67 Directional Overcurrent Relay
  • Basler BE1-25/79TR Reclosing Relay
  • Basler CEM-2020 Contact Expansion Module
  • Basler BE1-11 Overcurrent Protection Relay
  • Basler BE1-GPS Generator Protective Relay
  • BASLER ELECTRIC MVC-300 MANUAL VOLTAGE CONTROL UNIT 9121000106