In large commercial courtyards, church domes, hangars, warehouses, sports arenas, and enclosed parking lots, traditional point type smoke detectors are difficult to work effectively due to smoke stratification effects and installation and maintenance difficulties. The beam type smoke detector detects smoke by emitting a beam of infrared light and measuring the attenuation of the light intensity at the receiving end, which can cover a protection range of tens to hundreds of meters. However, traditional dual ended radiation detectors require precise alignment of the transmitter and receiver, which is time-consuming and costly to install and debug.
7.3 Selection Suggestions
For standard tall spaces (height 10-30 meters, span ≤ 70 meters), choose the TC847A1004 standard configuration.
For ultra long spans (70-100 meters), TC847A1004+BEAMLRK must be selected.
For extremely cold or high humidity environments such as cold storage and outdoor canopies, install BEAMHK and BEAMHKR to prevent mirror condensation.
For places with high vibration, such as near large stamping equipment or along railway lines, use the 6500-MMK heavy-duty installation kit.