S100 I/O is the central process interface for Advant
Controller 400 series process controllers. Thanks to
built-in cablemarshalling facilities and parallel
communication with the host controller, it is the
right choice for centralized I/O systems and
high-speed applications.
The range of process I/O modules is complete,
consisting of general purpose digital and analog
inputs and outputs and special interfaces for special
tasks. These specials include pulse counting,
frequency measuring, positioning, motor speed
control and communication with other controllers.
All I/O modules provide simple interfacing, accurate -
yet fast - control, and easy integration of individual
loops into a comprehensive plant-wide control
and supervision system.
The interface modules connect to the process
through screw terminals on connection units
normally installed inside, at the back of the cabinet.
This solution keeps noise and destructive voltage
spikes away from the central electronics and
provides a neat and tidy process interface that is
easy to maintain.
Prefabricated cables interconnect modules with
connection units. The cables come in different
lengths, permitting termination and marshalling
in controller cabinets, in adjacent cabinets, or in
cabinets a greater distance away.
There are connection units that support signaloriented
or device-oriented field wiring. The former
means that field wires with the same electrical
characteristics (e.g. all 24 V d.c. inputs) are grouped
and terminated together, the latter that field wires
to/from the same field devices are grouped and
terminated together. The combination means
maximum installation flexibility.
On-board processing capabilities
The process I/O modules are “intelligent” in the sense that module-related signal and data processing is performed on board as opposed to centrally, by the CPU of the host controller. Time tagging of events, filtering and gain control are some examples of board-level tasks. This functional distribution improves real-time performance and reliability of the system as a whole and maintains processing capacity when the system is expanded.
Comprehensive self-diagnostics
Comprehensive self-diagnostics continuously monitor the modules and report any errors through LEDs on the module fronts and through alarm messages and indications to process operator stations.
Malfunctioning inputs can be disabled and simulated by manual entry while failing outputs are deactivated or driven to a predetermined safe state automatically. All I/O modules can be replaced while the system is in service. Some modules can even be arranged, transparently into dually redundant configurations
forenhanced availability.
High disturbance immunity
All modules conform to the highest standards of electromagnetic noise immunity and satisfy the
requirements of the EU directives 2014/30/EU and 2014/35/EU. For the above reasons, S100 I/O is likely to be the best help you can get for putting your control system in touch with
Analog inputs
±10 V/±20 mA
• 16 ch., differential, 12 bits + sign resolution, CMV ≤ 50 V,
CMRR > 100 dB (at 50 Hz), (DSAI 130A)
0…+10 V/0…+20 mA
• 32 ch. (DSAI 133A1), single-ended, 12 bits resolution
-100…+320/-200…+640°C
• 31 measuring + 1 reference ch., Pt100, 3-wire, 12 bits + sign
resolution, (DSAI 146)
Thermocouples
• 14 measuring, 2 reference + 1 compensation ch., measuring
ranges B, C, E, J, K, R, S and T with grounded or floating output
signals, 12/13 bits + sign resolution, CMV ≤ 16 V,
CMRR > 100 dB (at 50 Hz), (DSAI 155A)
Digital outputs
24…250 V a.c. or d.c.
• 32 ch., (DSDO 115A/DSTD 108P), relay contacts.
Relay data: Load current; max. 3 A, min 0,1 A at 24 V d.c. or
2,5 VA a.c. Breaking capacity a.c max 720 VA at cos Φ > 0.4;
d.c. max 44 W at L/R <40 ms.
• 32 ch., (DSDO 115A/DSTD 108LP), relay contacts.
Relay data: Load current; max. 200 mA, min 1 mA, 0.05 VA. Breaking
capacity a.c max 5 VA at cos Φ > 0,4; d.c. max. 5 W at L/R
<40 ms.
24 V d.c.
• 32 ch., short-circuit-proof transistor, max. 500 mA, (DSDO 115A)
• 32 ch., (DSDO 115A/DSTD 109P) short-circuit-proof transistor,
max. 2 A
Pulse counting and positioning
5/12/24 V d.c.
• 12 ch., max. 10 kHz, (DSDP 150)
Complete interface (DSDP 140A) for one positioning loop,
consisting of:
• Pulse inputs: 3 (A, B and STROBE), ±15 mA, max. 80 kHz DI/DO:
24 V d.c. DO max. 150 mA AO: ±10V/±20 mA, 11 bits resolution
Complete interface (DSDP 170) for
• 4 position transducers, each circuit consisting of: Pulse inputs:
3 (A, B and STROBE), 5/12/24 V or ±15 mA d.c., max. 2.5 MHz
DI/DO: 24 V d.c. DO max.150 mA
Digital speed control of motors
Complete interface (DSDC 111) for one d.c. motor, consisting of:
3 pulse inputs for A, B and STROBE
1 DI, 24 V d.c.
1 DO, 24 V, 150 mA d.c.
1 AO, ±10 V/±20 mA, 12 bits resolution
email:1583694102@qq.com