HIMA CPU 01 Controller Module

F: | Au:FAN | DA:2025-11-12 | 779 Br: | 🔊 点击朗读正文 ❚❚ ▶ | Share:


HIMA CPU 01 Controller Module

Product Core Positioning and Certification

1. Core functions

CPU 01 is the central processing unit of the HIMatrix F60 modular controller, responsible for three core responsibilities:

Storage and Execution: Stores the operating system (OS) and user programs, performs core functions such as logical operations, I/O signal processing, and security self checks.

Communication management: Implement secure/non secure communication with programming and debugging tools (PADT), remote I/O, and external systems through Ethernet and fieldbus interfaces.

Status monitoring: Real time monitoring of power supply voltage, operating temperature, hardware faults, and automatic triggering of safety response in case of abnormalities (such as entering STOP state).

2. Safety and compliance certification

The module is certified by multiple international standards to ensure safety and integrity:

Certification Body/Standard Certification Level/Scope Applicable Scenarios

T Ü V (IEC 61508/61511/62061) SIL 3 industrial safety controls (such as process industry, mechanical safety)

T Ü V (EN ISO 13849-1) Cat. 4, PL e Mechanical Safety Systems

T Ü V CENELEC (EN 50126/50128/50129) SIL 4 for railway and high safety industrial scenarios

CE EMC, ATEX Zone 2 EU market compliance, use of explosion hazard zone Zone 2

FM Approval Class I, DIV 2 Explosion proof Scenarios for the North American Market

PNO PROFIBUS DP Slave fieldbus compatibility certification

3. Product variants and compatibility

The module is divided into two variants, adapted to different programming tools and cannot be used interchangeably:

CPU 01: Compatible with ELOP II Factory programming tool, requiring CPU OS ≤ V6. x and COM OS ≤ V11. x.

CPU 01 SILworX: Compatible with SILworX programming tool, requiring CPU OS ≥ V7 and COM OS ≥ V12. x.

Key limitation: Projects created by ELOP II Factory cannot be edited using SILworX, and vice versa.

image.png

Key technical parameters

1. Hardware configuration

Category detailed parameters

Processor system dual processor architecture (uP1/uP2) with synchronization (SYNC) and watchdog functionality

Communication interface Ethernet: 4 RJ-45 ports (10BASE-T/100BASE-Tx, supporting automatic negotiation and automatic crossover);

Fieldbus: 2 9-pin D-sub interfaces (FB1/FB2, RS485, optional submodule activation required)

Storage configuration CPU OS ≤ V6. x: maximum 500kB user program, 500kB user data;

CPU OS ≥ V7: maximum 2047 KB user program, 2047 KB user data;

Date/Time Cache: Powered by Gold Capacitor

Indicator light system LED (RUN/ERR), program LED (STOP/PROG/FAULT/ORCE/OSL/BL), communication LED (Ethernet/fieldbus)

Mechanical characteristic dimensions: 6 RU (rack unit), 4 HP; weight: 280g; protection level: IP20

2. Power and environmental requirements

Power supply parameters: rated voltage 24VDC, allowable fluctuation range -15%~+20% (18~28.8VDC), ripple peak ≤ 15%; Working current: 3.3VDC/1.5A, 5VDC/0.1A.

Environmental restrictions: working temperature of 0-60 ℃, storage temperature of -40~85 ℃, pollution level II (IEC/EN 61131-2), altitude ≤ 2000m, no condensation.

Voltage monitoring: Built in voltage monitoring function, triggering an alarm (written to system variables) when<18VDC, and automatically shutting down when<13VDC.

3. Communication Protocol and Ports

(1) Support agreement

Safety related: Safe Ethernet.

Standard protocols: Modbus TCP, OPC, SNTP (time synchronization) TCP S/R; Ethernet/IP only supports CPU OS ≤ V6. x.

(2) Default network port

Port Type Port Number Purpose

UDP 8000 Programming Tool (PADT) Connection

UDP 8001 ELOP II Factory Remote I/O Configuration

UDP 8004 SILworX Remote I/O Configuration

UDP 6010 Secure Ethernet OPC

UDP 123 SNTP time synchronization

UDP/TCP 502 Modbus (user modifiable)

TCP 44818 EtherNet/IP Explicit Messaging Service

TCP 2222 EtherNet/IP data exchange


Safety operation standards

1. Electrostatic protection (ESD)

Operators must master ESD protection knowledge, wear anti-static wristbands during work, and ensure that the work area is free of static electricity interference.

When the module is idle or transported, it should be stored in the original factory anti-static packaging and direct contact with the circuit board is prohibited.

2. Installation and operation safety

Installation restrictions: Zone 2 scenarios must be placed in an enclosure with a protection level of IP54 or higher, and the enclosure must be labeled with "Only power-off operation allowed (except when explosion risk is excluded)".

Cable requirements: Signal lines and power lines should be wired separately to avoid interference; Zone 2 installation must comply with DIN EN 60079-15/14 standards (terminals, wiring, creepage distance, etc.).

Prohibited behavior: live plugging and unplugging modules or cables; Operate the reset button during module operation; Replace core components with non original parts.

3. Emergency and residual risks

Emergency response: When the module fails, it automatically enters a safe state (input processing stops, output power is cut off), and any operation that prevents the safe operation of the system is prohibited.

Residual risks: may arise from engineering design defects, user program errors, wiring faults, and need to be avoided through compliant design and regular testing.


Installation and configuration process

1. Installation steps

(1) Basic installation (inside the rack)

In the power-off state, insert the module along the upper and lower rails of the rack, align it with the backplane slot, and press the front end board until the buckle "clicks" to lock.

Secure the module with screws on both sides of the front panel to ensure a secure installation.

Connection cables: Ethernet cable (RJ-45), fieldbus cable (D-sub, requiring sub module connection), power cord (powered by power module, no direct wiring required).

(2) Zone 2 Special Installation

Additional requirements: The enclosure protection level should be ≥ IP54 to ensure heat dissipation (the basic power consumption of the module is 6.5W, and it can reach 12W when equipped with a communication submodule).

Power requirements: PELV/SILV grade safety isolation power supply must be used, in compliance with IEC 61131-2 standard.

Label pasting: The shell needs to be pasted with ATEX compliant labels, and the module comes with an "Ex113GExnA II T4X" label.

2. Configuration process

(1) Tool selection and preliminary preparation

Confirm module OS version: Select the corresponding programming tool (ELOP II Factory/SILworX) based on the model label or front-end LED.

Reference documents: HIMatrix system manual (HI 800 191 E), safety manual (HI 800 023 E), and programming tool help documentation are required.

(2) Core configuration steps

Hardware Mapping: Create a project in the programming tool and configure the CPU module (Slot 2) and I/O module (Slot 3~8) according to the rack slot. There is a slight difference in slot numbers between SILworX and ELOP II Factory (refer to the table below). |Rack slot | SILworX slot number | ELOP II Factory slot number | Module type | | --- | --- | --- | --- | | | | | | 1 | - | PS 01 power module (no configuration required) | | 2 | 0 (CPU)/1 (COM) | - | CPU/communication module (integrated) | | | 3 | 2 | 1 | I/O module | | 4 | 3 | 2 | I/O module | | | 5~8 | 4~7 | 3~6 | I/O module|

Network configuration: Set the IP address (default 192.168.0.99) and subnet mask to ensure consistency with the PADT (programming computer) network segment; If modifications are required, they can be restored to default values through programming tools or reset functions.

Programming and downloading: Write user programs using IEC 61131-3 standard languages such as Function Block Diagram (FBD), compile them, and download them to the module Flash EPROM.

Security configuration: Set the watchdog time (WDT) and security cycle time according to the security manual, and configure security communication parameters (if applicable).

3. Reset operation (restore default settings)

Applicable scenario: Forgetting administrator account password or IP address conflicts with PADT.

Operation steps:

Disconnect the module power supply and unplug all fieldbus connectors (to avoid interfering with other devices).

Insert a needle shaped insulating material into the reset hole of the front end board, press and hold for ≥ 20 seconds, and at the same time, turn on the power to restart the module.

Reset effect: The IP address is restored to 192.168.0.99, the system ID (SRS) is restored to 6000.0.0, and only the default administrator account (empty password) is activated.

Note: In COM OS versions ≥ 10.42, after resetting, it is necessary to reconfigure the connection parameters and account before downloading the program/OS.

image.png

Operation and Diagnosis

1. Running status indication (LED interpretation)

The LED status of the module varies slightly with the CPU OS version, and its core meaning is as follows:

(1) System LED

Meaning of LED color status (CPU OS ≥ V8)

RUN green constantly on and running normally (STOP/RUN status)

RUN green Blinking1 (600ms on/off) is loading a new operating system

RUN green off, non RUN state

ERR red constant light lacks additional function authorization and testing mode

ERR red Blinking1 fault shutdown (hardware/voltage/configuration failure), requiring PADT restart

ERR red goes out without any malfunction

(2) Program LED

STOP (red): Always on=STOP/valid configuration; Blinking=STOP/Invalid configuration.

PROG (yellow): Always on=loading configuration/OS, modifying WDT/safe time/SRS.

Fault (yellow): Blinking=OS damage, invalid configuration, I/O failure.

FORCE (yellow): constantly on=forced function preparation; Flashing=forced function activation.

(3) Communication LED

Ethernet (next to RJ-45): Green=Full Duplex; Yellow=connection is valid; Flashing=data transmission/conflict.

Fieldbus (FB1/FB2): yellow=interface activated; Synchronized flashing=emergency loader activated.

2. Basic operating procedures

(1) Start the process

Confirm that the module is securely installed, the cable connections are correct, and there is no risk of static electricity.

Connect the power module to supply power, and the module will automatically perform LED self-test (all LEDs will briefly light up).

Start the programming tool and establish a communication connection with the module (via IP address).

Download user programs and configuration files to verify the validity of the configuration.

Switch the module to RUN state and confirm normal operation through LED and programming tools.

(2) Shutdown process

Normal shutdown: Use programming tools to switch the module to STOP state, and disconnect the power after the program stops.

Emergency stop: When the module fails, it automatically enters the ERROR STOP state, and after troubleshooting, it restarts through PADT.

3. Diagnostic methods

First level diagnosis: Determine the fault type based on the status of the front-end LED (such as ERR flashing=system fault, FAULT flashing=I/O fault).

Secondary diagnosis: By using programming tools to read diagnostic logs and system variables (such as power status and temperature status), locate specific fault points.

Common diagnostic items: communication failure (port/protocol configuration), invalid configuration (slot mapping error), hardware failure (voltage/module damage).


Maintenance and troubleshooting

1. Daily maintenance

Regular maintenance: Conduct a Proof Test every 10 years, refer to the HIMatrix Safety Manual (HI 800 023 E).

System update: Use downtime to upgrade the operating system through programming tools (first place the module in STOP state), and confirm the compatibility of the new version before upgrading.

Cleaning requirements: Wipe the outer shell with a dry soft cloth, and do not clean with water or chemical solvents; Regularly check that the cooling vents are unobstructed.

2. Fault handling

(1) Common faults and solutions

Possible causes and solutions for the fault phenomenon

The module cannot be started, ERR is constantly on and the voltage is too low. Check the power supply voltage (≥ 18VDC) for hardware faults and replace the module

Communication failure, Ethernet LED off, IP address conflict, cable damage investigation, IP conflict (communication LED synchronously flashing=conflict), replace network cable

Program cannot be downloaded, invalid PROG flashing configuration, incompatible OS version, verification slot mapping and configuration parameters, upgrading/downgrading OS

I/O unresponsive, FAULT flashing. I/O module fault, wiring error. Check the I/O module connection, rewire and test

There is no communication on the fieldbus, and the FB LED is off. The fieldbus submodule has not been installed, and a compatible fieldbus submodule has been installed

(2) Module replacement process

Disconnect the power supply module and unplug all connecting cables (Ethernet, fieldbus).

Loosen the module fixing screws and remove the module from the rack rail through the bottom handle.

Fix the new module according to the installation steps, connect the cables, and ensure that the wiring is consistent with the original module.

Connect the power, download the original configuration and program, and verify that it runs normally.

Attention: Only modules of the same model or HIMA authorized substitute models can be replaced, and mixing different variants (CPU 01/CPU 01 SILworX) is prohibited.


Transportation, discontinuation, and disposal

1. Transportation and Storage

Transportation requirements: Use original packaging (including anti-static protection) to avoid severe vibration and impact; Moisture and static prevention are required during transportation.

Storage requirements: Store in a dry, ventilated, non corrosive environment at a temperature of -40~85 ℃, avoiding heavy pressure and direct sunlight.

2. Deactivation process

Disconnect the power supply to the power module and ensure that the module is completely shut down.

Unplug all I/O terminal connectors, Ethernet cables, and fieldbus cables.

Dismantle the module and store it in anti-static packaging, record the date and status of discontinuation.

3. Disposal requirements

Industrial users are responsible for the compliant disposal of scrapped modules and are required to separate electronic components and metal casings according to environmental standards.

You can contact HIMA to sign a disposal agreement, and the original factory will provide professional disposal services. Random disposal is prohibited.

image.png

  • National Instruments cDAQ-9189 Chassis
  • National Instruments PXIe-8394 MXI Module
  • National Instruments PXIe-4112 Power Supply
  • National Instruments 778472-01 Module
  • National Instruments cFP-DO-401 Module
  • National Instruments PXIe-8379 Interface Card
  • National Instruments PXIe-7965R Module
  • National Instruments NI-9485 Relay Module
  • National Instruments 181045-01 Module
  • National Instruments TB-4302 Terminal Block
  • National Instruments PXI-2533 Matrix Switch Module
  • National Instruments PCI-6220 Analog Input Card
  • National Instruments PXI-2529 Matrix Switch Module
  • National Instruments 783732-01 Ordering Part Number
  • National Instruments PXI-6542 Digital Waveform Module
  • National Instruments PCI-1411 Image Acquisition Card
  • National Instruments PXI-6511 Industrial Digital I/O Module
  • National Instruments TPC-2012 Touch Panel Computer
  • National Instruments PXI-8101 Embedded Controller
  • National Instruments cRIO-9035 CompactRIO Controller
  • National Instruments PXIe-5114 Digitizer Card
  • National Instruments SCXI-1315 Block
  • National Instruments PXI-7842R Card
  • National Instruments PCI-6031E DAQ Device
  • National Instruments NI-9792 Gateway
  • National Instruments PXI-4132 SMU
  • National Instruments USB-5132 Digitizer
  • National Instruments NI 9244 Input Module
  • National Instruments SCXI-1163R Module
  • National Instruments PCI-6221 DAQ Device
  • National Instruments cFP-2120 Compact FieldPoint Controller
  • National Instruments cRIO-9073 CompactRIO Controller
  • National Instruments PCI-8516 CAN Interface Card
  • National Instruments PXIe-1073 5-Slot Chassis
  • National Instruments NI 9421 DSUB Digital Input Module
  • National Instruments PXI-4204 High Voltage Input Module
  • National Instruments PCI-6111 Multifunction DAQ Card
  • National Instruments cRIO-9035 CompactRIO Controller
  • National Instruments NI 9759 Powertrain Control Module
  • National Instruments 187254A-01 Ordering Part Number
  • National Instruments PXI-6624 Module
  • National Instruments cDAQ-9137 Chassis
  • National Instruments PXIe-8133 Controller
  • National Instruments 779139-01 Module
  • National Instruments FP-DI-301 Module
  • National Instruments 194021D-01L Module
  • National Instruments PXI-1000B Chassis
  • National Instruments PXIe-8510 Module
  • National Instruments PXI-6221 DAQ Card
  • National Instruments cDAQ-9188 Chassis
  • National Instruments PXI-5421 Arbitrary Waveform Generator
  • National Instruments cRIO-9023 CompactRIO Controller
  • National Instruments PCI-6221 Multifunction DAQ Card
  • National Instruments PXI-4065 Digital Multimeter Card
  • National Instruments NI 9477 Digital Output Module
  • National Instruments cDAQ-9185 TSN Ethernet Chassis
  • National Instruments NI 9147 4-Slot cRIO Chassis
  • National Instruments USB-6259 Mass Termination DAQ Device
  • National Instruments 184120F-01 Ordering Part Number
  • National Instruments PCI-4472B Sound and Vibration Module
  • National Instruments SCXI-1130 Switch
  • National Instruments VB-8012 VirtualBench
  • National Instruments PXI-7350 Controller
  • National Instruments eDAQ-9174 Chassis
  • National Instruments PXI-4461 DSA Module
  • National Instruments PCI-6280 DAQ Card
  • National Instruments PXI-6251 DAQ Card
  • National Instruments PXI-6653 Module
  • National Instruments PCI-6509 DIO Device
  • National Instruments NI 9751 Driver Module
  • National Instruments PXIe-6361 Multifunction I/O Module
  • National Instruments cRIO-9014 CompactRIO Controller
  • National Instruments PCI-7390 Motion Control Card
  • National Instruments PXI-8512 CAN Interface Module
  • National Instruments sbRIO-9636 Single-Board Controller
  • National Instruments IC-3120 Industrial Controller
  • National Instruments PCI-6220 M Series DAQ Card
  • National Instruments PXI-8176 Embedded Controller
  • National Instruments PXI-6132 S Series DAQ Module
  • National Instruments NI 9206 Analog Input Module
  • National Instruments PXI-2584 Switch Module
  • National Instruments 196541B-01L Module
  • National Instruments 778075-01 Module
  • National Instruments FP-RLY-420 Module
  • National Instruments USRP-2920 Radio
  • National Instruments PCIe-6351 DAQ Card
  • National Instruments cRIO-9040 Controller
  • National Instruments NI 9201 Input Module
  • National Instruments NI 9411 Input Module
  • National Instruments NI 9216 Input Module
  • National Instruments PCI-6221 DAQ Device
  • National Instruments PXI-4498 DSA Module
  • National Instruments PXI-6259 DAQ Card
  • National Instruments PXI-7354 Motion Controller
  • National Instruments FP-AI-110 Input Module
  • National Instruments 192172F-04L Module
  • National Instruments PXIe-8115 Controller
  • National Instruments 142931B-01L Module
  • National Instruments PXI-2503 Switch Module
  • National Instruments 776246-01 Module
  • National Instruments CFP-2110 Compact FieldPoint Controller
  • National Instruments 779429-01 Ordering Part Number
  • National Instruments NI-9149 8-Slot EtherCAT Chassis
  • National Instruments PXI-4110 Programmable DC Supply
  • National Instruments 192061-10 Ordering Part Number
  • National Instruments cDAQ-9181 Chassis Module Carrier
  • National Instruments NI 9437 Digital Input Module
  • National Instruments cFP-2020 Compact FieldPoint Controller
  • National Instruments PCI-6259 Multifunction DAQ Card
  • National Instruments FP-TC-120 Thermocouple Module
  • National Instruments NI-9174 CompactDAQ Chassis
  • National Instruments PXI-6030E DAQ Module
  • National Instruments PXIe-5160 Oscilloscope
  • National Instruments PXI-4462 DSA Module
  • National Instruments PXI-8109 Controller
  • National Instruments PXI-6259 DAQ Card
  • National Instruments PXI-6030E DAQ Card
  • National Instruments cRIO-9056 Controller
  • National Instruments PXIe-8370 MXI Kit
  • National Instruments USB-6212 DAQ Device
  • National Instruments RMX-4000 Electronic Load System
  • National Instruments 785040-01 Ordering Part Number
  • National Instruments cFP-AI-110 Analog Input Module
  • National Instruments cDAQ-9189 8-Slot Chassis
  • National Instruments PXIe-4139 Source Measure Unit
  • National Instruments PXI-5620 Digitizer Module
  • National Instruments PCIe-8371 MXI-Express Card
  • National Instruments 196762B-01L Ordering Part Number