Welcome to the Industrial Automation website!

NameDescriptionContent
HONG  KANG
E-mail  
Password  
  
Forgot password?
  Register
当前位置:

Watlow Series 965 Controller

来源: | 作者:FAN | 发布时间 :2025-11-10 | 290 次浏览: | Share:

Watlow Series 965 Controller

Product basic information and specifications

(1) Product positioning and certification

The Watlow Series 965 is a 1/16 DIN microprocessor based controller designed for precise industrial temperature control, suitable for plastic molding, food processing, electronic manufacturing, and other scenarios. It can achieve bidirectional heating/cooling control and process monitoring. The product has been certified by UL (file number E43684, compliant with UL873 standard) and CE (compliant with 89/336/EEC electromagnetic compatibility directive, 73/23/EEC low voltage directive), with NEMA 4X (IP65) protection level. The front panel adopts a sealing film design, which can prevent dust and water splashes and adapt to harsh industrial environments.

(2) Core specification parameters

Category detailed specifications

Input characteristics - Thermocouples: J-type (0-750 ° C), K-type (-200-1250 ° C), T-type (-200-350 ° C), N-type (0-1250 ° C), S-type (0-1450 ° C)

-RTD: 2/3 wire system, 100 Ω (at 0 ° C), supports DIN (0.00385 Ω/Ω/° C), JIS (0.003916 Ω/Ω/° C) curves, range -200-700 ° C (1 ° resolution), -128.8-537.7 ° C (0.1 ° resolution)

-Process signal: 0-5V DC (input impedance 10k Ω), 4-20mA DC (input impedance 5 Ω), range -999-9999 units

Output Characteristics - Output 1 (Heating/Cooling): Mechanical Relay (Form C, 5A@120 /240V AC、 5A@30V  DC)、 Solid state relay (Form A, 0.5A@24-264V  AC)、 Switching DC (3-12V DC, minimum 500 Ω load), 4-20mA DC (maximum 800 Ω load)

-Output 2 (Heating/Cooling/Alarm): Same as Output 1 type, alarm mode supports process/deviation alarm, can be configured with locking/non locking

Control Performance - Control Modes: PID, P, PI, PD, Switch Control

-Sampling rate: 2.5Hz, display update rate: 1Hz

-Calibration accuracy: ± 0.1% range ± 1 least significant position (@ 25 ± 3 ° C environment, rated voltage)

-Temperature stability: ± 0.2 ° C/° C ambient temperature variation

-Slope function: 0-9999 °/hour, supports starting temperature rise and setting value change temperature rise

Power and Environment - Power Supply: High Voltage Type (100-240V AC, 85-264V AC actual, 50/60Hz), Low Voltage Type (12-24V AC/DC, 10-26V AC/DC actual, 50/60Hz)

-Power consumption: maximum 5VA

-Working environment: 0-65 ° C, 0-90% RH (no condensation)

-Storage environment: -40-85 ° C


Installation and Wiring Guide

(1) Installation preparation and steps

The panel cut and size need to be processed according to the specifications, with a size of 55mm × 55mm (± 0.5mm). The panel thickness should be between 1.5-9.7mm, and the surface roughness should not exceed 0.000812mm to ensure NEMA 4X sealing effect. Recommend using Greenlee punch (# 60020) and mold (# 60021) for incision processing to improve installation efficiency.

Installation Process

Disassemble the controller chassis: Hold down the buckles on both sides of the panel with both hands, apply force outward until the chassis is detached from the housing, and place it separately for future use.

Place the shell: Confirm that the sealing ring of the shell (rounded side facing the panel) is not twisted, insert the shell into the panel cut, and ensure that the sealing ring fits the surface of the panel.

Fixed installation ring: Insert the installation ring from the back of the chassis, align it with the installation ridge on the housing, and push the installation ring firmly until the buckle is fastened, ensuring that the housing is not loose (the sealing can be checked by pressing both sides of the panel).

Reinstall the chassis: Insert the chassis into the housing, press the panel until the buckle is reset, and confirm that the internal sealing ring is not offset.

(2) Wiring specifications and examples

Power wiring

High voltage type (model 965A-30-00): L1 (live wire) is connected to terminal 11, L2 (neutral wire) is connected to terminal 12, and a 1A/250V slow melting fuse (pre installed at the factory and cannot be replaced by oneself) needs to be connected in series.

Low voltage type (model 965A-31-00): L1 (positive) connected to terminal 11, L2 (negative) connected to terminal 12, connected in series with 2A/250V slow melting fuse. Warning: Connecting high voltage to low voltage models can cause irreversible damage.

Input wiring

Thermocouple: Taking J-type as an example, the positive terminal is connected to terminal 3, and the negative terminal is connected to terminal 5. The extension wire should be made of the same material as the thermocouple (such as iron constantan alloy wire for J-type) to avoid temperature deviation at the joint affecting the measurement.

3-wire RTD: Terminal 2 is connected to one lead, Terminal 3 is connected to one lead, and Terminal 5 is connected to the third lead. The three leads must be of the same specification (such as 22AWG copper wire, with the same length) to compensate for lead resistance errors.

4-20mA process signal: Connect the positive terminal to terminal 5 and the negative terminal to terminal 2. The signal source should be grounded together with the controller to avoid introducing noise into the grounding loop.

Output wiring

Mechanical relay (output 1, model 965A-3D-00): Terminal 10 is connected to the common terminal (COM), terminal 1 is connected to the normally closed (NC), and the terminal is not labeled as normally open (NO). When controlling inductive loads (such as relay coils), an RC suppressor (Watlow part number 0804-0147-0000) needs to be connected in parallel.

4-20mA process output (output 1, model 965A-3F-00): terminal 9 is connected to the positive pole, terminal 10 is connected to the negative pole, and the maximum load is 800 Ω. It can be used to drive valves, recorders, and other equipment.

Typical heating control system wiring example: Controller terminals 11/12 are connected to a 120V AC power supply, terminals 3/5 are connected to a J-type thermocouple, terminals 10/1 are connected to a solid-state relay (SSR) control terminal, and the SSR output terminal is connected to a heater and a 240V AC power supply. At the same time, a Series 92 limit controller (terminals 13/14) is connected in series to achieve over temperature protection, and terminal 7 is connected to an alarm light (which lights up when a high temperature alarm is triggered).

image.png

Operation interface and menu configuration

(1) Button and display functions

Key definition

MODE key: Switch operation menu parameters. In automatic mode, if there is no operation for 5 seconds, the parameter change will be automatically confirmed.

Up and down arrow keys: Adjust parameter values (short press to increase or decrease by 1, long press to quickly increase or decrease), while long press for 3 seconds to enter the settings menu, continue long press to enter the calibration menu.

A/M key: Short press to clear the lock alarm, press twice continuously within 2 seconds to switch between automatic/manual mode. In manual mode, the lower screen displays the output power (-100% to 100%).

Display screen and indicator lights

Upper screen: Red/green 4-digit LED, displaying process value (PV), parameter value or error code (such as "----" indicating sensor failure).

Lower screen: red/green 4-digit LED, displaying set value (SP), parameter name (such as "LOC" "Pb1"), alarm information ("LO" "HI") or error code (such as "Er7").

Indicator lights: L1 (red) on indicates output 1 activation, L2 (red) on indicates output 2 activation, MN (green) on indicates manual mode, flashing indicates pending mode switch.

(2) Core menu configuration

1. Setup Menu

Entry method: Simultaneously press and hold the up and down arrow keys for 3 seconds, the lower screen will display "LOC", and the upper screen will display the current lock level. The main parameters are as follows:

Parameter Function Range Default Values Precautions

LOC operation permission lock 0-4 0 level: full permission; Level 4: Only view PV/SP, non adjustable

In the input type selection J/K/t/n/S/rtd/rt.d/0-5/420 J, it needs to be consistent with the internal DIP switch (DIP switch is located on the left side of the chassis, view from the bottom)

Temperature unit C/F F (US mode)/C (SI mode) displayed only when input as thermocouple/RTD

The upper and lower limits of the rL/rH range, where rL<rH, depend on the input type. When the input type defaults to the range process signal, rL corresponds to 0V/4mA, and rH corresponds to 5V/20mA

Ot1 output 1 function ht (heating)/CL (cooling) ht heating is the reactive effect (output activated when PV<SP), cooling is the positive effect

Ot2 output 2 function Con/PrA/Pr/dEA/dE/no Con Con: opposite function to output 1; PrA: with display process alarm

HSC switch control hysteresis of 1-99/0.1-9.9/0.01-0.99 3 (° F)/2 (° C) takes effect when Pb1=0, avoiding frequent output switching

RP slope function Str/On/OFF Str: only heats up during startup; On: Setting value changes also increase temperature

Display when rt slope rate 0-9999 100 (°/hour) rP ≠ OFF

2. Operation Menu

Entry method: Press the MODE key to switch, the main parameters are as follows:

Parameter Function Range Default Values Precautions

SP control set value rL-RH 75 (° F)/24 (° C) displays the target set value in ramp mode, and the actual value gradually approaches

Pb1/Pb2 ratio with 0-999 (° F/° C/unit)/0-0999.9% (span) 25 (° F)/3% (span) Pb1=0 is switch controlled, Pb2 is only displayed when Ot2=Con

RE1/It1 integral (reset) rE1: 0.00-99.9 (times/minute); It1: 0.0-99.9 (minutes/time) 0.00 Eliminate static deviation between PV and SP, excessive deviation can easily lead to oscillation

RA1/dE1 differential (rate) 0.00-9.99 (minutes) 0.00 suppresses overshoot, which can lead to slow response if it is too large

Ct1/Ct2 cycle time 0.1-999.9 (seconds) 5.0 Mechanical relays are recommended to last for 5-60 seconds, while solid-state relays can last for 0.1-5 seconds

ALO/AHI alarm upper and lower limits ALO < AHI, according to the alarm type, the deviation alarm of -999/999 is the offset relative to SP (e.g.+5 represents SP+5)

AUt self-tuning 0 (off)/1 (slow)/2 (medium)/3 (fast) 0. After starting, the Lower screen alternately displays "At", and automatically resets to 0 after completion

3. Calibration Menu

Entry method: Starting from the LOC parameter in the settings menu, continue to press and hold the up and down arrow keys simultaneously. The lower screen will display "CAL" and the upper screen will display "no". Press the up arrow key to change to "YES" and then press the MODE key to enter. Main functions:

Input calibration: For two-point calibration of thermocouples (input 0.00mV, 50.00mV), RTDs (input 44.01 Ω, 255.42 Ω), and process signals (0.000V/4.00mA, 5.000V/20.00mA), a precision signal source is required.

Output calibration: 4-20mA output calibration, adjust the output values of 4mA (target 3.85 ± 0.10mA) and 20mA (target 20.15 ± 0.10mA).

Factory calibration restoration: restored through the "rSt" parameter. It can be used in case of calibration errors, but the parameters need to be reconfigured after restoration.


Control functions and operating procedures

(1) PID control and self-tuning

Self tuning operation steps

Confirm that the input/output configuration is correct, set the target SP (recommended within the common operating range), and set the HSC parameter to 3 ° F/2 ° C (to avoid interference with self-tuning).

Press the MODE key until the lower screen displays "AUt" and the upper screen displays "0".

Press the up arrow key to select the response mode (1=slow/2=medium/3=fast, recommended 2), press the MODE key to start self-tuning, and the Lower screen alternately displays "At" and the current parameter.

Self tuning process: The controller sets the output 1 proportional band to 0 and drives the PV to approach 90% SP through switch control. After completing 4 temperature crossings (PV crossing 90% SP), the PID parameters are automatically calculated and saved, and AUt is reset to 0.

Abort self-tuning: Set AUt to 0, press the A/M key twice, or turn off the power to restore the parameters before self-tuning.

Manual tuning steps

Initial parameter settings: Pb1=1 (° F/° C/unit) or 1% (span), rE1/It1=0.00, rA1/dE1=0.00, Ct1=5.0 seconds, AUt=0。

Proportional band adjustment: Gradually increase Pb1 until PV stabilizes (without significant fluctuations), at which point PV may deviate from SP (static deviation).

Integral adjustment: Gradually increase rE1 (or decrease It1), observe the speed at which PV approaches SP. If oscillation occurs, decrease rE1 (or increase It1) until PV stabilizes near SP.

Differential adjustment: Set rA1/dE1 to 1.00 minute, increase SP by 20-30 ° F (11-17 ° C), increase differential if PV overshoot, and decrease differential if response is slow.

Cycle time adjustment: Mechanical relays are recommended to take 10-60 seconds (to reduce contact wear), while solid-state relays can take 1-5 seconds (to improve control accuracy).

(2) Alarm function operation

Alarm configuration steps

Set Ot2 in the settings menu: If a deviation alarm with display is required, set it to "dEA"; If a process alarm is required, set it to "PrA".

Set HSA (Alarm Lag): It is recommended to use 3 ° F/2 ° C to avoid frequent alarms caused by temperature fluctuations.

Set LAt (lock mode): "LAt" is locked (needs to be manually cleared), "nLA" is non locked (automatically cleared when the alarm condition disappears).

Set ALO/AHI in the operation menu: When a deviation alarm is triggered, set ALO to negative offset (e.g. -5) and AHI to positive offset (e.g.+5); When a process alarm occurs, set it to an absolute temperature value (such as 50 ° F, 200 ° F).

Alarm response and clearing

Alarm triggered: When Ot2=PrA/dEA, the Lower screen alternately flashes "LO"/"HI" with the current parameter, the L2 light is on, and the alarm output is de energized (normally open end disconnected, normally closed end closed).

Non locking alarm: When the PV returns to the ALO/AHI range, the alarm will automatically clear and the L2 light will turn off.

Lockout alarm: After the PV returns to the safe range, press the A/M key once to clear it, and the L2 light will turn off.

Alarm mute (only supported by dEA/dE): Set SIL="On" in the menu, press the A/M key once to disable the alarm output when powered on, and restore the PV after it returns to the safe range.

(3) Automatic/manual mode switching

Mode switching operation

Auto → Manual: Press the A/M key twice, the MN light will turn on, and the Lower screen will display the current output power (inheriting the power value in automatic mode, switching without disturbance). The power can be adjusted by pressing the up and down arrow keys (-100% to 100%).

Manual → Automatic: Press the A/M key twice, the MN light will turn off, the controller will restore PID control, and adjust the output based on the current PV and SP.

Sensor fault handling

LOC=0/1/2: When the sensor is open/short circuited, it automatically switches to manual mode. If the power is stable before the fault (± 5% for 2 minutes and<75%), maintain the power before the fault; Otherwise, output 0%.

LOC=3/4: When the sensor fails, the output is turned off, only an error code is displayed, and the buttons are disabled (only the up and down arrow keys can enter the settings menu).

image.png

Troubleshooting and Maintenance

(1) Handling common error codes

Steps for handling error code reasons

Er2 RTD input under range (< -200 ° C) or A/D circuit fault 1. Check if the RTD wiring is loose or broken; 2. Measure the RTD resistance with a multimeter (100 Ω at 0 ° C, 109.73 Ω at 25 ° C); 3. Confirm that both the In parameter and DIP switch are set to "rtd/rt.d"; 4. If the error persists, contact after-sales service

Er4 microprocessor configuration error: 1. Power off and restart after 30 seconds; If it repeatedly occurs, record the controller model (12 digits, located on the chassis side label), and contact Watlow technical support (phone+1 (507) 454-5300)

Er5 non-volatile memory verification error: 1. Power off and restart after 30 seconds to eliminate transient interference; 2. Enter the calibration menu and execute "rSt" to restore factory calibration; 3. If it is invalid, it is necessary to return to the factory to replace the memory

Er6 A/D conversion undercurrent (input voltage too low) 1. Check sensor wiring: thermocouple confirms polarity, RTD confirms lead resistance, process signal confirms signal source; 2. After replacing the sensor, press the MODE key to clear the error; 3. Confirm that the In parameter matches the input type

Er7 A/D conversion overflow (input voltage too high) 1. Check if the sensor is open circuit or polarity reversed (thermocouple); 2. Confirm whether the process signal exceeds the range (such as 4-20mA signal exceeding 20mA); 3. Confirm that the DIP switch is consistent with the In parameter

(2) Daily maintenance and noise suppression

Regular maintenance project

Monthly: Check whether the wiring terminals are loose (especially in vibration environments), whether the panel sealing ring is aging (NEMA 4X protection), and whether the sensor probe is scaled (affecting temperature measurement accuracy).

Quarterly: Clean the panel (using a soft cloth dipped in neutral cleaner), check the mechanical relay contacts (replace if there is erosion), calibrate the input accuracy (using a precision temperature source or signal source).

Every year: Conduct a comprehensive calibration of input/output, check power fuses (factory replaceable only), and evaluate the lifespan of output relays (mechanical relays are recommended to be replaced after 100000 cycles).

Noise suppression measures

Wiring: The distance between the input signal line (sensor line) and the power line and output line should be ≥ 305mm, and they should intersect at a 90 ° angle to avoid parallel wiring; Use shielded twisted pair cables (the shielding layer is only grounded at the controller end).

Load handling: Inductive loads (relay coils, solenoid valves) need to be connected in parallel with RC suppressors (Watlow 0804-0147-0000) to avoid electromagnetic interference during switching.

Grounding: Controller chassis grounding (through panel grounding), signal source and controller are grounded together to avoid grounding loops; An EMI filter can be installed on the power end (optional).

image.png

  • Alstom CPRM1 SINGLE-PHASE POWER REGULATION BOARD
  • Alstom ESVI1 INPUT/OUTPUT BOARD FOR CURRENT AND VOLTAGE SIGNALS
  • Alstom RDSP1 BOARD FOR ADJUSTING DIGITAL SIGNAL PROCESSES
  • Alstom MDEX1 microprocessor control board
  • Alstom IRVI20 - REGULATION INTERFACE BOARD
  • Alstom AMS42 POWER SUPPLY BOARD
  • ABB VACUUM CONTACTOR VSC7 SCO IEC 60470 400A 3POLE 220-250V 50/60Hz
  • ABB DRIVEMONITOR VERSION 4000 DRIVE MODULE RBOX316-ABB-00
  • YASKAWA JACP-317802 AC servo drive
  • YASKAWA JACP-317801 Advanced Process Controller
  • YASKAWA JACP-317120 Power Supply Unit
  • YASKAWA CP-9200SH/SVA servo controller
  • YASKAWA CP-9200SH/CPU Programmable Controller
  • YASKAWA CP-317/DO-01 Digital Output Module
  • YASKAWA CP-317/218IF high-speed communication interface module
  • YASKAWA CP-317/217 IF Communication Interface Module
  • YASKAWA CIMR-M5D2018 High Performance Inverter
  • YASKAWA CACR-HR10BB servo drive
  • YASKAWA 218IF machine controller
  • YOKOGAWA YS1700-100/A06/A31 Programmable Indicator Controller
  • YOKOGAWA KS9-5 * A signal cable
  • YOKOGAWA KS8-5 * A signal cable
  • YOKOGAWA KS2-5 * A DSC signal cable
  • YOKOGAWA PW482-10 power module
  • YOKOGAWA SCP451-11 processor module
  • YOKOGAWA SR1030B62-3MN * 1C High Frequency Signal Processor
  • YOKOGAWA SR1030B62 Analog Input Module
  • YOKOGAWA CP451-10 processor module
  • YOKOGAWA CP451-50 processor module
  • YOKOGAWA AAI143-H50 Analog Input Module
  • YOKOGAWA 22.5 × 17.4 × 10 Compact Industrial Control Module
  • YOKOGAWA AMM42 multiplexer input module
  • YOKOGAWA SDV144-S63 Digital Input Module
  • YOKOGAWA AIP830-111 single player keyboard
  • YOKOGAWA S9361DH-00 Terminal Board Module
  • YOKOGAWA ATK4A-00 S1 KS Cable Interface Adapter
  • YOKOGAWA PW701 power module
  • YOKOGAWA AVR10D-A22010 Duplex V-net Router
  • YOKOGAWA PW441-10 power module
  • YOKOGAWA VI451-10 Communication Interface Module
  • YOKOGAWA VC401-10 Coupling Module
  • YOKOGAWA ALP121 Communication Module
  • YOKOGAWA NFAI841-S00 Analog Input Module
  • YOKOGAWA AIP591 Process Control Module
  • YOKOGAWA AIP578 optical link transceiver
  • YOKOGAWA PW501 power module
  • YOKOGAWA YNT511D fiber optic bus repeater
  • YOKOGAWA AIP171 transceiver control module
  • YOKOGAWA VI702 Vnet/IP Interface Card
  • YOKOGAWA 2302-32-VLE-2 electronic mixer
  • YOKOGAWA ATK4A-00 Cable Interface Adapter
  • YOKOGAWA ALR121-S00 Communication Module
  • YOKOGAWA CP461-50 processor module
  • YOKOGAWA AIP121-S00 Control Module
  • YOKOGAWA UR1800 Recorder
  • YOKOGAWA LC82 * A Industrial Controller
  • YOKOGAWA ANR10D bus node unit
  • YOKOGAWA SDV144-S13 Digital Input Module
  • YOKOGAWA NFAI143-H00 Analog Input Module
  • YOKOGAWA EB501 Bus Interface Module
  • YOKOGAWA CP451-10 Process Control Module
  • YOKOGAWA V0/E1/TCAM/L08 Advanced Process Control Module
  • YOKOGAWA VO/E2/TCDM24/L8 high-precision temperature control module
  • YOKOGAWA 16137-119 high-precision digital input module
  • YOKOGAWA 16114-500 module rack
  • YOKOGAWA PSCDM024DCBAN Key Discrete Module
  • YOKOGAWA 16137-151 Process Control Module
  • YOKOGAWA 16137-188 Process Control Module
  • YOKOGAWA 16137-222 Process Controller
  • YOKOGAWA 16137-223 high-precision temperature transmitter
  • YOKOGAWA 16137-153 Digital Input Module
  • YOKOGAWA 866257000 high-precision temperature controller
  • YOKOGAWA 8596020000 Digital I/O Module
  • YOKOGAWA 866256000 high-precision process control module
  • ABB AFS670 19" Ruggedized Switch AFS670-EREEDDDSSEEEEEEEPZYX05.1.0
  • NI VXIpc-871B Controller
  • YOKOGAWA PSCAMAAN Process Control Analog Input Module
  • YOKOGAWA DR1030B60 servo actuator
  • YOKOGAWA ADV551 Digital Output Module
  • YOKOGAWA AAI543 proposed output module
  • YOKOGAWA LR 4220E Level Transmitter
  • YOKOGAWA SR1008B62 External Wiring Module
  • YOKOGAWA SC200S Control Valve Positioner
  • YOKOGAWA PW301 power module
  • YOKOGAWA NP53 * C Precision Control Module
  • YOKOGAWA F3YD64-1A transistor output module
  • YOKOGAWA F3XD64-3N Industrial Module Controller
  • YOKOGAWA F3WD64-3N High Performance Module Controller
  • YOKOGAWA F3SP21-0N CPU module
  • YOKOGAWA F3PU10-0N AC power module
  • YOKOGAWA F3PU06-0N power module
  • YOKOGAWA F3NC02-0N positioning module
  • YOKOGAWA F3NC01-0N positioning module
  • YOKOGAWA F3LC21-1N Multi Link Module
  • YOKOGAWA F3BU06-0N Base Module
  • FORCE PMC234 control module
  • FORCE CPU-2CE/16 Industrial Control CPU Module
  • Foxboro PBCO-D8-010 FBM I/O cards
  • FOXBORO PBCO-D8-009 Digital Output Module
  • FOXBORO FBM207C RH917GY High Density Contact Induction Input Module
  • FOXBORO AD916AE Digital Control System Module
  • FOXBORO FBM217 discrete input module
  • FOXBORO RH926GH processor module
  • FOXBORO H90 H90C9AA0117S Differential Pressure Transmitter
  • FOXBORO P0926GJ high-precision differential pressure transmitter
  • FOXBORO RH928AW control module
  • FOXBORO N-2AX+DIO signal distribution module
  • FOXBORO RH924WA Fiber Optic Network Adapter
  • FOXBORO P0924JH Control System Module
  • FOXBORO H92 Process Automation System
  • FOXBORO PP0926KN control module
  • FOXBORO P0916FH controller
  • FOXBORO E69F-T-I2-JRS on-site installation signal converter
  • FOXBORO P0926JM Standard 200 Series Baseplates
  • FOXBORO E69F-BI2-S Current Pneumatic Signal Converter
  • FOXBORO P0926GU FBM230 Field Equipment System Integration Module
  • FOXBORO RH931RQ cable terminal
  • FOXBORO H92A049E0700 server module
  • FOXBORO H90C9AA0117S Differential Pressure Transmitter
  • FOXBORO RH101AA High Performance Pressure Transmitter
  • FOXBORO FPS400-24 P0922YU power module
  • FOXBORO P0973LN differential pressure transmitter
  • FOXBORO P0926GV FBM231 Field Equipment System Integration Module
  • Foxboro FBM202 P0926EQ thermocouple/mV input module
  • FOXBORO FBMSVL Safety Valve Logic Solver
  • FOXBORO P0926PA Industrial Control Module
  • FOXBORO L0130AD L0130AE-0H Digital Input Module
  • FOXBORO 0399085B 0303440C+0303458A combination control module