Rate alarm (Tasa) process value change rate exceeds threshold: change per unit time>"Velocidad m á x. de alarma" trigger - Velocidad m á x. de alarma: 1-30000 units/second, matching the maximum allowable change rate of the process
-Suitable for preventing sudden changes in parameters (such as temperature drops caused by heating tube breakage), set "Tipo de alarma=Vel. m á x." in "P á gina Configuraci ó n>Salida de alarma x" and set the threshold in "P á gina Operaiones"
(2) Alarm response and security mechanism
Alarm output logic: supports "Autoborrado" (automatic reset after fault relief) or "Enganche" (manual reset), "Silenciamiento" (mute during startup phase to avoid false alarms during initial heating), "Mensajes de alarma" (P á gina Principal displays fault information).
Fault protection:
Sensor open circuit detection: After triggering, the controller switches to manual mode (output 0%) and displays "oPLP `" (open circuit fault). The wiring needs to be repaired and restarted to restore.
Power failure response: Supports "Modo de falla" (failure mode), such as "Fijo" (maintain output before failure) and "Apagado" (turn off output), with parameters stored in non-volatile memory (not lost when power is turned off).
Independent limit control: It is recommended to connect an external limit controller (such as Watlow 97 series) as redundant protection to prevent overheating/overpressure caused by main controller failure.
4. Communication and Expansion Functions (System Integration)
(1) Communication Protocol and Configuration
Support EIA-232 and EIA-485 buses, adapt to Modbus RTU protocol, and achieve communication with PLC, HMI, SCADA systems:
Key parameter configuration points for communication types, applicable scenarios
EIA-232- Transmission distance: maximum 15 meters
-Baud rate: 9600/19200/38400bps
-Data format: 8-bit data bit, 1-bit stop bit, no checksum (8N1)
-Interface: DB9 terminal, TX/RX/GND. Set "Baudios" (baud rate) and "Direcci ó n" (addresses 1-247) in "P á gina Configuraci ó n>Comunications", support "Modbus RTU" protocol, can transmit input values, setpoints, and output status for short distance point-to-point communication (such as controller and local PC)
EIA-485- Transmission distance: up to 1200 meters (shielded twisted pair)
-Baud rate: Same as EIA-232
-Topology: daisy chain, supporting 32 nodes (expandable through repeaters)
-Terminal resistance: A 120 Ω resistor should be connected to the front and rear nodes to reduce signal reflection. The wiring should distinguish T+/T -/GND (EIA-485 terminal: CA=T -, CB=T+, CC=GND), and star topology is prohibited. Communication lines and power lines should be wired separately (spacing ≥ 10cm) for long-distance multi node communication (such as multiple controllers networked to PLC)
(2) Extended functionality and integration
Remote Setpoints: Switch 3 sets of remote setpoints through analog input (such as 4-20mA) or digital input, suitable for multiple process scenarios (such as different temperature settings corresponding to different products).
Data Resend: Resend output can forward input signals (such as temperature) or control output signals (such as valve opening), support range offset ("Compensataci ó n de escala"), and adapt to the signal requirements of third-party devices.
Software integration: Supports configuring parameters, monitoring status, and backup/restore configurations through EZ-ZONE Configurator software. The software is compatible with Windows systems and requires connection through a USB-EIA-485 converter.

Operation and Configuration Guide
1. Menu navigation and operation logic
The F4P controller software is divided into 4 levels of pages, which are navigated through panel buttons and support wizard style configuration. The operation is intuitive:
(1) Page Structure
Page hierarchy core function access path common operations
P á gina Principal (homepage) displays real-time data (process values, setpoints, output status), fault alarms, quick access to other pages, default page for startup, switches display items by pressing "Up/Down" to view temperature/pressure values, confirms alarm information, and presses "Go to Operations/Configuraci ó n/F á brica" to enter the corresponding page
PID tuning, alarm threshold setting, manual PID parameter adjustment, slope control homepage → "Go to Operations" to start automatic tuning, modify alarm threshold, adjust proportional band/integral time, trigger slope control
P á gina Configuraci ó n (configuration page) Input/output configuration, system parameters (units, filtering), communication parameters, static message homepage → "Go to Configuraci ó n" Select sensor type, set output function, configure baud rate, edit static message (such as "PUERTA ABERTA")
P á gina F á brica (factory page) security permissions (password/lock), calibration (input/output), diagnosis, restore factory settings homepage → "Go to F á brica" (permission required) Set user/administrator password, calibrate input/output accuracy, view fault codes, restore factory parameters