Location selection: Outdoor ventilated area, at least 5 feet away from buildings and combustibles, on a horizontal dry surface, avoiding loose materials (such as sand and grass debris) to prevent blockage of air vents.
Oil inspection:
Engine oil: The new machine has no engine oil and needs to be added to the "MAX" mark on the dipstick (place the cold machine horizontally, wipe the dipstick dry, fully screw it in, and then remove it for inspection).
Fuel: Add unleaded 87-93 gasoline with ethanol content ≤ 10%; Clean the fuel tank after refueling and check for leaks.
Load and grounding: Disconnect all electrical equipment connections; Grounding must comply with local regulations. If connecting to building systems, an electrician must confirm whether a grounding rod (copper wire ≥ 10 AWG) is required.
3. Startup and shutdown operations
(1) Start the process
Turn the fuel valve to the "ON" position.
Cold machine: fully pull out the air damper; Heat engine: Set the choke to the middle or "RUN" position.
Press the start switch to "START" and hold for up to 5 seconds (to avoid overheating of the starter motor); After successful startup, release and warm up for 3-5 minutes.
After the engine runs steadily, slowly push back the choke to the "RUN" position.
(2) Shutdown process
Normal shutdown: Disconnect all loads → Run without load for 3-5 minutes → Turn the switch to "OFF"; Long term non use requires closing the fuel valve and allowing the engine to run until it shuts down on its own (running out of carburetor fuel).
Emergency stop: Simply turn the switch to "OFF" (only for use in case of malfunction or danger).

Key maintenance operation details
(1) Oil change
Place the refrigeration unit horizontally, clean the area around the oil filling port, and place the oil pan.
Remove the oil drain hose, open the valve to drain the oil, close the valve and secure the hose.
Disassemble the old oil filter counterclockwise and clean the installation surface; Apply a small amount of engine oil to the rubber sealing ring of the new filter, manually tighten it until it fits snugly, and then tighten it 3/4 turn (do not overtighten).
Add recommended engine oil to the "MAX" mark on the dipstick, install the dipstick and filler cap, start the engine and check for leaks.
(2) Battery maintenance
Charging: The generator can recharge the battery after running for 30-60 minutes; Long term use of the included trickle charger (connected to the control panel charging port), red light charging in progress, green light fully charged.
Replacement: First disconnect the negative cable, then disconnect the positive cable; The installation sequence of new batteries is reversed (connect the positive electrode first), part number 511075 (36AH), and used batteries need to be disposed of according to local regulations.
(3) Storage maintenance
Key points for storage duration operation
No special treatment is required within one month to maintain normal oil and fuel levels
Add fresh fuel and fuel stabilizer every 2-6 months, and empty the carburetor float
Drain the fuel tank and carburetor fuel after more than 6 months; Change the engine oil; Inject 1 tablespoon of engine oil into the spark plug hole, pull the starting rope to make the piston run (protect the cylinder wall); After cleaning the equipment, store it in a dry and ventilated place, and do not cover it with plastic sheeting (which is prone to moisture and rust)
Common troubleshooting
Possible causes and solutions for the fault phenomenon
The engine cannot start. 1. The battery switch is turned off or running low; 2. Insufficient/deteriorated fuel; 3. Air filter blockage; 4. Low oil level (low oil protection); 5. Spark plugs are damp/faulty/have improper clearances; 6. Fuel filter blockage 1. Turn on the battery switch or charge; 2. Add fresh fuel; 3. Clean/replace the filter; 4. Add engine oil; 5. Dry/replace spark plugs and adjust clearances; 6. Replace the fuel filter
Immediately turn off the engine after starting. 1. Fuel is depleted; 2. Abnormal oil level; 3. The air filter is dirty; 4. Fuel pollution; 5. Low oil level switch fault: 1. Add oil; 2. Check the oil level; 3. Clean the filter; 4. Drain the deteriorated fuel; 5. Contact customer service
No power output 1. Circuit breaker tripped; 2. Load overload; 3. Power cord/electrical equipment malfunction; 4. Internal fault of the generator: 1. Reset the circuit breaker to reduce the load; 2. Disconnect some equipment; 3. Replace the power cord or test the normal equipment; 4. Send to authorized service points
Insufficient engine power/unstable operation 1. Air filter blockage; 2. Fuel deterioration/filter blockage; 3. Overloading; 4. Aging of spark plugs; 5. Abnormal valve clearance: 1. Clean/replace the filter; 2. Replace the fuel and filter; 3. Reduce load; 4. Replace the spark plug; 5. Adjust the valve clearance
Remote start failure (if supported): 1. Remote control battery runs low; 2. Exceeding the remote control distance (≤ 100 feet); 3. Not paired. 1. Replace the remote control battery; 2. Get close to the generator; 3. Re pair (long press the panel pairing button+remote control start/stop button)