System scalability: CIOC can connect up to 4 controllers via Ethernet, and adding controllers or reallocating I/O does not require any physical wiring changes; Support online addition of CHARM (any empty space on the motherboard) and CIOC to adapt to changes in I/O requirements during the migration process.
Installation flexibility: CIOC needs to be installed on vertical DIN rails (which can be located on the front and rear sides, upper and lower parts of the cabinet), and cannot be installed horizontally; The height of the CHARM base plate migration component is 3 EIA units (5.25 inches), and the installation location can be flexibly selected (reusing existing cable trays/cable trays, adjacent installation, or reserved spacing).
Hardware specifications and compatibility
(1) Core hardware environment and size specifications
1. CHARM I/O Migration Panel
Environmental specifications working temperature: -40~70 ° C (copper Ethernet port), -40~60 ° C (fiber Ethernet port); Storage temperature: -40~85 ° C; relative humidity: 5%~95% (no condensation); Protection level: IP20; Pollutant level: ISA-S71.04-1985 G3 level (with conformal coating); Impact resistance: 10g half sine wave (continuous for 11ms); Vibration: 5-13.2Hz (1mm peak to peak), 13.2-150Hz (0.7g)
Dimensions: Height 10.5 inches (26.7cm), Depth 6.68 inches (17.4cm), Width 19 inches (48.3cm); Installation method: 19 inch EIA rail (6 rack units high)
2. CHARM Bottom Plate Migration Panel
The environmental specifications are consistent with the CHARM I/O migration panel (with a fixed operating temperature of -40~70 ° C)
Dimensions: Height 5.25 inches (13.3cm), Depth 4.8 inches (12.2cm), Width 19 inches (48.3cm); Installation method: 19 inch EIA rail (3 rack units high)
3. IS CHARM Bottom Plate Migration Panel
The environmental specifications are consistent with the above-mentioned bottom migration panel
Size without channel identification label: Height 5.34 inches (13.6cm), Depth 6.45 inches (16.4cm); Channel identification label: height 5.73 inches (14.6cm), depth 6.45 inches (16.4cm); The width is 19 inches (48.3cm), and the installation method is the same as before (3 rack units high)
Special note: The size of IS CHARM is different from non IS models. When installed on a 19 inch panel, it protrudes 45mm from non IS models
(2) System compatibility
Software version requirements: DeltaV electronic grouping hardware must be paired with DeltaV v11.3.1 or higher versions.
Controller adaptation: Supports M-series, S-series, and PK series controllers.
Component compatibility: All CHARM types, IS/non IS I/O terminal blocks, and key control columns are compatible with the migration panel; CIOC2 can directly replace CIOC, and the fiber optic Ethernet I/O ports cannot be cascaded.
Ordering Information and Preconditions
(1) Core Hardware Ordering List (Some Key Models)
CHARM I/O card redundant migration CIOC2 (copper Ethernet), including redundant CIOC2, carrier with screw terminals, copper I/O ports, etc. SE6505T03
CHARM I/O card redundant migration CIOC2 (fiber optic Ethernet), including redundant CIOC2, carrier with screw terminals, fiber optic I/O ports, etc. SE6505T04
Migration panel 19 inch migration panel, supporting 2 redundant migration CIOC SE6503T01
CHARM Base Plate Component Standard Migration Base Plate Component (2 Base Plates, 24 Standard Terminal Blocks, etc.) SE4601T03
CHARM motherboard component with 3-wire DI fuse injection power supply migration motherboard component SE4601T10
CHARM Base Plate Component with Relay Output Migration Base Plate Component SE4601T06
IS CHARM Base Plate IS CHARM Migration Base Plate Component (2 IS Base Plates, 24 IS Standard Terminal Blocks, etc.) SE4608T02
Address plug CHARM Address plug (1-8) SE4602
Address plug CHARM Address plug (1-4) SE4613
Auxiliary component CHARM baseplate top extender (with plug) SE4603T05
Auxiliary component CHARM base plate bottom extender (with socket) SE4603T06
Auxiliary component CHARM base cable (2 pieces, 0.5m) SE4605T02
Auxiliary component DIN rail block (5 pieces/box) VE4054DRS
IS special accessory IS CHARM 24V DC power fuse component SE4610T01 (to be ordered in combination with SE6501T03/SE6501T04 for 2 units)
(2) Pre requirements
Hardware installation must follow DIN rail specifications, and vertical DIN rails must be equipped with a stopper (model VE4054DRS) to fix the position of the base plate.
When using the IS CHARM motherboard, an additional order for SE4610T01 fuse components is required (2 for each CIOC configuration compatible with the IS motherboard).
Fiber optic Ethernet I/O ports cannot be cascaded, and attention should be paid to network topology design.
email:1583694102@qq.com