Welcome to the Industrial Automation website!

NameDescriptionContent
HONG  KANG
E-mail  
Password  
  
Forgot password?
  Register
当前位置:

Watlow Series 942 Controller

来源: | 作者:FAN | 发布时间 :2025-11-11 | 453 次浏览: | 🔊 Click to read aloud ❚❚ | Share:


Watlow Series 942 Controller

Core features and specifications of the product

core functionality

Control mode: Supports PID or ON/OFF control, can be manually selected; Dual output design, output 1 can be set as heating or cooling, and output 2 can be set as heating, cooling, or off.

Input type: compatible with J, K, T, N, R, S, B, C, Pt2 thermocouples, RTD (2-wire or 3-wire) and 0-5VDC, 4-20mA process inputs.

Programming ability: Supports 24 step program curves, including four step types: set point (StPt), constant temperature (SoAh), jump cycle (JL), and end, and can achieve multi-stage temperature control.

Auxiliary functions: optional dual auxiliary output (alarm or time triggered event), set point/process value retransmission output, supports RS-422A/RS-423A/EIA-485 communication interface.

Data storage: Non volatile memory automatically saves all parameters, and data is not lost after power failure; Lithium battery backup operation parameters, with a service life of about 10 years.

Key specifications

Temperature range: thermocouple (-328 ° F~4200 ° F/-200 ° C~2315 ° C), RTD (-328 ° F~1112 ° F/-200 ° C~600 ° C), process input (-500~3500 units).

Accuracy: ± 0.1% ± 1 LSD of full scale (ambient temperature 77 ° F ± 5 ° F, rated voltage ± 10%).

Output specifications:

Solid state relay output: 0.5A@24-264VAC Optical isolation and zero crossing switching.

Mechanical relay output: 6A@120 /240VAC or 28VDC.

Process output: 0-5VDC/0-10VDC (minimum load 10K Ω), 4-20mA/0-20mA (maximum load 600 Ω).

Working environment: Temperature range of 32 ° F~149 ° F (0 ° C~65 ° C), humidity range of 0~90% (no condensation).


Installation and wiring process

Installation preparation

Panel Hole: Process panel holes according to size requirements (nominal 3.625 × 3.625 inches/92.08 × 92.08mm, thickness 0.06~0.25 inches/1.5~6.35mm).

Equipment fixation: Insert the controller housing into the opening, fix it from the back of the panel with the matching bracket, then insert the control chassis into the housing and lock it by rotating the front plate screw 90 ° clockwise (note that the screw should only be rotated 90 ° to avoid excessive force damage).

Wiring operation

Power wiring

Supports 120VAC or 240VAC power supply (50/60Hz universal, no adjustment required), requires connection to L1 and L2 power terminals and grounding terminals, and wiring must comply with the National Electrical Code (NEC) to avoid the risk of electric shock.

The power supply end needs to be connected in series with a fuse. When powered by 120VAC, the L1 end needs to be connected in series with a fuse. When powered by 240VAC, both the L1 and L2 ends need to be connected in series with a fuse.

Sensor wiring

Thermocouple: Use extension cords made of the same material as the thermocouple to avoid errors; If connecting non isolated external devices, an isolated thermocouple should be selected, with positive and negative terminals corresponding to terminals 7 (+) and 9 (-).

RTD: 2-wire RTD needs to short-circuit terminals 5 and 6, and 3-wire RTD needs to ensure that the resistance of the three extension wires is consistent (with the same wire diameter and material) to compensate for lead resistance errors (every 1 Ω lead resistance of 2-wire RTD will cause an error of about+2 ° C).

Process input: 0-5VDC input is connected to terminals 1 (+) and 3 (-), with an input impedance of 100K Ω; 4-20mA input requires short circuiting terminals 2 and 3, followed by connecting the positive and negative poles of the signal, with an input impedance of 249 Ω.

Output wiring

Output 1/2: Select the wiring method according to the model (solid-state relay, mechanical relay, DC switch, process output, etc.), refer to the wiring diagram of the corresponding model in the manual for details, and ensure that the load impedance matches (such as process output 4-20mA maximum load 600 Ω).

Auxiliary output: 6 auxiliary options are available (single relay, dual relay, relay+retransmission, etc.), wired according to the corresponding terminals (24-27) of the model, and the alarm/event output is a mechanical relay( 6A@28VDC /120VAC)。

Wiring precautions

Separation of strong and weak electricity: The sensor signal line (low power) is wired separately from the power line and output line (high power), with a minimum spacing of 12 inches (305mm) to avoid cross interference; When crossing, use a 90 ° crossing.

Shielding and grounding: Shielded cables are used for low-level signal lines, and the shielding layer is only grounded at the controller end; The system is grounded at a single point to avoid grounding loops, and all grounding terminals are connected to a unified grounding body.

image.png

Parameter Configuration Guide

Enter the configuration menu

Press the UP and DOWN keys simultaneously for 3 seconds to enter the Setup menu (displaying LOC parameters); Continue holding down the UP and DOWN keys under the LOC parameter to enter the calibration menu.

During the configuration process, press the MODE key to switch parameters, use the UP/DOWN key to adjust values, and if there is no operation for 5 seconds, it will automatically save and return to the previous level, or press the MODE key to manually save and switch.

Key configuration parameters (Setup menu)

Parameter Category Core Parameter Function Description Default Values

Security and Permission LOC Operation Permission Lock (Level 0-3): Level 0 Full Permission, Level 3 Only View Setpoint/Process Values 0

Input configuration In Select input type (such as J, K, RTD, 4-20, etc.) J or r

Temperature unit (° F/° C), only displays F when input as thermocouple/RTD

The upper and lower limits of the range for the rL/rH set point/process input, as well as the default range for scaling and retransmitting the output range of the sensor

Output configuration Ot1/Ot2 output 1/2 action type (ht heating/CL cooling/no off) ht/CL

HYS1/HYS2 output 1/2 ON/OFF switching hysteresis (effective when Pb=0) 3 ° F

Alarm and event Ot3/Ot4 auxiliary output 3/4 function (AL alarm/Ent event/PrOC retransmission) AL/PrOC

AL1/AL2 alarm type (Pr process alarm/DE deviation alarm) Pr

Programming configuration PtYP program type (ti time basis/ratE ramp rate basis) ti

GSD constant temperature deviation window (program pauses when out of range) 0 (disabled)

Power outage recovery Pout program recovery method after power outage (Cont continue/HOLD hold/Abrt abort) Cont

Communication configuration: bAUD baud rate (300-9600), only models with communication function display 1200

Addr device address (0-31), only displaying 0 under FULL protocol

Operation menu parameters (Operation menu)

Setpoint (SP): Adjust the control target value within the range of rL~rH, and display OFF (disable all outputs) when it is lower than rL.

PID parameters (Pb1/Pr2, rE1/rE2, rA1/rA2): proportional band, reset/integral, rate/derivative, automatically generated after automatic tuning, or manually adjustable.

Automatic tuning (Aut): Only output 1 for heating display, select tuning rate (1 slow/2/3 fast), and the controller automatically optimizes PID parameters after startup.

Alarm setting (A1LO/A1HI, A2LO/A2HI): Process alarm setting upper and lower limits (Pr type) or deviation alarm offset (dE type).


Program Programming and Running

Fundamentals of Programming

Program structure: Up to 24 steps, each step can be selected from four types: StPt (Setpoint Slope), SoAh (Constant Temperature Holding), JL (Jump Loop), and End (Program End), supporting multiple program concatenation (a new program can start after one End step).

Programming entrance: Select Prog=YES from the Operation menu to enter the Program menu. Press the StEP parameter to select steps (1-24), and press StYP to select the step type.

Detailed explanation of four step programming methods

1. Set point step (StPt)

Core parameters:

SP: Target Set Point (rL~rH).

Time basis (PtYP=ti): HOUr/Min/SEC, total time is the sum of the three (0-23h59m59s).

Rate basis (PtYP=rAtE): rAtE, temperature change rate (0-360 ° F/min or 0-200 ° C/min).

Ent1/Ent2: On/Off status of event 1/2, displayed only when Ot3/Ot4 is set to Ent.

Example: Step 1 is set to StPt, SP=75 ° F, Min=0, SEC=1, Ent1=OFF, achieving the initial setting of reaching 75 ° F within 1 second.

2. Constant temperature step (SoAh)

Core parameters: HOUr/Min/SEC (constant temperature duration), Ent1/Ent2 (event switch), no SP parameter (inherited from the previous set point).

Example: Set Step 3 to SoAh, Min=0, SEC=25, Ent1=On, achieve 25 seconds of constant temperature and trigger Event 1.

3. Jump loop step (JL)

Core parameters:

JS: Jump to the target step (must be smaller than the current step, cannot jump to itself).

JC: Jump count (0=infinite loop, 1-100=finite loop).

Example: Set Step 6 to JL, JS=2, JC=1, implement a jump to Step 2 and repeat once (execute Steps 2-5 twice in total).

4. End step

Core parameters: End (HOLD remains in the last state/OFF closes all outputs/OFFA closes control outputs, retains alarms).

Example: Step 4 is set to End, End=OFF. After the program ends, all outputs are turned off, and 'lower' displays' OFF '.

Program Execution and Control

Start program: In the non Setup menu interface, press the HOLD/RUN button, the RUN LED flashes, select the Start Step (StP), then press the HOLD/RUN button to confirm, the RUN LED stays on, and the program starts.

Pause and Resume: Press the HOLD/RUN button once to pause (RUN LED flashes); Press the HOLD/RUN key again to switch to the rESU parameter, and press the HOLD/RUN key to resume operation (only when the program has not been modified).

View operating status: Press the MODE key to switch parameters in the RUN menu, where you can view remaining time (HOUr/Min/SEC), current rate (rAtE), event status (Ent1/Ent2), etc.

Programming Example (Slope Constant Temperature Cycle)

Requirement: Initial temperature of 75 ° F → 25 seconds to rise to 100 ° F (event 1 activated) → 25 seconds constant temperature → 25 seconds to rise to 125 ° F (event 2 activated) → 25 seconds constant temperature → jump to step 1 and repeat twice → maintain the final state.

Step by step SP (° F) Time (minutes: seconds) Ent1 Ent2 JS JC End

1 StPt 75 0:01 OFF OFF - - -

2 StPt 100 0:25 ON OFF - - -

3 SoAh - 0:25 ON OFF - - -

4 StPt 125 0:25 OFF ON - - -

5 SoAh - 0:25 ON OFF - - -

6 JL - - - - 1 2 -

7 End - - - - - - HOLd

image.png

Tuning operation (automatic and manual)

Automatic tuning (recommended)

Applicable scenario: Quickly obtain optimized PID parameters after first use and system load changes.

Operation steps:

Enter the Operation menu and find the Aut parameter (displayed only when Ot1=ht).

Press the UP/DOWN keys to select the tuning rate (1 slow/2/3 fast, mostly 2 in most scenarios).

Press the MODE key to start tuning, and the lower display alternately flashes Aut and the current parameter. During tuning, the cooling output is turned off, and the heating output runs at 90% set point ON/OFF.

Complete tuning within 80 minutes, automatically save PID parameters, restore Aut to 0, and return to normal control mode; Modifying the set point during tuning will restart tuning. Press the UP/DOWN key to set Aut=0 to abort (restore the original parameters).

Manual tuning (precise optimization)

Operation steps:

Initialization parameters: Pb1=1, Ct1=5, rE1=rA1=0, CAL=0, Aut=0, set target temperature.

Proportional band (Pb1) adjustment: gradually increase Pb1 until the process temperature stabilizes (initial reset to 0, temperature may deviate from the set point).

Reset/Integral (rE1) Adjustment: Gradually increase rE1 until the temperature begins to oscillate, then slowly decrease until the temperature stabilizes near the set point.

Rate/Differential (rA1) Adjustment: Assuming rA1=1.00 minutes, raise the set point by 20-30 ° F. If the temperature is overshoot, increase rA1 (maximum 9.99) to avoid overshoot and slow response.

Cycle time (Ct1) adjustment: Optimized within the range of 1-60 seconds. It is recommended to choose a longer cycle time for mechanical contactors (to reduce wear) and a shorter time for electronic loads (to improve control accuracy).


Alarm and fault handling

Alarm function operation

Alarm type:

Process alarm (Pr): Based on the absolute temperature threshold (A1LO/A1HI), an alarm is triggered when the temperature exceeds the range.

Deviation alarm (dE): Based on the set point offset (such as+7 ° F/-5 ° F), the alarm threshold synchronously shifts when the set point changes.

Alarm status:

Non Locked (nLA): Automatically resets after the alarm condition disappears.

Lock (LAt): Manual reset is required (first eliminate the alarm condition, then press the HOLD/RUN button).

Alarm indication: The lower display alternately flashes "LO"/"HI" and the current parameter, the L3/L4 LED lights up, and the auxiliary output triggers (N.O. closed/N.C. open).

Common faults and solutions

Fault symptoms, error codes, possible causes, and solutions

The upper display shows "----", the lower display shows Er7 Er7 A/D overflow, the sensor is open/polarity reversed, check the sensor wiring (positive and negative poles, terminal contact), confirm that the In parameter is consistent with the sensor type

The upper display shows "----", the lower display shows Er1/Er2 Er1/Er2 sensor over/under range, A/D fault confirms that the sensor range matches rL/rH, checks if the sensor is damaged, and recalibrates the A/D

Pause during program operation - gSD deviation window enabled, adjust gSD value if temperature exceeds ± gSD range (increase window), check if heating/cooling system is normal, eliminate load interference

Communication failure - baud rate/protocol/address mismatch, wiring error. Confirm that bAUd (baud rate), Prot (protocol), Addr (address) in the Setup menu are consistent with the host, and check the communication line wiring (RS-485 requires corresponding A/B lines)

Large temperature measurement error - sensor wiring error, calibration offset, environmental interference. Reconnect and confirm sensor type, enter Cal menu to adjust CAL offset, check signal line shielding and grounding

Output unresponsive - Set the set point to OFF, configure the output type incorrectly, adjust the SP to the rL~rH range for load faults, confirm the Ot1/Ot2 parameters (ht/CL), check if the load impedance matches the output type, and test if the load is normal

image.png

Calibration operation (accuracy calibration)

Calibration prerequisite

Only enter under LOC parameters and require precise equipment (such as precision millivolt source, resistance box, voltage/current source, 4.5-inch multimeter).

Backup all parameters (Setup/Operation/Program) before calibration, turn off all outputs during calibration (except for process outputs), and automatically save calibration values when the RUN LED lights up.

Core Calibration Process (Taking Thermocouples as an Example)

Wiring: Connect the precision millivolt source to terminals 7 (+) and 9 (-), connect to AC power and ground.

Preheating: Power on for 15 minutes, enter the Cal menu (hold down the UP/DOWN key under LOC parameters), press the MODE key to select the tCL parameter.

Low range calibration: The millivolt source outputs 0.00mV, and after stabilizing for 10 seconds, press the MODE button.

High range calibration: J-type thermocouple outputs 50.00mV, R/S/B type outputs 16.035mV. After stabilizing for 10 seconds, press the MODE button.

Compensation calibration: Disconnect the millivolt source and connect the J-type reference compensator (32 ° F/0 ° C). After stabilizing for 10 seconds, press the HOLD/RUN button to exit the RUN mode and complete the calibration.

Other calibrations (RTD/process input/output)

RTD calibration: Use a 1K Ω precision resistance box to connect terminals 4-6, and input low/high resistance values according to the rLO/rHI parameters (refer to Table 7 in the manual).

4-20mA input calibration: Short circuit terminals 2-3, output 4.00mA (4A parameter) and 20.00mA (20A parameter) from the current source, and calibrate sequentially.

Process output calibration: Connect a multimeter and a matching resistor (such as 4-20mA connected to a 470 Ω resistor), adjust the output to the target value (such as 4.00mA/20.00mA) according to the O1LO/O1HI parameters.


Maintenance and Precautions

routine maintenance

Regular inspection: Check whether the sensor wiring is loose or corroded, whether the panel screws are tightened, and whether the heat dissipation is good.

Battery replacement: Lithium batteries (with backup operating parameters) have a lifespan of about 10 years. In case of abnormal Pout or Run parameters, they need to be returned to the factory for replacement.

Cleaning and maintenance: Wipe the panel with a dry soft cloth to prevent liquid from seeping into the interior of the equipment; Avoid using in damp, dusty, and corrosive environments.

Safety precautions

Disconnect the power supply before wiring, strictly follow NEC and local electrical regulations, and ensure reliable grounding (to avoid electric shock and interference).

The front plate screws should only be rotated 90 °, and excessive force should be avoided to avoid damaging the chassis locking structure.

Mercury relays are only suitable for resistive loads and are prohibited from being used for inductive loads (such as motors without buffering).

Calibration and maintenance must be carried out by professional personnel, and unauthorized disassembly of the equipment casing is prohibited (which may affect warranty).

image.png

  • ELAU DB-5 Distribution HW 5104 Servo System
  • Touchstar 10K TS10KCC0CEMP Industrial Touch Panel
  • Beckhoff CX2030-0125 Embedded PC PLC
  • Parker Hannifin HID5CS/S4 HIDRIVE 5A Servo Drive
  • Yaskawa ACE-P300-TH5 Servo Drive with Profibus
  • Omron Sysmac SCY-P0 13E Sequencer Controller
  • Saia Burgess PCD4.M120 PCD4.M12 Central Controller
  • Schneider Electric TSX3722101 Modicon Micro PLC
  • Siemens Micromaster 440 6SE6440-2AD25-5CA1 Inverter
  • SICK DL50-P1123 Distance Sensor
  • Yaskawa SGDH-04AE-OY Servo Driver 200V 400W
  • Cincinnati Milacron 3-542-1203A Circuit Board Module
  • Allen-Bradley 1756-EN2T EtherNet/IP Communication Module
  • OMRON CS1H-CPU66-V1 Programmable Logic Controller
  • ABB SACE TMAX S6N 630 Molded Case Circuit Breaker
  • Weidmuller IE-SW-VL16-16TX 16-Port Ethernet Switch
  • Schneider PowerLogic CM4250 Circuit Monitor
  • Sacmi IDPM IDMP1.A SMC 085.16.982 Control
  • Omron C120-LK202-EV1 Host Link Unit
  • Omron FQ2-S15050F Smart Camera Vision System
  • OMRON CJ1G-CPU44H Programmable Logic Controller
  • SIEMENS KTP600 HMI 6AV6 647-0AD11-3AX0 Touch Panel
  • OMRON CS1G-CPU45H EV1 Programmable Logic Controller
  • Omron C200HG PLC System C200H-ID212 C200H-OC226
  • ROBOSYSTEM IOG4AX-HD-100 IOG-HD Motion Controller
  • Datalogic SG4-S3-080-PP-W Safety Light Curtain
  • Omron NS12-TS01B-V2 Interactive Display
  • Esto Electronic E.CGT-405-42TE PLC Rack
  • Siemens 7ED62 Static Three Phase Counter
  • Oemer QCAVS 100 LBE AC Square Frame Servo Motor
  • Schneider Electric TM262M25MESS8T Motion Controller
  • Eaton Moeller MFD-CP8-ME Power Supply
  • Pro-face PL-5700T1-24VDC Industrial Panel PC
  • GE Fanuc IC693APU300J High Speed Counter
  • Fuji Electric Micrex-F FPU080S PLC Module
  • Automation Direct GS2-45P0 AC Drive
  • Omron 3G3MV-C4015 V1000 Inverter
  • Vacon NXI01055A2T0CSS Industrial Inverter
  • Saia Burgess PCD4.M240 Central Controller Module
  • Yaskawa SGDH-10DE Sigma II Servo Drive
  • Stober EK501USOM140 Servo Motor and Drive
  • SCE M68-2000/4 CNC Controller and I/O Board
  • Omron SP10-PR001-V1 PLC Programming Console Specs
  • VACON NXI01055A2T0CSSA Industrial AC Drive
  • OMRON SYSMAC SCY-P1 Sequencer Controller PLC
  • SEL-2440 DPAC Discrete Programmable Controller
  • BIVIATOR CI3098 CPU Encoder Module Industrial Control Unit
  • Siemens 6FC5371-0AA10-0AA2 SINUMERIK NCU 710.2
  • KOLLMORGEN SERVOSTAR S70601-NA High Performance Servo Drive
  • OMRON C200HW-PCU01 Fastnet PCMCIA LAN Communication Unit
  • ibaFOB-2io-D Two-Channel Fiber Optic Input Output Card
  • ibaFOB-4io-D Four-Channel Fiber Optic Input Output Card
  • ibaFOB-io-S Single-Channel Fiber Optic Input Output Card
  • ibaFOB-4io-S Four-Channel Fiber Optic Input Output Card
  • ibaFOB-4o Four-Channel Fiber Optic Output Interface Card
  • ibaFOB-4i-S Enhanced Four-Channel Fiber Optic Input Card
  • ibaFOB-4i Four-Channel Fiber Optic Input Interface Card
  • ibaFOB-io Fiber Optic Interface Card for iba Systems
  • SM128V VMEbus Interface Card for Industrial Data Acquisition
  • ibaLink-SM-128V-i-2o VMEbus Fiber Optic Interface Board
  • GE Fanuc IC693MDL632 125V DC Input Module 8 Points
  • GE Fanuc IC693MDL241 24V AC/VDC Input Module 16 Points
  • GE Fanuc IC693MDL240 120V AC Input Module 16 Points
  • GE Fanuc IC693MDL231 240V AC Isolated Input Module
  • GE Fanuc IC693MDL230 120V AC Isolated Input Module
  • GE Fanuc IC693MDL654 5/12 VDC 32-Point Input Module
  • GE Fanuc IC693MDL653 24 VDC 32-Point Input Module
  • GE Fanuc IC693MDL648 48 VDC 16-Point Input Module
  • GE Fanuc IC693MDL646 24 VDC 16-Point Input Module
  • GE Fanuc IC693MDL634 24 VDC Input Module 8 Points
  • GE IM 3100 D 1007722 Control Module
  • GE IM0146B Industrial Circuit Board
  • GE IM0059E0-10070 Interface Board
  • GE IM0094C Industrial Control Board
  • GE IC200PNS002-AB VersaMax PROFINET Scanner
  • GE F650BFBF1G0HI Feeder Protection Relay
  • GE TPR5616NRHC Protection Relay
  • GE D6P3KH Digital Protection Relay
  • GE F650BABF2G0HIS Feeder Protection Relay
  • GE F650BADF2G1HIR Feeder Protection Relay
  • GE F650BABF2G1HI6 Digital Bay Controller
  • GE Multilin 745-W2-P1-G1-H-I-A-R-E Transformer Protection Relay
  • GE 100BASE-T Industrial Ethernet Interface
  • GE Multilin 350-E-P1-S1-H-S-E-C-N-2E-D-H Feeder Protection System
  • GE F650MXCF1G1HI6 Bay Controller
  • GE MM300-GEHD2CAB Motor Management Relay
  • GE MMS35-621-1-00 Motor Management System
  • GE 100BASE-T Ethernet Communication Module
  • GE F650MFCF1G1HI6 Feeder Protection Relay
  • GE CK13BA300 Control Module
  • GE W2-P1-G1-H Industrial Control Unit
  • GE PIB315B Power Interface Board
  • GE 343L695VAGIRHC Multi-Function Relay
  • GE Multilin B90N05HKHF8NH6 Bus Differential Protection
  • GE ZX3SC0204N-930 Intelligent Control Module
  • GE PIB504 Process Interface Board
  • GE D20MX Remote Terminal Unit
  • GE T60UJ3HKHF8NH6 Transformer Protection Relay
  • GE ZG3SA02041-58S600X Motor Protection Relay
  • GE ZG3SA02041-58S Motor Protection Relay
  • ABB DSDX 452 L Remote Input Output Module
  • ABB RDCU-02C Drive Control Unit
  • ABB COMMANDER 350 Process Controller
  • ABB Tmax XT4S 250 Molded Case Circuit Breaker
  • DEIF MALLING 8027.90 Industrial Control Unit
  • DEIF DCP2-2410 Power Supply Module
  • DEIF FAS-2N Synchronizer
  • DEIF MALLING 827.54 Processor Module
  • DEIF DU-2/MKIII Display Unit
  • DEIF DRW-2 Reverse Power Relay
  • DEIF 827.4 Power Management Module
  • DEIF 1044220060F Mains Measurement Module
  • DEIF 1044220190G Remote Display Module
  • DEIF 1044220140C AGC 200 Display Module
  • DEIF BRW-1-NB Remote Display Unit
  • DEIF MALLING 827.52 Industrial Control Unit for Automation Systems
  • DEIF BRW-2 Industrial Relay Module for Control Systems
  • DEIF 1044220080D Power System Control Module Industrial Automation
  • DEIF 1044220100F Controller Module for Generator Control Systems
  • DEIF DU-300 Voltage Monitoring Relay Industrial Protection Unit
  • DEIF 1044220060F I/O Extension Module
  • DEIF 1044220150C Interface Module
  • DEIF GCU 100 Engine Control Unit
  • DEIF XDI144-DUAL Marine Indicator
  • DEIF 827.41 Multi-line 2 Processor Module
  • DEIF AGC 146 Automatic Genset Controller
  • DEIF 1044220080E MDR-2 Display Module
  • DEIF MDR-2 Multifunctional Digital Relay