A. 83 Absolute Value Encoder Battery Error Battery voltage<2.7V Replace battery when powered on (ER6VC3 or JZSP-BA01)
A. CC multi cycle limit inconsistency SERVPCACK and encoder multi cycle setting are different. After modifying Pn205, execute Fn013
A. The d0 position error pulse overflow position gain is too low, the load inertia is large, and the pulse frequency is too high, increasing Pn102; Reduce the electronic gear ratio; Check the machinery
A. F1 power supply phase loss inspection, main power supply phase loss inspection, L1/L2/L3 wiring and MCCB
7.2 Alarm Reset
Press the RESET button on the numeric operator (while pressing UP+DOWN on the panel operator).
Through the CN1-44 (/ALM-RST) signal (low level active).
Partial alarms (A.02, A.04, A.81, A.82, etc.) require power outage and restart.
7.3 Troubleshooting of motor not rotating despite no alarm display
Check if/S-ON is at low level (servo enabled).
Check if P-OT/N-OT is at low level (operation is prohibited when overtravel is prohibited).
Check if the control power supply DC24V is normal.
Speed control mode: Check if there is voltage in V-REF; Position control mode: Check if PULS signal is input.
When using an absolute value encoder, the SEN signal must be at a high level (absolute data request).
Chapter 8: Maintenance and upkeep
8.1 Regular inspection items
Component cycle inspection content
Daily vibration, abnormal noise, and surface cleaning of the motor
The insulation resistance of the motor is measured annually with a 500V megohmmeter, and is ≥ 10M Ω (with SERVOPACK disconnected)
Oil seal replaced every 5000 hours
SERVOPACK cooling fan replacement in 4-5 years
Smooth capacitors should be checked for leakage and discoloration after 7-8 years, and replaced if necessary
Circuit board electrolytic capacitor 5-year test, replace circuit board if necessary
8.2 Absolute value encoder battery replacement
When an A.83 alarm occurs, the battery (model ER6VC3 or JZSP-BA01) must be replaced while the SERVOPACK control power supply is powered on. After replacement, turn off the power and then turn it back on to clear the alarm. If the battery is completely discharged and multiple cycles of data are lost, Fn008 needs to be executed to reset multiple cycles of data and reset the zero point.
8.3 Precautions for long-term discontinuation
If stored for a long time (more than 6 months), it is recommended to power on every six months to prevent the degradation of electrolytic capacitors.
Chapter 9: Selection and Combination Quick Search
9.1 Combination Table of Servo Motor and SERVOPACK
Rated power of servo motor SERVOPACK Continuous current (A) Maximum current (A) Allowable load inertia (× 10 ⁻⁴ kg · m ²)
SGMBH-2BD 22kW SGDH-2BDE 58 120 2960
SGMBH-3ZD 30kW SGDH-3ZDE 80 170 3865
SGMBH-3GD 37kW SGDH-3GDE 100 210 6950
SGMBH-4ED 45kW SGDH-4EDE 127 260 7550
SGMBH-5ED 55kW SGDH-5EDE 150 310 9850
9.2 External Regenerative Resistance Unit
SERVOPACK regeneration resistor unit resistance value (Ω) capacity (W)
2BDE/3ZDE JUSP-RA12 9 3600
3GDE JUSP-RA14 5 4800
4EDE JUSP-RA15 4 6000
5EDE JUSP-RA16 3.8 7200
9.3 Recommended MCCB and noise filter
SERVOPACK MCCB Capacity (A) Recommended Noise Filter
2BDE 100 FN258L-75-34
3ZDE/3GDE 150 FN258L-100-35 / FN258L-130-35
4EDE/5EDE 225 FN258L-180-07