Welcome to the Industrial Automation website!

NameDescriptionContent
XING-Automation
E-mail  
Password  
  
Forgot password?
  Register
当前位置:

YOKOGAWA YS100 series instrument

F: | Au:FAN | DA:2025-12-22 | 541 Br: | 🔊 点击朗读正文 ❚❚ | Share:

YOKOGAWA YS100 series instrument

Product Overview

(1) Product positioning and core applications

The YS100 series instruments are industrial grade control and monitoring equipment launched by Yokogawa Electric, covering multiple models such as multifunctional controllers, programmable controllers, alarm indicators, and automatic/manual operation stations, with core adaptability to industrial process control scenarios. As a key extension option, its communication function supports two mainstream communication methods: RS-485 communication (option code/A31) is used to build a distributed monitoring network with monitoring computers (such as PCs), and DCS-LCS communication (option code/A32) is used to access the Yokogawa CENTUM-XL/μ XL distributed control system, realizing equipment status monitoring, parameter configuration, and remote operation, providing stable and flexible human-machine interaction and system linkage solutions for industrial automation.

(2) Applicable models and document basic information

Applicable models for communication function

Communication option code supports model but not supports model

/A31 (RS-485 communication) YS150, YS170, YS131, YS135, YS136 None

/A32 (DCS-LCS communication) YS150, YS170, YS135, YS136 YS131 (with alarm indicator)

(3) Overview of Startup Process

The communication function activation of YS100 series instruments needs to follow standardized procedures, and the core steps include:

Open the box and check the product specifications and communication option configuration (confirm if A31 or A32 options are pre installed);

Complete equipment installation and communication wiring (wiring according to RS-485 or DCS-LCS requirements);

Connect the power supply and enter engineering mode to configure communication parameters (address, baud rate, etc.);

Load control program (programmable model such as YS170) or directly perform communication function testing;

After verifying the stability of the communication link and confirming that data reading, writing, and remote operations are normal, enter the normal operating state.


Core communication specifications

(1) RS-485 Communication Specification (Option Code/A31)

1. Interface and protocol parameters

Communication interface: RS-485 five signal interface, including SD (A) (sending data A), SD (B) (sending data B), RD (A) (receiving data A), RD (B) (receiving data B), SG (signal ground);

Communication protocol: no protocol (command response message format), asynchronous transmission mode;

Transmission parameters: baud rate supports four adjustable levels of 1200/2400/4800/9600bps; Stop position 1 or 2; Parity check supports no check (NO), odd check (ODD), and even check (EVENT);

Data format: ASCII 8-bit encoding, single block text structure, maximum length of a single message is 220 bytes (including CR carriage return and LF line break);

Transmission characteristics: Half duplex communication, bit transmission order is the least significant bit first; The character interval timer is 0.1 seconds, and if it expires, it is judged as a communication error;

Error detection: Supports vertical parity check (even/odd/none), can identify frame errors, parity errors, overflow errors, etc.

2. Connection capability and physical characteristics

Connection method: 1: n multi station connection, a single RS-485 port can connect up to 16 YS100 series instruments, and each instrument needs to be assigned a unique address (1-16);

Communication distance: maximum transmission distance of 1200m (using recommended cables);

Recommended cable: shielded twisted pair, wire diameter 0.5~1.25mm ² (AWG No.20~AWG No.16), such as Hitachi wire CO-SPEV-SB (A) 3Px0.5PQ;

Terminal resistor: A terminal resistor of 120 Ω± 1%, 1/2W, 100ppm/℃ must be connected at both ends of the communication cable. The receiving side is controlled by the JP1 jumper on the RS-485 communication board (ON is enabled, OFF is disabled), and an additional resistor needs to be installed on the instrument panel for the four wire transmission side.

(2) DCS-LCS Communication Specification (Option Code/A32)

1. Adaptation system and connection parameters

Adaptation system: Yokogawa distributed control system CENTUM-XL, μ XL;

Communication link: Connected to DCS field control unit (such as MFCU of μ XL) through LCS loop communication card;

Connection capability: A single LCS card can support up to 8 YS100 instruments, and a single MFCU can install up to 3 LCS cards, so a single MFCU can connect up to 24 instruments; A single EFCS on-site control station can connect up to 120 instruments;

Wiring requirements: KS4 cable (maximum transmission distance of 100m), communication cable using shielded SCCD twisted pair;

Core feature: YS100 instrument is registered as an internal instrument of DCS, supporting monitoring and operation through DCS operator station without additional programming. Monitoring functions can be assigned through standard FIF (Fill In Forms) method.

2. Corresponding relationship between DCS instrument models

YS100 series models, DCS internal instrument models, core monitoring permissions

YS150 (Multi functional Controller) SLPC supports PV/SV/MV read-write, PID parameter configuration, and alarm status monitoring

YS170 (Programmable Controller) SLPC supports PV/SV/MV read and write, program control parameter adjustment, and alarm status monitoring

YS135 (SV setting automatic/manual station) SMST-111 supports PV monitoring, SV setting, and high/low limit alarm configuration

YS136 (MV setting automatic/manual station) SMST-121 supports PV monitoring, MV setting, and upper and lower limit configuration of operating variables

image.png

Installation and wiring specifications

(1) Terminal allocation

The communication terminal of YS100 series instruments is located on the back of the equipment, and can be viewed after removing the terminal cover. The terminal number is marked on the sealing parts and terminal cover on both sides of the chassis. The core communication terminals are assigned as follows:

Terminal Number RS-485 Communication Function DCS-LCS Communication Function Remarks

14 Signal Ground (SG) LCS+, LCS - dual function terminal, switch usage according to communication options

15 Send Data A (SD (A)) - Used only for RS-485 communication

16 Send Data B (SD (B)) - Used only for RS-485 communication

17 Receive Data A (RD (A)) - Used only for RS-485 communication

18 Receive Data B (RD (B)) - Used only for RS-485 communication

FG (GND) shielding layer grounding shielding layer grounding forced grounding, used for anti-interference

Note: The voltage definition of terminals A and B follows the EIA standard: when the signal is "mark" and VA<VB, the corresponding terminal status is OFF or 1; When the signal is "space" and VA>VB, the corresponding terminal status is ON or 0.

(2) RS-485 communication wiring

1. Four wire wiring system

Applicable scenarios: Bidirectional communication scenarios that require simultaneous sending and receiving, with higher communication stability;

Wiring requirements: Use 4-core shielded twisted pair cables to connect SD (A), SD (B), RD (A), and RD (B) respectively. The signal ground (SG) and shielding layer (FG) should be grounded together to avoid common mode interference;

Terminal resistance: Connect 120 Ω terminal resistors between SD (A) - SD (B) and RD (A) - RD (B) on the monitoring computer side and the farthest instrument side, respectively.

2. Two wire wiring system

Applicable scenarios: scenarios with low communication speed requirements and sensitive wiring costs;

Wiring requirements: Use 2-core shielded twisted pair, short-circuit SD (A) and RD (A), short-circuit SD (B) and RD (B), and connect them to the bus. Signal ground and shielding layer ground;

Terminal resistor: Connect a 120 Ω terminal resistor between the short circuited terminals at both ends of the bus.

3. Wiring precautions

Avoid parallel laying with power cables. If crossing is necessary, maintain a 90 ° vertical crossing to reduce electromagnetic interference;

The shielding layer needs to be grounded at one end (recommended to be grounded on the monitoring computer side) to avoid the formation of a grounding loop at both ends;

The cable length cannot exceed 1200m, and if it exceeds this limit, a signal amplifier (compatible with RS-485 protocol) must be used;

When multiple instruments are connected, a bus topology structure is used, and star connections are prohibited to avoid signal reflection.

(3) DCS-LCS communication cabling

1. Core wiring structure

Link composition: DCS field control unit (such as MFCU) → LCS communication card → TE08 terminal block → YS100 instrument, connected to SCCD twisted pair cable through KS4 cable;

Wiring distance: The maximum length of a single section of KS4 cable is 100m. The length of the SCCD twisted pair between the TE08 terminal block and the instrument should be adjusted according to the site layout, and the total attenuation should be controlled;

Shielding requirement: The shielding layer of all communication cables must be connected to the shielding terminal (S) of TE08 terminal block to achieve unified grounding.

2. YS100 and TE08 terminal block wiring

Wiring method: Each YS100 instrument is connected to the LCS+and LCS - terminals of the TE08 terminal block through SCCD twisted pair cables. Terminal 17 corresponds to LCS+, and terminal 18 corresponds to LCS -;

Connection restriction: A single TE08 terminal block can connect up to 8 YS100 instruments, and multiple instruments can be connected in parallel on the same LCS+or LCS - bus.


Communication parameter configuration

(1) Configure entrance and basic parameters

1. Configuration method

The communication parameters are set through the engineering panel group (CONFIG1 menu) on the instrument front-end panel, and only the enable/disable of the terminal resistor needs to be operated through the JP1 jumper on the RS-485 communication board (hardware configuration).

2. Core configuration parameters (CONFIG1 menu)

Line number display item function description default value optional range remark

1 SET configuration enable/disable INHB (disable) INHB, ENBL (enable) must be set to ENBL to modify other parameters

5 COMM communication function display -485 (RS-485), LCS (DCS-LCS) automatically recognizes installed communication options without manual setting

When COMWR communication is enabled with ENBL (allowed) and INHB (prohibited), instrument parameters cannot be modified through communication

8 ADRS RS-485 instrument addresses 1~16. Multiple instruments cannot be duplicated and are not related to DCS-LCS communication

9 STBIT RS-485 stop bits 1 and 2 need to be consistent with the monitoring computer settings

10 PAR RS-485 parity check NO (no check) NO, ODD, EVENT need to be consistent with the monitoring computer settings

11 BPS RS-485 baud rates 1200, 2400, 4800, 9600 need to be consistent with the monitoring computer settings

(2) Computer mode settings

1. Mode type and scope of application

The YS100 series instrument supports two computer modes for achieving deep control of the instrument by the monitoring system:

SPC mode: The monitoring system sends a set value (SV), and the instrument automatically runs according to the set value;

DDC mode: The monitoring system sends operation signals (MV), and the instrument directly outputs the signal;

Applicable restrictions: Only YS150 and YS170 support SPC and DDC modes; YS131, YS135, and YS136 do not support computer mode.

2. C mode configuration

C mode activation: When the "C" key LED of the instrument front-end operation mode key lights up, it enters C mode, which is divided into CAS (cascade mode) and CMP (computer mode);

CAS mode: Receive external cascaded input signals (1-5V) as the set values for YS150/YS170, YS135, and YS136;

CMP mode: CMOD1 (YS135/YS136 only CMOD1) needs to be set as CMP in the CONFIG2 menu. At this time, the set value or operation value can be set from the monitoring computer through SPC/DCD mode.

3. Backup mode settings

Trigger condition: In computer mode, if the instrument does not receive a monitoring system signal or receives a Fail signal, it is determined as a monitoring system failure and automatically switches to backup mode;

Mode options: YS150/YS170 can be set through the BMOD1/BMOD2 parameters in the CONFIG2 menu. BUA is the automatic backup mode, and BUM is the manual backup mode (maintaining output); YS135/YS136 default to fixed BUM mode;

Recovery mechanism: After the monitoring system returns to normal, the instrument needs to manually switch back to computer mode or trigger recovery through communication commands.

(3) Operating mode switching rules

1. YS150/YS170 (RS-485 communication)

Core mode: Supports AUT (automatic), MAN (manual), CAS (cascade), SPC (computer set value control), DDC (computer operation value control), BUA/BUM (backup mode);

Switching logic: SPC/DCD mode is activated through CMP mode, and switches to BUA/BUM when the monitoring system fails; Manual operation can switch between AUT/MAN through the "A/M" button on the panel. In computer mode, you need to exit CMP mode before switching;

Special rule: When using selector control, CMOD2 must be set to CAS; When the DDC status is ON (DDCF1=1) and the mode is AUT/MAN, pressing the C key can directly switch to DDC mode.

2. YS150/YS170 (DCS-LCS communication)

Mode correspondence: The LOOP status displayed on the DCS operator station corresponds one-to-one with the instrument mode, AUT corresponds to automatic mode, MAN corresponds to manual mode, CAS corresponds to cascade mode, and SPC/DCD corresponds to computer mode;

Operation permissions: The DCS side can modify SV (automatic mode) and MV (manual mode). In computer mode, only commands can be sent through the monitoring system, and the DCS side cannot directly modify the set values.

3. YS135/YS136 (Universal Communication)

YS135: Supports CAS (cascade, output CIN1 input value), MAN (manual, output manual set value), DDC (computer mode, output monitoring system set value), DDC mode cannot be activated from the DCS side;

YS136: Supports CAS (cascade, output CIN1 input value), MAN (manual, output manual operation value), DDC (computer mode, output monitoring system operation value), MV setting is only available in MAN mode.

image.png

  • Basler D90 96801 100 PCB Card
  • Basler XR2002F Voltage Regulator (110 VAC, 48-480 Hz)
  • Basler SR8A-2B14B3A Regulator
  • Basler 9561500100 Module
  • Basler DECS-400 BE1-11 System
  • Basler DECS-100-B15 Excitation Control
  • Basler SCP 210 Frequency Controller
  • Basler SR4A-2B15B3A Static Voltage Regulator
  • Basler BE1-32R Power Relay
  • Basler PIA2400-17GM Power Interface Adapter
  • Basler MVC 232 Manual Voltage Control Module
  • Basler SSR 32-12 Static Voltage Regulator
  • Basler 5MW AVR Generator Voltage Regulator
  • Basler VR63-4B Voltage Regulator
  • Basler DECS-100-A05 AVR for Engine Generator
  • Basler DECS-100-B15 Automatic Voltage Regulator
  • Basler BE1-32R Directional Power Relay
  • Basler BE1-87B Differential Relay
  • Basler UFOV 260A Protective Module
  • Basler 9-2614-02-100 PCB Rev M
  • Basler DECS-100-B15 Digital AVR
  • Basler 9284900103 PS DECS-400N
  • Basler D4N3H1U Intertie Protection
  • Basler DECS-100-B15 A15 AVR
  • Basler KR4F Voltage Regulator
  • Basler BE26434 T14 Transformer
  • Basler SR8A-2B15B3A Regulator
  • Westinghouse 774B472A12 AR Relay
  • Basler DECS-100-B15 AVR
  • Basler XR2002F Regulator 110V
  • Basler SR125-E Static Regulator
  • Basler SSR 125-12 Regulator
  • Basler MOC2599 Motor Pot
  • Basler BE1-DFPR Feeder Relay
  • Basler CBS 305 Current Boost
  • Basler BE1-25 AutoSync
  • Basler MVC 300 Voltage Control
  • Basler BE3-25A AutoSync
  • Basler KR7FF Static Regulator
  • Basler 90-49000-100 Regulator
  • Basler 880 kVA Dry Type Transformer Specs
  • Basler Electric BE1-25 Sync-Check Relay Specs
  • Basler SSR 125-12 Voltage Regulator Specs
  • Basler Electric BE1-851 Overcurrent Relay Review
  • Basler Electric 149D930G02 Control Sub-Assembly
  • Basler Electric BE1-81O/UT Frequency Relay Specs
  • Basler Electric BE1-51/27C Overcurrent Relay
  • Basler Electric 149D956G02 Industrial Component
  • Basler Electric BE1-51A Overcurrent Relay Specs
  • Basler Electric BE1-40Q Loss of Excitation Relay
  • Basler DECS-200 Excitation Control System
  • Basler DECS-200 Voltage Regulator 56-277V AC / 125V DC
  • Basler BE1-87T Transformer Differential Relay
  • Basler RDP-110-S1 Protection Relay
  • Basler BE1-700V Digital Protective Relay
  • Basler BE1-951 Overcurrent Protection System
  • Basler DECS-300 Digital Excitation Control
  • Basler DECS-200 Digital Excitation Control
  • Basler DECS-200-1C Excitation Control System
  • Basler DECS-200-1L Digital Excitation Control
  • Basler Electric BE1-GPS Generator Protection System
  • Basler Electric DECS-200-1C Digital Excitation Controller
  • Basler Electric DECS125-15 Excitation Control with Power Module
  • Basler Electric BE1-87G Differential Relay
  • Basler Electric BE1-11 Protection System I5A3M2P2N0EA00
  • Basler Electric DECS-200-1C Excitation Control System
  • Basler Electric BE1-11g Generator Protection Relay
  • Basler Electric DECS 125-15-B2C1 V2.0.9 Excitation Control
  • Basler Electric BE1-81O/UT3ED1JA7N2F Frequency Relay
  • Basler Electric BE1-81O/UT3EE1YB7N1F Frequency Relay
  • Basler Electric DECS-200-1L Digital Excitation Control System
  • Basler DECS125-15-B2C1 Excitation Control
  • Basler 9507900205 SSR Retrofit Voltage Regulator
  • Basler BE2000E Digital Voltage Regulator
  • Basler BE1-GPS Generator Protection System
  • Basler DECS-250-CN1CN1N Digital Excitation Control
  • Basler DGC-2020 Genset Controller
  • Basler BE1-81O UT3ED1LA7N0F Frequency Relay (Variant)
  • Basler BE1-81O UT3EE1YA9S0F Frequency Relay (Variant)
  • Basler BE1-81O Over/Under Frequency Relay
  • Basler DECS125-15 Digital Excitation Control
  • Basler Electric BE1-951 Overcurrent Protection System
  • Basler Electric BE1-700V Digital Protective Relay
  • Basler Electric APR63-5 Automatic Voltage Regulator
  • Basler Electric BE1-851 Overcurrent Protection System
  • Basler Electric DECS-250-LN1SN1N Excitation Control
  • Basler Electric BE1-87T Transformer Differential Relay
  • Basler Electric DECS-200-1L Excitation Control System
  • Basler Electric 9310300100 DECS-300 Excitation Control
  • Basler Electric SSE-N 125-4.5KW Shunt Exciter Regulator
  • Basler Electric DGC-2020HD-5NS1DNSBA Genset Controller
  • Basler Electric BE1-81-O/UT3EE1JB7N1F Frequency Relay
  • Basler Electric BE1-81T1EE1WA0N1F Frequency Relay
  • Basler Electric BE1-25M1EA6PN5R1F Sync-Check Relay
  • Basler Electric BE1-GPS Generator Protection System
  • Basler Electric DECS-250-LN1SN1N Excitation Control Rev V
  • Basler Electric DECS-250-CN2CN1N Excitation Control
  • Basler Electric BE1-50/51B-207 Overcurrent Relay
  • Basler Electric DECS-300-C0N0 Excitation Control System
  • Basler Electric DECS-200 Digital Excitation Control System
  • Basler Electric DECS-250-LN1CN1N Excitation Unit
  • Basler Electric DECS-250 LN2SA1D Excitation Unit Specs
  • Basler Electric BE1-87T Transformer Relay Review
  • Basler Electric BE1-11 Protection System
  • Basler Electric BE1-GPS100-E4N1H1N Protection System
  • Allen-Bradley 442G-MABH-R Safety Module
  • Beckhoff CX1030-0111 PLC Assembly Profile
  • FANUC IC693CPU364 PLC Module
  • Orange Denmark Type 200816 220 PLC Specs
  • OMRON C200H-SNT31 Sysmac PLC Module
  • Allen Bradley 20AB022A3AYNANC0 PowerFlex 70
  • OMRON C200HW-PCU01 Position Control Unit
  • ABB AO845A-eA Analog Output Module
  • OMRON CJ1M-CPU22 CPU Unit
  • Allen Bradley 100-E265ED11 Contactor
  • Honeywell 51304511-100 Interface Module
  • SOLEXY BXF3S0101N0018 Gateway Module
  • OMRON CJ2H-CPU65 CPU Unit
  • Automation Direct GS2-45P0 AC Drive
  • M68-2000 2-Axis Motion CNC Controller
  • OMRON CJ1M-CPU11 V3.0 PLC CPU Unit
  • OMRON CJ1W-NC413 4-Axis Positioning Controller
  • OMRON 3G2A3-PRO16 Programming Console HMI
  • Siemens 3VT8440-2AA04-2GA2 Molded Case Circuit Breaker
  • Siemens 3RT5045 Contactor Series
  • OMRON C200HS-CPU01-E SYSMAC PLC Controller
  • OMRON C500-NC103-E Positioning Control Unit
  • OMRON CJ1W-TC001 Temperature Control Unit