The safety circuit (STO, emergency stop) needs to be independently wired to ensure that protection is triggered first in case of a fault.
2. Debugging process and parameter configuration
The manual provides standardized debugging steps, suitable for most application scenarios:
Pre power on inspection: Confirm correct wiring (no short circuit, virtual connection), grounding resistance ≤ 4 Ω, parameter reset (default factory settings);
First power on: first turn on the control power supply (check if the panel display is normal), then turn on the main power supply (continue only if there are no fault alarms);
Motor identification: Implement the "motor identification" function (static/dynamic identification optional), the frequency converter automatically reads motor parameters (such as rated power, current, impedance), and optimizes control accuracy;
Core parameter settings: Configure key parameters based on load characteristics (such as control mode P100, rated speed P304, starting torque P640, acceleration/deceleration time P221/P222);
Trial operation: First, jog the motor to test the direction of rotation (to avoid equipment damage caused by reverse rotation), then gradually increase the speed to the rated value, and monitor whether the current and temperature are normal.
3. Fault diagnosis and maintenance
The manual includes a "fault code table" that details the causes and troubleshooting methods of common faults (such as F001 overcurrent, F002 overvoltage, F003 overheating), and provides maintenance recommendations:
Daily maintenance: Clean the heat dissipation channel (dust screen, heat sink) weekly, check the tightness of the wiring terminals monthly, and check the insulation resistance quarterly (main circuit to ground ≥ 1M Ω);
Regularly replace components: cooling fan (with a lifespan of about 2-3 years), electrolytic capacitor (with a lifespan of about 5-8 years, adjusted according to the ambient temperature). The manual specifies the vulnerable part models and replacement steps for different models;
Fault record: The frequency converter can store the last 20 fault information (including fault time, current/voltage/speed at the time of the fault), which can be read through the panel or communication interface to assist in locating the root cause.