(2) Regular maintenance (by cycle)
Maintenance project cycle operation requirements
Check the blade wear of the cooling fan after running for 20000 hours or 10 years, replace it with a fan of the same model, and reset the parameter o4-03
Measure the capacitance of the main circuit capacitor after 5-7 years of operation. If it is lower than 80% of the initial value, it needs to be replaced. Monitor the lifespan through U4-05
Check the torque of the main and control circuit terminals every 6 months to prevent looseness and heating during terminal tightening
Clean the radiator with compressed air every 3 months after power failure to avoid clogging the air duct
3. Maintain monitoring function
Parameters U4 series: U4-03 (fan running time), U4-04 (fan life percentage), U4-05 (capacitor life percentage), U4-06 (soft charging relay life). If it is less than 20%, it needs to be replaced in advance.
Peripheral equipment and communication configuration
1. Standard configuration and peripheral equipment
Required equipment: power coordination reactor, current suppression reactor, fuse (model needs to be matched according to the model);
Optional devices: 24V power supply (PS-A10LB/HB), USB replication unit (JVOP-181), LED operator (JVOP-182), communication tab (MECHATROLINK-II, CC Link, etc.).
2. MEMOBU/Modbus communication configuration
Communication parameters:
H5-01 (slave address): 0~FFH, default 1FH, ensure unique address;
H5-02 (baud rate): 0 (1200bps)~8 (115200bps), default 3 (9600bps);
H5-03 (checksum): 0 (no checksum), 1 (even checksum), 2 (odd checksum), default 0.
Communication function: Supports reading monitoring data, writing parameters, controlling operation/stop, fault reset, and can be remotely controlled through PLC or upper computer.