High voltage discrete output TA: Suitable for 120V ac/240V ac voltage, using plug-in SPDT (Form C) electromechanical relays or solid-state switches, relays can be replaced on site, supporting mixed voltage, high and low voltage signal isolation layout, power supply needs to be provided externally, some models include power distribution function (power supply positive pole fuse, negative pole connected to site).
(3) Partial TA models and parameters (compatible with FBM242)
TA model output signal terminal type cable type certification type
RH916JY (replacing P0916JY) 16 channel, with fuse, 15-60V DC (external supply), 2A max, FBM isolation C (crimping terminal) 4, 4H 1, 2
RH917XX (replacing P0917XX) 16 channels, no fuse, 15-60V dc (external supply), 2A max, FBM isolation C 4, 4H 1, 2
RH923LL (replacing P0923LL) 16 channel, SPDT relay (with LED),<30V DC 5A/125V DC 600mA (resistive)/240mA (inductive)/250V AC 5A, TA relay isolation C 4 5
RH926BE (replacing P0926BE) 16 channel, solid-state switch (with fuse), 125V ac/125V dc 2A max, TA isolated Knife (blade terminal) 4 5
Cable and certification related
(1) Terminal cable
Specification: 37 pin male D-subminiature interface, with a maximum length of 30m (98ft), made of polyurethane or low smoke halogen-free (LSZH) material, divided into Type 4 and Type 4H types (Type 4H is suitable for>5m long distance wiring to reduce voltage drop).
Partial cable models: 0.5m Type 4 RH916FG, 10m Type 4H RH916GE, 30m LSZH RH928BK, etc. (refer to Table 2 for details).
(2) Certification compliance
Electromagnetic compatibility (EMC): Complies with the EU EMC Directive 2004/108/EC (before April 20, 2016), 2014/30/EU (after April 20, 2016), and meets the EN61326-1:2013 Class A emission and industrial immunity levels.
Environmental compliance: Compliant with the EU RoHS Directive 2011/65/EU.
Safety certification: UL/UL-C certification, applicable to Class I A-D Group 2 T4 temperature code enclosure systems; DEMKO certified Ex nA IIC T4, suitable for Zone 2 hazardous environments; Classification certification (ABS type approval, French Classification Society EC31 environmental category certification).
TA certification type description: Type 1 (UL/UL-C Class I A-D Group 2 Zone T4, DEMKO Ex nA IIC T4), Type 2 (UL/UL-C associated equipment, DEMKO Zone 2 IIC associated equipment, Class 2 limited energy), Type 4 (Class 2 limited energy), Type 5 (only applicable to ordinary non hazardous locations).
Email:wang@kongjiangauto.com