Supporting requirements: A dedicated installation carrier must be selected for each controller (refer to the "I/O Carrier" product data sheet for details), and each controller must be equipped with an independent system power supply (refer to the "Power Supplies" product data sheet for details).
(2) Environmental parameters
Specific requirements for environmental indicators
Working temperature -40 ° C~70 ° C (-40 ° F~158 ° F)
Storage temperature -40 ° C~85 ° C (-40 ° F~185 ° F)
Relative humidity 5%~95% (no condensation)
The air pollutants meet the ISA-S71.04-1985 G3 level air pollutant standard and have a conformal coating
Shock (normal working state) 10g half sine wave, lasting for 11 milliseconds
Hazardous area/location level ATEX EEx nA IIC T4, Class 1, Div 2, Groups A, B, C, D, T4 level
When the vibration (working limit) is between 5Hz and 16Hz, the peak to peak value is 1mm; 0.5g at 16Hz~150Hz
Technical specifications
Specific content of technical parameters
The power requirement is supplied by the system power supply through a 2-wide Power/Controller Carrier
Fuse protection 3.0A non replaceable fuse
Typical power consumption is 5.0W, maximum value is 7.0W
User memory 48MB
Main control network interface 8-pin RJ-45 connector
Redundant control network interface 8-pin RJ-45 connector
LED indicator light (meaning lit) - green (power): indicates that the DC power supply has been connected
-Red (Error): Indicates the existence of an error status
-Green (Active): indicates that the controller is running as the main controller
-Green (Standby): indicates that the controller is running as a backup controller (reserved function, not yet enabled)
-Yellow flashing (Pri. CN): indicates normal communication in the main control network
-Yellow flashing (Sec. CN): indicates that the backup control network communication is normal
-All flashing except for the power light: triggered by the ping command of the user interface software, used for visual recognition of the controller
-Except for the power light, even and odd digits flash alternately: indicating that a firmware upgrade is in progress