SIEMIENS SIMATIC 505 Analog I/O Module

F: | Au:FAN | DA:2025-11-24 | 925 Br: | 🔊 点击朗读正文 ❚❚ | Share:

SIEMIENS SIMATIC 505 Analog I/O Module

The complete user guide for SIMATIC 505 series analog I/O modules focuses on four single width modules (input module PPX: 505-6108A/6108B, output module PPX: 505-62088A/6208B), covering the entire process of module technology principles, installation and wiring, calibration and maintenance, and troubleshooting. All modules are compatible with the Series 505 controller, and the input module supports 8-channel ± 5V/± 10V voltage or 0-20mA current signal acquisition (12 bit resolution for version A and 13 bit resolution for version B). The output module synchronously provides 8-channel 0-10V voltage and 0-20mA current signals (12 bit resolution); Installation must follow shielded twisted pair wiring and terminal block wiring specifications. The input module does not require an external power supply, while the output module requires a 20-28VDC user power supply; Calibration needs to be carried out every 6-12 months to ensure measurement and control accuracy in industrial scenarios. At the same time, solutions such as LED status indication and fuse replacement are used to ensure stable operation of equipment, suitable for industrial analog signal processing scenarios such as pressure, temperature, and flow.


Overview of Core Framework and Modules

2.1 Basic Information

Applicable module analog input: PPX: 505-6108A, PPX: 505-6108B; Analog output: PPX: 505-6208A, PPX: 505-6208B

The core positioning is aimed at industrial automation engineers, providing a full process operation guide for module selection, installation, configuration, and maintenance

Certified compliance with UL (Industrial Control Equipment), CSA (Process Control Equipment), ATEX Class I Div.2 (Hazardous Areas), CE (Low Voltage/EMC Directive) and other standards

The supporting documents should be used in conjunction with the SIMATIC 505 System Manual, SIMATIC 500/505 TISOFT Release 6.3 User Manual, and other related documents

2.2 Module Core Positioning and Advantages

Design features: Single width structure, can directly replace dual width analog modules (without modifying the original wiring), saving controller slot space;

Function positioning: As a bridge between the Series 505 controller and industrial field equipment, the input module collects analog signals from sensors (such as temperature transmitters and pressure sensors) and converts them into digital signals. The output module converts the controller's digital signals into analog signals to drive actuators (such as regulating valves and frequency converters);

Core advantages: Supports multiple signal types, strong anti-interference ability (1500Vrms isolation), easy installation and maintenance, suitable for harsh industrial environments (0-60 ℃ working temperature, 5% -95% non condensing humidity).

image.png

Module technology principles and core parameters

3.1 Analog Input Module (PPX: 505-6108A/6108B)

3.1.1 Working principle

The module adopts analog-to-digital conversion (ADC) technology to convert continuously changing voltage/current signals into discrete digital quantities:

PPX: 505-6108A: Adopting dual slope integral conversion method, strong anti-interference ability, suitable for low-speed stable signal acquisition;

PPX: 505-6108B: Adopting the successive approximation conversion method, the conversion speed is faster and the resolution is higher, suitable for high-precision dynamic signal acquisition.

Both convert current signals into voltage signals through internal 250 Ω± 0.1% precision resistors, and then perform ADC conversion.

3.1.2 Key Technical Parameters

Parameter category PPX: 505-6108A PPX: 505-6108B

Number of channels: 8 channels, single ended input: 8 channels, single ended input:

Signal range voltage: ± 5V (default), ± 10V (jumper selection); Current: 0-20mA Same as left

Resolution of 12 bits+sign bit (± 5V range: 1.25mV/step; 0-20mA range: 5 μ A/step) 13 bits+sign bit (± 5V range: 0.625mV/step; 0-20mA range: 2.5 μ A/step

Conversion accuracy (25 ℃) Voltage: ± 0.5% of full scale; Current: ± 0.7% full-scale voltage: ± 0.25% full-scale; Current: ± 0.35% of full scale

Temperature coefficient voltage: 58ppm/℃; Current: 83ppm/℃ Voltage: 50ppm/℃; Current: 80ppm/℃

The maximum conversion time is 330ms (input system delay); Maximum update time 250ms (full channel), maximum sampling repetition time 25ms

Input protection overvoltage: ± 30VDC (clamp diode); Overcurrent: 30mA (optical isolation) same as left

Power requirement: Base only power supply (from controller): maximum 4W, typical 2.5W. Base only power supply: maximum 4W, typical 1.1W

3.1.3 Digital Format and Signal Conversion

The controller only receives 16 bit digital signals, and the module encapsulates the ADC conversion results into 16 bit words:

PPX: 505-6108A: bits 1-12 are valid data, bit 13 is the sign bit (1=negative, 0=positive), bit 14 is the over range bit (1=over range), bits 15-16 are invalid bits (fixed 0);

PPX: 505-6108B: bits 1-13 are valid data, bit 14 is the sign bit, bit 15 is the overrange bit, and bit 16 is the invalid bit (fixed 0);

Over range determination: When the input voltage exceeds ± 5.00125V (± 5V range) or ± 10.0025V (± 10V range), the over range position 1 and the digital quantity exceed ± 32000;

Conversion formula:

Voltage input (± 10V range): Digital quantity (WX)=(input voltage/10V) × 32000;

Current input (0-20mA range): Digital quantity (WX)=(input current/20mA) × 32000.

3.2 Analog Output Module (PPX: 505-6208A/6208B)

3.2.1 Working principle

The module receives a 16 bit digital signal from the controller and converts it into a continuous analog signal through digital to analog conversion (DAC) technology. The voltage and current outputs are synchronized (the same channel can output two types of signals simultaneously without switching):

The current output is designed as a source type, and in the event of a short circuit, the current will bypass the on-site equipment. It is necessary to avoid short circuits in the output circuit;

If the digital sign bit (bit 1) is 1 (negative value), the module does not update the output and maintains the previous positive value output.

3.2.2 Key Technical Parameters

Parameter category PPX: 505-6208A PPX: 505-6208B

Number of channels: 8 channels, single ended output: 8 channels, single ended output:

Signal range voltage: 0-10VDC; Current: 0-20mA (source type) same as left

Resolution 12 bits (voltage: 2.5mV/step; Current: 5 μ A/step) Same as left

Conversion accuracy (25 ℃) Voltage: ± 0.5% of full scale; Current: ± 0.5% full range same as left

Full temperature range precision voltage: ± 1.45% of full range; Current: ± 1.83% full range same as left

Temperature coefficient voltage: 136ppm/℃; Current: 204ppm/℃ Voltage: 50ppm/℃; Current: 100ppm/℃

Response characteristic response time: 27ms (minimum) -54ms (maximum); Stability time: Voltage 0.2ms, Current 2.0ms Response time: Maximum 10ms Stability time: Same as left

Load requirement voltage: ≥ 5000 Ω, maximum capacitance 0.01 μ F; Current: 10-600 Ω (over 600 Ω requires 10V power supply, maximum 1000 Ω) Same as left

Power demand base power supply: maximum 2W (typical 1.0W); User Power Supply: 20-28VDC, 0.5A (Ripple ≤± 0.4VDC, UL Class 2) Same as Left

3.2.3 Digital Format and Signal Conversion

The controller outputs a 16 bit digital quantity: bits 1-12 are valid data, bits 13-16 are invalid bits (fixed to 0);

Conversion formula:

Voltage output: Digital quantity (WY)=(target voltage/10V) × 32000;

Current output: Digital quantity (WY)=(target current/20mA) × 32000.


Installation and wiring specifications

4.1 Wiring Core Requirements

4.1.1 Cable selection and protection

Cable specifications: 14-24 AWG (0.18-1.5mm ²) shielded twisted pair, supporting stranded (multi strand) or solid (single strand) wires;

Temperature and voltage resistance: The wire has a temperature resistance of ≥ 75 ℃ and a rated voltage of ≥ 300V, meeting the insulation requirements of industrial environments;

Anti interference measures:

Separate the wiring of signal cables and power cables (such as motor power lines) to avoid parallel laying, and form a 90 ° angle when crossing;

Avoid laying cables on vibrating surfaces, do not bend them into sharp angles, and use cable trays for standardized routing;

Shielding layer grounding: The shielding layer of the input cable is grounded at the signal source end, and the shielding layer of the output cable is grounded at the controller base end. It is strictly prohibited to ground both ends at the same time (to prevent noise caused by ground circulation).

4.1.2 Output module circuit calculation

Current circuit resistance: circuit cable equipment (L is the cable length, cable is the unit length resistance, equipment is the on-site equipment resistance); When the circuit is between 10-600 Ω, connect it directly; When the circuit is between 600-1000 Ω, a 10V DC power supply needs to be connected in series in the circuit; When the circuit is greater than 1000 Ω, it is necessary to replace the thick wire diameter cable or shorten the wiring distance, otherwise the output accuracy will decrease.

Fixed error of voltage circuit: The error equipment cables must ensure that the error is within the allowable range.

4.2 Terminal block wiring

4.2.1 Terminal block types and wiring steps

Terminal block model:

Standard configuration: PPX: 2587705-8006;

Optional: PPX: 2587705-8002 (wiring method consistent with standard, can replace old terminal blocks of double width modules);

Wiring steps:

Strip wire 0.25 inches (1.0cm), optional installation of fork/ring terminal blocks (Amp 321462/327891, compatible with # 4 studs);

Connect the wires according to the pin diagram (Figure 2-4), first connect the D terminal, then connect the C, B, and A terminals in sequence, and tighten the screws to ensure good contact;

After the wiring is completed, check the terminal definition to avoid misconnection (such as the "Return" terminal of the input module cannot be suspended, and the "24V common" output module needs to be reliably grounded).

4.2.2 Input module wiring differences

Key points to note for input type wiring method

Voltage input (± 5V/± 10V) signal+connected to voltage input terminal (such as channel 1 connected to A2 "V1 in"), signal - connected to return terminal (A3 "Return 1") does not need to be short circuited, ensuring that the internal resistance of the signal source is ≤ 1k Ω to avoid signal attenuation

Current input (0-20mA): First, short-circuit the current input terminal (A1 "I1 in") to the voltage input terminal (A2 "V1 in"). Connect the signal+to A1 and the signal - to A3. The short circuit should be directly connected with a wire and should not pass through high resistance components to ensure that the current flows through the internal 250 Ω resistor

4.2.3 Typical wiring scenarios

2-wire transmitter wiring (input module): transmitter+connected to input module current input terminal, transmitter - connected to return terminal, module provides power to transmitter through internal circuit;

4-wire transmitter wiring (input module): The transmitter is independently powered, with signal+connected to the current input terminal and signal - connected to the return terminal;

Output module wiring (4-channel example): Each channel simultaneously outputs voltage (such as A2 "V1 out") and current (A1 "I1 out"), which are connected to the corresponding actuators. The common terminal (Return) is grounded uniformly.

4.3 Module Installation and I/O Configuration

4.3.1 Module installation steps

Power off operation: Before installation, turn off the controller and all external power sources to avoid electric shock or component damage;

Slot selection: Insert the module into the idle single width I/O slot of the Series 505 controller, avoiding proximity to high-energy switch modules or EMI sources (such as frequency converters);

Fixed module: Tighten the module panel with screws and control the torque at 2.6-4.12 in lb (0.3-0.6N · m) to avoid damaging the module or base due to over tightening;

Static protection: Do not touch the module circuit board during installation, and wear an anti-static wristband if necessary.

4.3.2 I/O Configuration Process

Configuration tool: Use SIMATIC 500/505 TISOFT Release 6.3 software to connect the controller through programming devices;

Module registration: Select the base number and slot number in the "I/O Module Definition Table", configure the module type and I/O parameters (Table 2-1):

|Module model | WX (number of input words) | WY (number of output words)|

| PPX:505–6108A | 08 | 00 |

| PPX:505–6108B | 08 | 00 |

| PPX:505–6208A | 00 | 08 |

| PPX:505–6208B | 00 | 08 |

Address allocation: The system automatically assigns I/O addresses (such as the input module address for slot 1 starting from WX0001), which are downloaded to the controller after configuration is complete;

Verify configuration: After powering on, observe the "Module Good LED" of the module. If the LED lights up, it indicates that the configuration is successful and the module has no faults.

image.png

Calibration and maintenance process

5.1 Basic Requirements for Calibration

5.1.1 Calibration cycle and conditions

Calibration cycle: It is recommended to calibrate every 6-12 months; If the module is used in high temperature and vibration environments for a long time, or if the measurement accuracy exceeds the tolerance, it needs to be calibrated immediately;

Environmental conditions: The calibration environment temperature is 25 ℃± 2 ℃, with no vibration or electromagnetic interference. The module reaches working temperature after being powered on for 30 minutes;

Tool preparation:

Calibration power supply: DC voltage source with an accuracy of ≥ 0.01% (used for input module calibration);

Measurement tool: a multimeter with an accuracy of ≥ 0.1% (for voltage/current measurement);

Load resistance: 5.1k Ω± 5% (voltage output calibration), 100 Ω± 5% (current output calibration);

Auxiliary tools: non-metallic screwdriver (to avoid short circuits), Euro extender card (optional, convenient for accessing potentiometers).

5.1.2 Calibration precautions

Disconnect the on-site wiring before calibration, leaving only the connections between the module, controller, and calibration equipment;

The controller needs to switch to "STOP mode" to avoid interference with calibration during operation;

The input module needs to first select the voltage range (jumper setting ± 5V or ± 10V) before calibration;

During the calibration process, avoid touching the module circuit board to prevent static damage or short circuits.

5.2 Input module calibration steps (PPX: 505-6108A/6108B)

Power off preparation: Turn off the controller power, disconnect the module field wiring. If using Euro extender card, remove the module first, insert the card, and then install the module onto the card;

Range selection: Select the calibration voltage range (± 5V or ± 10V) through the jumper on the module circuit board;

Power on preheating: Turn on the controller power and wait for 30 minutes for the module to reach operating temperature;

Device connection: Connect programming devices and controllers to ensure that module input data can be read; Connect the calibration voltage source to all input channels of the module;

Full range calibration (positive direction):

Input+5V (± 5V range) or+10V (± 10V range) to all channels;

Adjust the calibration potentiometer on the module circuit board with a non-metallic screwdriver until the programming device displays an average of+32000 for all channel numbers;

Full range calibration (negative direction):

Input -5V (± 5V range) or -10V (± 10V range) to all channels;

Adjust the potentiometer until the average digital value of all channels is -32000;

Accuracy verification: Enter+5V/+10V again to verify the numerical deviation:

PPX: 505-6108A: allowable deviation of ± 129/± 128;

PPX: 505-6108B: allowable deviation of ± 81/± 80;

Restore wiring: After calibration is complete, power off, remove the calibration equipment, restore on-site wiring and module installation positions, and reconfigure I/O addresses.

5.3 Calibration steps for output module (PPX: 505-6208A/6208B)

Power outage preparation: Turn off the controller and user power, disconnect the module load from the on-site wiring, and retain the user power wiring;

Load connection: Connect calibration loads to all output channels of the module (voltage channel connected to a 5.1k Ω resistor, current channel connected to a 100 Ω resistor);

Power on preheating: Turn on the controller and user power, wait for 30 minutes for the module to reach operating temperature;

Device connection: Connect programming devices and controllers to ensure that digital data can be written to the module;

Full range output: Write a digital quantity of 32000 to all channels (corresponding to 10V/20mA full range output);

Reference channel selection: Measure the current output values of all channels, calculate the average value, and select the channel with the output value closest to the average value as the reference;

Current calibration: Use a non-metallic screwdriver to adjust the calibration potentiometer so that the reference channel current output is 20.000mA (25 ℃);

Accuracy verification:

Voltage output: All channels must be 10.000V ± 50mV;

Current output: All channels must be 20.00mA ± 0.1mA;

If the deviation exceeds the tolerance, repeat steps 6-8;

Restore wiring: After calibration is completed, power off, remove the calibration load, and restore on-site wiring and module configuration.

5.4 Daily maintenance and troubleshooting

5.4.1 Key points of daily maintenance

Cleaning module: Clean the module panel and terminal block with a dry soft cloth every 3 months to avoid dust accumulation;

Wiring inspection: Check the tightening of terminal block screws every 6 months to prevent loose wiring caused by vibration;

Power inspection: Regularly check the user power supply (20-28VDC) of the output module to ensure that the ripple is ≤ ± 0.4VDC;

Fuse maintenance: When the output module fuse (0.5A fast melting, model PPX: 2587679-8009) burns out, it is necessary to first investigate the cause of overvoltage/overcurrent before replacing the fuse.

5.4.2 Common troubleshooting

Possible causes of malfunction, troubleshooting steps, and solutions

Module Good LED not lit (input module) Base power failure, module self diagnosis failure 1. Measure whether the base power supply voltage is normal; 2. Check if the module is correctly inserted into the slot; 3. Disconnect all wiring and reinstall. 1. Repair the power supply of the base; 2. Re plug and unplug the module; 3. Module self diagnosis failure requires return for repair

Module Good LED not lit (output module) Base power failure, user power failure, blown fuse, self diagnosis failure. 1. Measure the base and user power supply; 2. Check the status of the fuse; 3. Check if the module wiring is short circuited. 1. Repair the power supply; 2. Replace the fuse; 3. After eliminating the short circuit, power on again; 4. Self diagnosis failure requires return for repair

Input module reading error, wiring error, signal noise, calibration deviation, signal source out of range. 1. Check the wiring by referring to the pin diagram; 2. Check if the grounding of the shielding layer is correct; 3. Verify whether the output of the signal source is within ± 5V/± 10V or 0-20mA; 4. Recalibrate module 1. Correct wiring; 2. Optimize shielding and wiring; 3. Adjust the signal source to the effective range; 4. Complete calibration

The output module outputs abnormal loads beyond the range, digital input errors, calibration deviations, and unstable user power supply. 1. Measure whether the load resistance/capacitance meets the requirements; 2. Check if the digital output of the controller is correct; 3. Recalibrate the module; 4. Measure the user's power ripple. 1. Replace the load that meets the requirements; 2. Repair the digital output of the controller; 3. Complete calibration; 4. Replace the stable power supply

PLC reports non fatal module configuration error, module and controller communication failure. 1. Check the I/O configuration parameters (WX/WAY quantity); 2. Check if the module is in good contact with the base; 3. Restart the controller. 1. Correct the configuration parameters; 2. Re plug and unplug the module; 3. If the error persists after restarting, it needs to be returned for repair


Environmental and Safety Parameters (Appendix B)

6.1 Environmental adaptation parameters

Parameter indicators

Working temperature 0-60 ℃ (32-140 ℉)

Storage temperature -40-70 ℃ (-40-158 ℉)

Relative humidity 5% -95% (non condensing)

Vibration resistance sinusoidal vibration: 10-57Hz, 0.15mm peak to peak value; Random vibration: 57-150Hz, 1.0g

Impact resistance meets the IEC 68-2-27 Test Ea standard

Electrostatic Discharge (ESD) IEC 801-2 Level 4 (15kV)

Electromagnetic compatibility (EMC) conducted immunity: IEC 801-4 Level 3; Radiation immunity: IEC 801-3 Level 3

1500Vrms between the isolation voltage field and the controller

All components of corrosion protection are treated with corrosion-resistant materials, coatings, or spray paint

6.2 Safety Regulations

Overvoltage protection: Input module ± 30VDC, output module 30VDC;

Overcurrent protection: Input module 30mA, output module protected by fuse (0.5A);

Hazardous area use: Complies with ATEX Class I Div.2 standards and can be used in flammable dust environments (must meet dust explosion prevention requirements);

Wiring safety: The rated voltage of signal cables should be ≥ 300V, avoid mixing with power cables, and prevent insulation breakdown.

image.png

  • Guardmaster 440R-D22R2 Safety Relay Specifications
  • NL12880BC20-10ND Industrial Display Panel Data
  • LFI 12X5326-S1 Slide-in Control Board Technical Data
  • Modicon AS-9370-001 Programmable Controller Data
  • Mitsubishi Kakoki E-01B-4130 PLC Module Overview
  • Guardmaster 440R-D22S2 Dual Input Safety Relay Data
  • NL10276AC30-48D Industrial LCD Display Panel Data
  • GE ICMFA000000-ABAC Field Control Module Specification
  • Siemens 6SN1123-1AB00-0BA1 SIMODRIVE Module Review
  • Siemens 6SL3210-1SE23-2AA0 Power Module Technical Data
  • Schmersal T.250-11z-t Limit Switch
  • Schmersal T.250-11z-t Limit Switch
  • Honeywell 900H32-0102 ControlEdge 900 PLC
  • Siemens 6FX1132-1BA01 PCB B84141-A-A40
  • BEMAC UST-202-D 1307D PLC Circuit Board
  • Mitsubishi HS-MF23-S2A Servo Motor
  • B&R 3AI775.6 Analog Input Module
  • Omnipure 69003 Rev 11 3-Phase Gate Board PCB
  • Pilz 751134 PNOZ s4 C Safety Relay
  • Proface PFXGM4301TAD HMI Graphic Panel
  • Keyence KV-RC8BXR Programmable Controller
  • Siemens 6GK7243-1BX30-0XE0 CP 1243-1 Ethernet Module
  • Mitsubishi GT2310-VTBA GT2310-VTBD HMI 10.4 Inch
  • Schmersal SRB-NA-R-C.21-24V Safety Relay Module
  • Emotron 01-2520-40 M20 Shaft Power Monitor 3x380-500V
  • Omron CQM1 SYSMAC PLC System PA203 ID211 OC221
  • ABB CI830 3BSE013252R1 Profibus DP V1 Module
  • B&R 4PP035.0300-01 Power Panel PLC Module
  • SICK S30A-6111CL S3000 PROFINET Safety Laser Scanner
  • Siemens 6ES7215-1HG40-0XB0 CPU 1215C AC/DC/RLY
  • Automation Direct H2-ECOM100 Ethernet Module Details
  • Siemens 6GK1143-0TB01 CP 1430 TF Module Review
  • Siemens Simatic 505 10 Slot PLC Rack Technical Review
  • Automation Direct EZ-SP Message Display Unit
  • Mitsubishi A1SJ71QE71N-B5T Ethernet Interface Unit
  • Modicon AS-P810-000 Modbus Plus Processor Unit
  • Honeywell 51309241-175 TK-PPD011 PWA Specifications
  • Omron S8AS-24006N Smart Power Supply Specifications
  • Beckhoff EL3218-0018 EtherCAT Terminal Specifications
  • Omron CJ1W-PRT21 PROFIBUS-DP Interface Unit
  • Inovance AC810-0122-U0R0 PLC Controller
  • Cypress CY7C1021CV33-10ZXCT 1Mb SRAM IC
  • GE Fanuc IC695CPU315-CD PLC CPU Module RX3i
  • Drager 8312088 PCB Safety Module PAC 5500
  • Weltronic H70-T02A S430-V1.2 Weld Timer PLC
  • B&R 3AM051.6 PLC Analog Input Module
  • Schneider BMENOC0301 Communication Module M580
  • Mitsubishi FX3UC-32MT-LT PLC Controller
  • Omron TZ-1G TZ-1GV TZ-1GV2 TZ-1GV22 Motion Switch
  • Mitsubishi AJ71C21-B1-S2 PLC Controller 424749
  • Beckhoff EL5042 EtherCAT Encoder Terminal BiSS C
  • Eaton easyE4 Programmable Relay 12 Inputs 8 Outputs
  • Carel PCO5 P+ 500BAA000L0 Programmable Controller
  • Siemens 6ES7223-1PL22-0XA0 EM223 I/O Module 16DI 16DO
  • Lenze EMF2179IB DeviceNet Communication Module
  • Mitsubishi Q173DCPU Motion CPU Module
  • B&R X20AT2222 Temperature Input Module Pt100
  • Siemens SITOP UPS1100 Battery Module 7Ah 6EP4134-0GB00-0AY0
  • Mitsubishi QJ71DN91 DeviceNet Master Slave Module
  • B&R X20AO4622 Analog Output Module 4 Channels
  • B&R X20CP1486 Controller Manual
  • Siemens 6ES7134-4GB51-0AB0 Module Manual
  • Schneider LMC201CAA10000 Controller Manual
  • Fuji Electric NP1L-RS4 Module Guide
  • Mitsubishi FX2N-16LNK-M Master Guide
  • Yaskawa SGDM-08ADA SGMAH-08AAA41 Manual
  • Fanuc A20B-0008-0470 Board Manual
  • Calpeda T 70/B Module Specifications
  • Eurotherm TC3000 Power Drive Specifications
  • Mitsubishi QJ71GP21S-SX Module Manual
  • B&R X20AI4622 Analog Input Module 4 Channels
  • Siemens Simatic S5 PLC I/O and CPU Modules
  • Tel 38950 PCB Board 5044-000171-11 AP9Z-2033A
  • Sanyo PLC-XTC50L Multimedia Projector
  • Siemens 6GK7243-5DX30-0XE0 CP 243-5 AS-Interface
  • Omron V680-CA5D02-V2 RFID Controller
  • Pilz 570640 PSEN SL-1.0P Safety Switch
  • Schneider LXM62DD27D21000 Servo Drive
  • Pilz 401112 PITswitch en1.1a-5m-s Emergency Stop Switch
  • Pilz 774350 P2HZ X3 Safety Relay
  • Siemens S30810-Q1113-X4-6/02 EWSD Module Board
  • Honeywell 30751044-008 ROM PLC Control Board
  • Allen-Bradley 440R-W23219 MSR310P Safety Relay
  • Siemens 6GK5204-2BB10-2AA3 Industrial Ethernet Switch
  • Siemens YSU C32353ADDAGS C98043 PC Board
  • Schneider TM241CEC24T PLC Controller Modicon M241
  • VARIAN E15000591 PLC PCB Assembly 132102
  • Schneider Electric HMIG3U PLC Controller Module
  • Siemens 6ES7148-4FC00-0AB0 ET200 IO Module
  • Siemens A5E30484420 Simatic IPC Redundant PSU
  • Allen Bradley 1771-A3B Chassis Manual
  • Schneider BMEH586040 Processor Manual
  • Mitsubishi GT2508 Graphic Panel Manual
  • Mitsubishi FX2N-16LNK-M Link Module Manual
  • Beckhoff EL3011 Analog Terminal Manual
  • Siemens 6SN1145-1AA01-0AA1 Infeed Manual
  • Proface SP5000 Series Display Specifications
  • NUM 0204203001 Axes Board Manual
  • Square D LV434001 Ethernet Interface Manual
  • Omron NA5 Series HMI Module Specifications
  • ABB 57619104E Inverter PCB Control Board
  • Allen-Bradley 100-E205ED11 MCS-E Contactor 205A
  • Omron NS12-TS01-ECV2 Series Operation Panel
  • Allen-Bradley 440R-EM4R2 Guardmaster Safety Relay
  • Omron CS1D-DPL01 Duplex System PLC Module
  • Beckhoff CX2030-0115 Embedded PC Controller
  • ABB Pluto S20 v2 Cfs Safety PLC 2TLA020070R4700
  • B&R X20AT4222 Analog Input Module RTD
  • Inovance H3U-3624MT PLC Controller
  • GE Fanuc IC698CPE010 PLC CPU Module
  • Texas Instruments Siemens 505-6208-A Analog Input Module
  • VDISP 0035416 Card Module Industrial Display Controller
  • HITACHI TX09D80VM3CCA 3.5 Inch LCD Screen 240x320
  • Siemens 545 555 1105 1106 PLC Controller
  • H2-ECOM100 PLC Communication Module Ethernet
  • B&R X20CS1012 PLC Module X20 CS 1012
  • Siemens 6ES7212-1HF40-0XB0 PLC Module 24VDC
  • Omron C120-0C222 IO Module 3G2A6-0C222
  • Electromatic Denmark PLC TYPE 200816 Industrial Controller
  • SANYO PLC-XTC50L Projector 50-60Hz LCD Installation
  • LTi SO84.450 Servo Drive Controller - 450A Three-Phase BG7
  • LTi SO84.375 Servo Drive Controller - 375A Three-Phase BG7
  • LTi SO84.325 Servo Drive Controller - 325A Three-Phase BG7
  • LTi SO84.250 Servo Drive Controller - 250A Three-Phase BG7
  • LTi SO84.170 Servo Drive Controller - 170A Three-Phase BG6a
  • LTi SO84.143 Servo Drive Controller - 143A Three-Phase BG6a
  • LTi SO84.110 Servo Drive Controller - 110A Three-Phase BG6
  • LTi SO84.090 Servo Drive Controller - 90A Three-Phase BG6