Description
The EDS3090 series is a complete portable ground fault locataion solution for ungrounded AC and DC systems. The system locates ground faults down to the load level while the system remains online. EDS3090 series kits may also be used for branch ground fault current measurement in grounded and high-resistance grounded AC systems. All essential components are housed in a robust aluminum case. The EDS3090 system is perfect for large general distribution networks, utilities, ships, healthcare facilities, and more. Various versions of the kit available, including completely standalone portable kits, as well as kits that work with installed BENDER ground fault detectors, including the IRDH575 and LIM2010.
Features
Portable ground fault location system for ungrounded systems: Up to 790 VAC (42 - 460 Hz) and up to 960 VDC (may require coupler: see description for details)
Locate ground faults with portable equipment while the system remains online
Works on AC and DC systems
Offline fault location also available
Branch ground fault current measurements in grounded AC systems
Use in both small and large ungrounded systems
Package includes 0.8" and 2" split-core clamps (4.5" clamp also available)
Robust aluminum carrying case
Various types of kits available - see description for more information
EDS195P hand-held evaluator
Backlit LCD display
Rechargable battery with power supply, microUSB connection
Read either tracer signal for fault location in ungrounded systems, or measured ground fault current in AC grounded systems
Kit Types and Application
Standalone portable fault location systems (no other devices required), refer to ordering information for a complete list of options:
• EDS3090PG
For general distribution: 20 - 575 VAC (42 - 460 Hz), 20 - 504 VDC
With AGE185 voltage coupler: 500 - 790 VAC, 400 - 960 VDC
• EDS3091PG
For smaller systems, control networks, and healthcare facilities:
20 - 265 VAC (42 - 460 Hz), 20 - 308 VDC
Kits used in conjunction with installed BENDER ground fault detectors:
• EDS3090
For general distribution
• EDS3091
For smaller systems, control networks, and healthcare facilities:

Detailed explanation of core components
(1) Core equipment
EDS195P Handheld Evaluator (System Control Core)
Function: Switching measurement modes, displaying data, triggering alarms, parameter adjustment, supporting two core modes:
I Δ s mode: Grounding fault location in ungrounded systems, receiving positioning current signals collected by measuring pliers;
I Δ n mode: residual current measurement of the grounding system, displaying the residual current value of the branch.
Key features: 3-line 16 character backlit LCD display screen, ALARM LED alarm light (lights up when the threshold is exceeded); Support HOLD data retention, RESET reset, and INFO device information query; Charging through MicroUSB interface.
Power supply and endurance: 3 AA batteries or NiMH rechargeable batteries (≥ 2000mAh), endurance ≤ 60h without backlight, power consumption ≤ 0.5W.
Protection and size: IP40 protection, ABS shell (UL94 V-0 flame retardant), size 84 × 197 × 30mm, weight ≤ 350g.
The PGH series current injector (positioning signal source) is responsible for generating stable positioning current and driving the fault location of ungrounded systems. Different models have clear adaptation scenarios: | Model | Adaptation Scenario | Power Supply Voltage | Maximum Positioning Current (optional) | Core Features|
|PGH183 | Small systems/medical facilities | 230V AC/90-132V AC (-13) | 1mA/2.5mA | Low current output, compatible with control circuits|
|PGH185 | Main distribution system | 230V AC/90-132V AC (-13) | 10mA/25mA | Medium high current output, compatible with main circuit|
|PGH186 | Offline System | 230V AC/90-132V AC (-13) | 10mA/25mA | Built in 50V DC Measurement Voltage, Suitable for Offline/Low Voltage Systems|
Operation design: including ON/OFF switch, current gear switch, back with magnetic strip (attached to metal cabinet), equipped with power ON and positive and negative current cycle LED indicator lights.
AGE185 voltage coupler (optional)
Function: Expand the system voltage range to AC 500-790V (42-460Hz), DC 400-960V, and adapt to high-voltage ungrounded systems;
Parameters: IP30 protection, safety plug+green yellow grounding wire (1mm ²), weight ≤ 200g, size 88.5 × 42 × 21mm.
(2) Measuring pliers
Classified by jaw diameter and adaptation scenario, the core parameters are as follows:
Model Jaw Diameter Adaptation Equipment Series Measurement Range Variable Ratio Weight Dimensions (W × H × D)
PSA3020/3320 20mm 30 series (main circuit)/33 series (control circuit) PSA30: 2mA-10A; PSA33:0.2mA-2A PSA30:10A/10mA; PSA33:1A/0.1mA ≤300g 135×65×30mm
PSA3052/3352 52mm 30 series (main circuit)/33 series (control circuit) with the same corresponding model as above ≤ 700g 216 × 111 × 45mm
PSA3165 (optional) 115mm 30 series (main circuit) 2mA-10A 10A/10mA ≤ 1300g 285 × 179 × 45mm
Common features: All are equipped with 2m long shielded wires, connected to EDS195P through BNC connectors, and comply with CAT III (AC 600V)/CAT IV (AC 300V) safety levels.
Key technical parameters
(1) Measure performance parameters
Measurement Function Adaptation System Core Parameters Measurement Accuracy Frequency Range
Grounding fault location (main circuit) Non grounded AC/DC system response value: 2-10mA (default 5mA), positioning current: 10-25mA ± 30%/± 2mA AC 42-460Hz
Grounding fault location (control circuit) Non grounded AC/DC system response value: 0.2-1mA (default 0.5mA), positioning current: 1-2.5mA ± 30%/± 0.2mA AC 42-460Hz
Residual current measurement (30 series clamp) grounding/high resistance grounding AC system measurement range: 2mA-10A, response value: 10mA-10A (default 100mA) 42-60Hz: ± 5%; 61-1000Hz:±20% AC 42-1000Hz
Residual current measurement (33 series clamp) grounding/high resistance grounding AC system measurement range: 0.2mA-2A, response value: 5mA-1A (default 100mA) with the same accuracy as above AC 42-1000Hz
(2) Environmental and physical parameters
Parameter category specific specifications
Working temperature -10 ℃~+55 ℃
Climate level (IEC 60721): Fixed use 3K5, transportation 2K3, long-term storage 1K4 (no condensation, no icing)
Mechanical grade (IEC 60721): Fixed use 3M4, transportation 2M2, long-term storage 1M3
Protection level: Core component IP40, AGE185 coupler IP30
The basic configuration of the chassis weight is ≤ 7kg, including PSA3165 pliers ≤ 8.5kg, EDS3092 model ≤ 9kg
Operation and usage characteristics
Core operating procedures
Mode switching: Use the EDS195P mode selection key to switch between "Fault location (I Δ s)" or "Residual current measurement (I Δ n)";
Clamp type selection: Match the corresponding type (such as P20=PSA3020/3320) with the selection key based on the measurement clamp model used;
Data processing: Press the HOLD button to save the current measurement value, and press the RESET button to reset; The MENU key enters the parameter adjustment interface (such as response value, harmonic setting);
Alarm indication: When the measured value exceeds the set threshold, the ALARM LED lights up to indicate a fault.
Typical application scenarios
Scenario 1: Independent online fault location (without installed equipment): EDS3090PG/3091PG series, generates positioning current through PGH injector, and EDS195P cooperates with measuring pliers to locate the fault branch;
Scenario 2: In conjunction with the installed equipment fault location: EDS3090/3091 series, using existing detectors such as BENDER IRDH575 to generate signals, only the evaluation instrument and measuring pliers are needed to complete the positioning;
Scenario 3: Measurement of residual current in grounding system: All models support it. Wrap the branch cable with measuring pliers and directly read the residual current value.
Ordering and Accessories
Optional accessories and functions | Accessory name | Function description | Adaptation scenario|
|PSA3165 measuring pliers | 115mm large clamp, suitable for thick cables | measurement of large section cables in the main distribution system|
|AGE185 voltage coupler | extends voltage range to AC 500-790V/DC 400-960V | high voltage ungrounded system|
|EDS145-SET | Special accessories for fault location of diode isolation system | Power plant diode isolation DC system|
Example of ordering code:
EDS3090PG-13: Main distribution system, independent, 90-132V AC power supply, including PGH185-13 injector;
EDS3091PG: Small system/medical facility, standalone, 230V AC power supply, including PGH183 injector.