The CJ1W-DA041 module converts digital data received from the CPU unit into analog output signals suitable for controlling analog field instruments. Each of the four outputs can be independently configured for either voltage or current operation, with a comprehensive selection of industry-standard signal ranges. This flexibility allows a single module to accommodate mixed signal types within the same installation, reducing the number of modules required and simplifying system design. The module supports signal ranges including 0 to 5 V, 0 to 10 V, 1 to 5 V, -10 to +10 V for voltage outputs, and 4 to 20 mA for current outputs, covering the vast majority of analog control applications in industrial automation.
Independent Channel Configuration: Each output channel can be configured with a different signal range
Removable Terminal Block: Facilitates easy wiring changes and module replacement without rewiring
External Power Supply: Operates on 24 V DC external power with 200 mA maximum current requirement
High Accuracy: Voltage output accuracy of ±0.3% of full scale at 25°C ambient temperature
Current Output Accuracy: ±0.5% of full scale at 25°C ambient temperature
Fast Update Rate: Conversion period of 1 ms per point for responsive control loops
Compact Profile: Dimensions of 90 x 31 x 65 mm for space-efficient cabinet mounting
| Parameter | Specification |
|---|---|
| Product Name | Analog Output Unit |
| Model | CJ1W-DA041 |
| Unit Type | CJ1 Special I/O Unit |
| I/O Points | 4 analog outputs |
| Signal Ranges | 1-5V, 0-5V, 0-10V, -10-10V, 4-20mA |
| Resolution | 1/4000 (12-bit equivalent) |
| Conversion Period | 1 ms per point |
| External Connection | Removable terminal block |
| External Power Supply | 24 V DC +10% / -15%, 200 mA max |
| Unit Number Allocation | 1 unit number |
| Current Consumption (5V) | 0.12 A |
| Current Consumption (24V) | 0.20 A |
| Dimensions (H x W x D) | 90 x 31 x 65 mm |
| Standards | UC1, N, L, CE |

The CJ1W-DA041 module is fully compatible with the complete Omron CJ series PLC line including CJ1G, CJ1H, and CJ2 CPU units. The module occupies a single unit number slot on the CJ series backplane and communicates with the CPU unit via the high-speed CJ system bus. Data exchange between the CPU and the analog output module occurs automatically during each system scan cycle, with the module reading output data from designated DM Area words and converting the values to analog output signals. The module‘s allocation of unit numbers can be configured through the CX-Programmer software, providing flexible addressing options for large systems with multiple analog modules.
Process Control: Analog setpoint generation for temperature, pressure, and flow controllers
Motion Control: Speed and torque reference signals for drive systems
Test and Measurement: Signal generation for equipment testing and validation
Machine Automation: Control of analog actuators and positioning systems
Building Automation: HVAC damper and valve control applications
The CJ1W-DA041 is rated for operation in industrial environments with an operating temperature range of 0°C to 55°C and relative humidity of 10% to 90% non-condensing. The module complies with Omron's standards for noise immunity and EMC performance, ensuring reliable operation in electrically noisy factory environments. Its UL and CE certifications confirm compliance with international safety and electromagnetic compatibility requirements for industrial control equipment.