The Siemens 6FX1122-1AC02 is a specialized PLC card primarily used within Sinumerik CNC control systems and SIMATIC S7-300 series I/O expansions. It serves as a signal interface between the CPU and external devices such as encoders, drives, or remote I/O stations.
This module provides digital input/output signal conditioning with electrical isolation. It is part of the 6FX1122 family of interface components designed for harsh industrial environments. The card plugs into a standard backplane or directly into a Siemens industrial PC slot (ISA or proprietary connector depending on revision).
| Parameter | Value |
|---|---|
| Supply voltage (logic) | 5VDC ±5% from backplane |
| Supply voltage (field) | 24VDC ±20% (external) |
| Number of channels | 8 digital inputs / 8 digital outputs (configurable) |
| Input voltage range (ON) | 15-30VDC |
| Input current per channel | 7mA at 24V |
| Output type | Transistor sourcing (PNP), 0.5A per channel |
| Output protection | Short circuit and overload protection |

Optical isolation between backplane logic and field I/O: 1500VAC for 1 minute. Each group of 4 channels shares a common potential. Status LEDs for each input and output indicate active signals. Reverse polarity protection on 24V field supply.
Dimensions: 100mm x 70mm x 15mm (approx.)
Weight: 0.12kg
Operating temperature: 0°C to 60°C
Storage temperature: -40°C to 85°C
Relative humidity: 5% to 95% non-condensing
Conformal coating: Yes (standard for industrial use)
The 6FX1122-1AC02 is compatible with Sinumerik 810D, 840D sl, and SIMATIC S7-300 PLCs using a dedicated interface cable (6FX8002 series). It is addressed via STEP 7 hardware configuration as a standard I/O module. Typical applications include connecting pushbuttons, limit switches, solenoid valves, and indicator lights to the CNC/PLC system.
Onboard diagnostics include green RUN LED and red ERROR LED. Fault codes can be read via Siemens diagnostic buffer. The card supports hot swapping when used with an appropriate backplane (not all systems support this). Replacement without power-down is allowed only in systems with passive backplane and proper grounding.