Status display: Each input channel has a yellow LED to show the status, which is easy to monitor the input signal status visually.
Output Specifications
Number and logic: 6 binary outputs, positive logic.
Electrical parameters: ‘1’ signal output voltage is min. DC 19V, nom. DC 24V, max. DC 30V; Output current is max. 3A per unit, max. 600mA for a single ‘1’ signal, inrush current limit is 0.7A - 1.5A. Inrush current limit is 0.7A - 1.5A; ‘0’ signal output voltage has different limits under different loads, residual current < 0.5mA, voltage drop < DC 0.15V (under 600mA load current) when signal ‘1’ is on.
Protection Circuit: It is equipped with perfect protection circuit to shut down the output when the output is short-circuited or the temperature of the driver chip reaches about 160°C; when the +24V power supply is lower than DC 8V, all outputs will be shut down to effectively protect the safety of the equipment and circuits.
Time constant: output signal time constant 50µs < td < 200µs, depending on the load and voltage changes, to ensure the stability and accuracy of signal transmission.
Status display: yellow LEDs for each output channel indicate status, making it easy to monitor the outputs.
Integrated communication channels
Number and interfaces: 2 non-isolated RS232 channels are integrated, connected via 8-pin RJ-45 connectors, with a metal housing for the connection cable shield to reduce electromagnetic interference.
Communication protocols: Channel 0 supports MMS (SattLink) protocol, channel 1 supports COMLI, MMS (SattLink), 3964R and user-defined protocols to meet different communication requirements.
Status display: Transmit (TD 0, TD 1) and receive (RD 0, RD 1) status is displayed by green LED.
Baud rate: Channel 0 is fixed at 9600 Baud, channel 1 supports various baud rates from 75 to 38400 Baud, which can be set flexibly according to actual communication requirements.
Data format: Data bit can be set as 7 or 8 bits (standard 8 bits), parity can be selected as odd parity, even parity or no parity, stop bit can be set as 1 bit (standard) or 2 bits.
Cable length: The maximum length of communication cable is 15m, which limits the communication distance, and signal attenuation should be considered in practical applications.
PROFIBUS-DP Interface Unit CI274 (optional)
Type: DP master class 1, connects to I/O units of S800, S200 and S200L series to achieve distributed control.
Communication protocol: Adopts PROFIBUS-DP protocol to ensure efficient and reliable data transmission on the bus.
Transmission rate: Supports 9.6, 19.2, 93.75, 187.5, 500, 1500, 3000, 6000 or 12000kBit/s transmission rates, which can be selected according to the network size and data transmission requirements.
Isolation mode: no electrical isolation, use should pay attention to the electrical compatibility and anti-interference measures.
Status display: Red error LED, green Ready and Run LEDs on the front panel, and 3 LEDs for service purposes on the card, which are convenient for users to know the working status of the device.
Interface: Connects via a 9-pin D-SUB connector for easy physical connection to other devices.
Current Consumption: Internal DC 5V current consumption of 700mA typical.
Weight and Dimensions: Weight 45g, dimensions 54 x 86mm, compact size for easy installation in the limited space inside the controller.
Battery / Real-time clock unit SB210 (optional)
Battery: A 3.0V, 0.22Ah lithium battery (Model CR2430, UL Listed) maintains real-time clock operation and RAM contents for approximately one year, ensuring that the system maintains the time and part of the data in the event of a power failure.
Real Time Clock Accuracy: 100ppm (approx. 1 hour/year) to ensure system time accuracy.
Weight and dimensions: Weight 15g, dimensions 44×57mm, compact size, easy to integrate into the controller.
email:1583694102@qq.com