This operation is simple but crucial - if the 60Hz system does not cut the jumper and the inflection point is still 45Hz, frequency compensation will not intervene during normal operation (above 50Hz), but may act too early or too late in low-frequency events.

Installation and Wiring Engineering Guide
1. Installation location
The regulator can be installed in any direction without affecting performance. The size of the panel opening is shown in Figure 1 of the manual (inches/millimeters double labeled). Due to its weight of only 283g, it can be directly fixed on the inner wall of the control box or in the generator junction box.
2. Wiring topology
Figure 2 of the manual provides four typical wiring diagrams, covering common generator wiring methods:
208/240Vac three-phase four wire: used for common industrial power distribution
120/240Vac single-phase with neutral wire: used for single-phase or phase separated power generation
240Vac three-phase three wire: used for three-phase systems without neutral wires
Solution with remote voltage regulator potentiometer: Remote control is achieved by cutting off the VAR line and connecting it to a 1k Ω potentiometer
Excitation output wiring:
The F+end is connected to the positive pole of the excitation machine magnetic field, and the F - end is connected to the negative pole.
It is strictly prohibited to connect switches in series in the F+and F - circuits - the excitation shutdown function is achieved through internal control of the regulator, rather than external contacts.
Fuse configuration:
It is recommended to install high breaking capacity fuses in the power input circuit to protect the circuit from short-circuit faults.
Important: The fuse must be installed according to the wiring diagram to avoid accidentally cutting off the excitation current circuit.
Principles of Regulation and Control
1. Voltage regulation
Internal potentiometer: Rotate clockwise to increase the voltage at the generator terminal, and counterclockwise to decrease.
Remote adjustment: When remote voltage adjustment is required, the VAR wire on the regulator can be cut and connected in series with a 1k Ω± 10%/0.5W potentiometer. Refer to Figure 2 for the wiring method. The remote potentiometer works in series with the internal potentiometer, and when the remote is placed in the middle position, the internal potentiometer can be used for coarse adjustment.
2. Stability adjustment
The stability potentiometer (STAB) affects the dynamic response of the generator to load changes:
Clockwise: Slow response speed and reduced overshoot (more stable) - suitable for situations with low response requirements.
Counter clockwise: response speed increases, overshoot increases (more sensitive) - suitable for situations where high voltage recovery speed is required.
Actual tuning suggestion: Switch the load slightly under rated load and observe the voltage waveform. If there is excessive damping (slow recovery), rotate counterclockwise appropriately; If there is insufficient damping (oscillation), rotate clockwise until critical stability is reached.
Complete process of operation and debugging
1. Check before startup
Confirm that the regulator specifications match the generator (voltage, frequency, excitation resistance)
Confirm that the wiring is correct (compare Figure 2)
Confirm that the fuse has been installed correctly
Turn the voltage regulator potentiometer counterclockwise to the lowest position; If there is a remote potentiometer, place it in the middle position
2. System startup
Start the prime mover to the rated speed
The generator should automatically build voltage (residual voltage ≥ 6Vac can start excitation)
Slowly adjust the voltage potentiometer clockwise until the output voltage reaches the rated value
If using a remote potentiometer, use it for fine adjustment
3. Failure handling of excitation
If the voltage building fails after the first operation or long-term shutdown (residual voltage below 6Vac), field flashing operation should be performed:
In the shutdown state of the prime mover, take a DC power supply (such as a battery) of ≤ 12Vdc, connect it in series with a 3-5 Ω current limiting resistor to the F+and F - terminals, hold for about 3 seconds, and then disconnect.
Restart the prime mover and measure the voltage between terminals 3-4. If>6Vac, the pressure building should be successful.
If it still fails, check the excitation circuit and residual magnetic polarity; If multiple attempts fail, consider replacing the regulator.
Safety warning: When starting excitation, it is necessary to use a current limiting resistor, otherwise it may damage the regulator output stage or excitation winding.
4. Operational testing (bench validation)
Before installation or during troubleshooting, the basic function of the regulator can be verified using the test circuit in Figure 5 of the manual:
Connect 120Vac power supply and indicator light (bulb)
The light bulb should flash briefly when starting
Slowly adjust the voltage potentiometer, the bulb should smoothly brighten and reach maximum brightness at a certain position (indicating that the adjustment point has been reached)