The ABB AF210-30-11 is a three-pole contactor from the AF series, designed for switching resistive and inductive loads up to 210A AC-1. Its coil accepts a wide voltage range of 110-240VAC, making it suitable for global industrial applications without requiring different coils for different line voltages.
Number of poles: 3 normally open (3NO)
Rated thermal current (Ith): 210A
AC-1 (resistive) rating: 210A @ 40°C
AC-3 (motor starting) rating: 165A / 90kW @ 400V
AC-4 (plugging/jogging) rating: 100A
Utilization category: AC-1, AC-3, AC-4, DC-1
Rated insulation voltage (Ui): 1000V
Impulse withstand voltage (Uimp): 8kV
| Parameter | Value |
|---|---|
| Coil voltage range | 110-240VAC (50/60Hz) |
| Pick-up voltage | 85% of min nominal (93.5VAC) |
| Drop-out voltage | 20-75% of nominal |
| Inrush VA (sealed) | 20 VA (typical) |
| Sealed VA (holding) | 4 VA |
| Built-in varistor | Yes, for surge suppression |
Electrical life (AC-3): 1.2 million operations. Mechanical life: 10 million operations. Maximum operating rate: 1200 cycles per hour (mechanical), 600 cycles per hour (electrical under AC-3).
The AF210-30-11 includes one normally open and one normally closed instantaneous auxiliary contact (1NO + 1NC) rated at 6A AC-15 / 0.5A DC-13. Additional auxiliary contact blocks (front or side mount) can be added up to 4 blocks.

Operating temperature: -40°C to +70°C
Storage temperature: -60°C to +80°C
Mounting: Screw terminals (main contacts: M8, aux: M3.5)
Dimensions (WxHxD): 85mm x 162mm x 158mm (without arc chute extension)
Weight: 2.2kg
Protection degree: IP20 (finger-safe terminals)
IEC 60947-1, IEC 60947-4-1, EN 60947-4-1. Approved by CCC, EAC, UL (pending), CSA. CE marked. RoHS compliant.
Motor control centers (MCC), lighting distribution, heating control, capacitor banks, and industrial power supplies requiring reliable AC switching. The wide coil voltage range makes it ideal for UPS-backed systems and unstable mains environments.