Three winding transformer (Figure 4): with high impedance grounding, grounding differential and zero sequence overcurrent can be configured separately.
Four winding transformer (Figure 5, Figure 6): emphasizes the current summation function, which can combine multiple winding currents for overcurrent protection (such as Sum1, Sum2), and 49 thermal protection can be applied to a single winding or summation value.
Dual generator booster station overall differential (Figure 7, Figure 8): Expand the differential protection zone to the entire generator and transformer.
Dual circuit breaker wiring for autotransformer (Figure 11): Each circuit breaker is equipped with independent failure protection and circuit monitoring.
Key points for tuning and operation maintenance
1. Setpoint Groups
The relay is equipped with four independent constant value groups, which can be switched through HMI, communication or external input to adapt to different system operation modes (such as summer/winter, parallel/disconnection). Switching will not affect the continuity of protection functions.
2. Measurement accuracy
Voltage: ± 0.5V or ± 0.5% (whichever is higher);
Current (5A rated): ± 0.1A or ± 3%;
Current (1A rated): ± 0.02A or ± 3%;
Frequency: ± 0.1Hz;
V/Hz: ± 1%.
Real time measurement includes three-phase voltage, current, frequency, sequence components, as well as 15/30/60 minute demand current and maximum value recording.
3. Loop monitoring
Trip Circuit Monitoring (TCM): The integrity of the trip coil is monitored through auxiliary inputs on standard I/O, suitable for 24~250Vdc; Extended I/O provides two independent TCM circuits and two closed circuit monitoring (CCM) circuits, which can monitor the corresponding circuits separately in the open/closed state of the circuit breaker.
The monitoring content includes the presence of DC power supply and circuit continuity. Once abnormal, an alarm output can be triggered.
4. Power supply and anti-interference
Supports wide range AC (85~265Vac) or DC (80~288Vdc), with a power consumption of 20VA; low-voltage DC (18~56Vdc) is optional. All inputs and outputs have passed multiple electromagnetic compatibility tests, including electrostatic discharge (8kV contact/15kV air), fast transient (4kV), surge (4kV), and oscillation wave (2.5kV), in compliance with IEC 60255 and IEEE C37.90 standards. The working temperature range is -20 ℃~+70 ℃, with a humidity of 95% and no condensation.
Engineering application precautions
CT connection and ratio matching: Differential protection requires CT ratio and wiring method (star/angle) of each winding to be compensated through CT tap settings to ensure minimum steady-state differential current. In practical engineering, phase correction should be reasonably set according to the transformer connection group (Y - Δ).
Surge suppression setting: The second harmonic braking ratio is generally set at 15%~20%, which needs to be adjusted according to the transformer capacity and system short-circuit capacity. For large transformers, the fifth harmonic braking can be activated simultaneously to enhance reliability under overexcitation.
Ground differential sensitivity: When the zero sequence current is very small, the directional element automatically exits, and 87GD becomes non directional. Attention should be paid to the coordination with adjacent line zero sequence protection.
Circuit breaker monitoring trigger condition: It is necessary to connect the circuit breaker auxiliary contact (56a) as the starting signal, and the integration time delay should avoid the circuit breaker opening time.
Oscillatory waveform storage: Note that if the relay loses power, waveform data and SOE events will be lost. Therefore, it is recommended to configure UPS and regularly upload data through communication.
