Welcome to the Industrial Automation website!

NameDescriptionContent
HONG  KANG
E-mail  
Password  
  
Forgot password?
  Register
当前位置:

Watlow Series 93 Controller

来源: | 作者:FAN | 发布时间 :2025-11-10 | 32 次浏览: | Share:

Watlow Series 93 Controller

Product Core Information

The Watlow Series 93 is a 1/16 DIN microprocessor based temperature controller with a single input dual output design. It supports J, K, T, N, S-type thermocouples, RTDs, or process signal (0-5V DC, 4-20mA) inputs, and outputs can be configured for heating, cooling, alarm, or shutdown functions. It has both PID and switch control modes and is suitable for industrial temperature control scenarios. The product complies with ISO 9001 standards, has an IP65 (NEMA 4X) protection level (optional), supports CE certification, provides a 3-year warranty, and is equipped with dual four digit red or green display screens by default, making it easy to operate.


Core functions and technical details

(1) Control mode and algorithm

PID control

Proportional band (Pb): The range can be set to 0-555 ° C (or ° F/unit), and it automatically switches to switch control when Pb=0; Under the SI unit, it is displayed in "% range" (0.0-999.9%), with a default value of 3%. The smaller the value, the higher the control sensitivity.

Integral/Reset (It/rE): Integral time 0.1-99.9 minutes/time (SI), reset frequency 0.01-99.9 times/minute (US), default 0, used to eliminate static deviation (droop) and avoid deviation from the set value after temperature stabilization.

Differential/Rate (dE/rA): 0.01-99.9 minutes, default 0, suppresses overshoot by predicting temperature trends, suitable for thermal systems with fast heating rates and high inertia.

Cycle time (Ct): 0.1-999.9 seconds, default 5 seconds. It is recommended to extend the cycle for mechanical relays to reduce contact wear, while solid-state relays can shorten the cycle to improve control accuracy.

Self tuning function

Trigger method: Set the [AUt] parameter in the operation menu (0=off, 1=slow, 2=medium, 3=fast), press the forward button to start, and after starting, the lower display screen will alternate between "[AUt]" and the current parameter.

Working principle: Based on 90% of the set value, the system's thermal characteristics are "learned" through 4 cross temperature points, and the optimal PID parameters are automatically calculated; If 4 crosses are not completed within 80 minutes, automatically exit and maintain the original parameters.

Applicable scenarios: Slow mode is suitable for scenarios where heating is slow and overshoot is not allowed (such as laboratory reactors), while fast mode is suitable for industrial heating furnaces and other scenarios where the set value needs to be quickly reached.

switch control

When the PID proportional band is set to 0, it is enabled, and the switching difference is defined by the [` HSC] parameter (1-55 ° C/1-99 ° F, default 2 ° C/3 ° F). When the temperature is below the set value - difference, the output is turned on, and when it is above the set value+difference, the output is turned off. It is suitable for scenarios with low control accuracy requirements (such as warehouse insulation).

(2) Alarm and safety functions

Alarm type configuration

**Process alarm ([PrA]/[Pr]) * *: Based on absolute temperature triggering, [ALO] (low alarm threshold, default range low limit) and [AHI] (high alarm threshold, default range high limit) need to be set in the operation menu. [PrA] will flash the alarm information, and [Pr] will only trigger the output without display.

**Deviation alarm (dEA/dE) * *: triggered based on the deviation of the set value, [ALO] range -999-0 (deviation below the set value), [AHI] range 0-999 (deviation above the set value), the alarm threshold automatically follows when the set value changes (e.g. set value of 100 ° F, deviation+7 ° F, alarm trigger point is 107 ° F).

Alarm auxiliary function

**Locked ([LAt]) * *: [LAt] (locked) needs to be manually cleared by pressing the infinite key, [` nLA] (non locked) will automatically clear when the temperature returns to the safe range, default is non locked.

**Silent (SIL) * *: Only deviation alarm is supported. When set to "On", press the infinite key to activate the alarm output when powered on. Even if the temperature exceeds the difference after activation, the alarm output will remain closed until the temperature returns to the safe range and the triggering ability is restored.

Hysteresis (HSA): 1-5555 ° C (or ° F/unit), default 2 ° C/3 ° F, to avoid frequent alarms caused by temperature fluctuations near the alarm threshold (e.g. alarm threshold of 100 ° C, hysteresis of 2 ° C, temperature drops below 98 ° C before the alarm is released).

(3) Auxiliary control function

Slope heating (rP)

Supports two modes: [Str] (only slopes from the current temperature to the set value when powered on), [On] (also slopes when the set value changes), with a ramp rate range of 0-9999 °/hour (default 100 °/hour), and the lower display screen alternately flashes "rP" and the target set value during the ramp process.

Applicable scenarios: To avoid damage to heating elements due to instantaneous high temperatures (such as glass melting furnaces), and to prevent deformation of workpieces due to excessive temperature differences (such as metal heat treatment).

Power Limit ([PL])

Only heating output is available, with a range of 0-100% (default 100%), limiting the maximum power of heating output to avoid load overload (such as when a small heater is adapted to a high-power controller, power should be limited to prevent burnout).

Calibration offset (CAL)

Range ± 100 ° C/± 180 ° F (or ± 180 units), default 0, used to compensate for measurement deviations caused by sensor installation errors or environmental interference (if the sensor is installed in a heat dissipation area and the actual temperature is 5 ° C higher than the measured value, a+5 ° C offset can be set).

Automatic/manual undisturbed switching

Switching mode: Press the infinite key twice to enter manual mode, the percentage indicator light remains on, and the lower display screen shows the output power (-100% to 100%, negative sign represents cooling); Press the infinite key again to return to automatic mode.

Non disruptive logic: When switching from automatic to manual mode, the output power remains at the PID calculated value before switching; When manually switching to automatic mode, transition to PID control starting from the current manual power to avoid sudden temperature changes.

Sensor fault handling: When the lock level [LOC] is 0/1/2, the sensor will automatically switch to manual mode after an open circuit (maintain the power before the fault, set to 0% if the power is unstable); Directly turn off the output at level 3/4.

image.png

Installation and wiring specifications

(1) Installation process

Panel preparation: Cut according to the size of 44.96-45.47mm (width x height). It is recommended to use Greenlee 60287 type 1/16 DIN punch, with a panel thickness of 1.5-9.7mm. When installing multiple units, the distance between adjacent cuts should be ≥ 20mm (to avoid heat dissipation interference).

Sealed installation (IP65 model):

Confirm that the housing gasket (circular with rounded corners) is facing the panel, without distortion or damage, and is embedded in the groove of the housing frame.

Insert the controller into the incision, press the panel side shell, insert the installation ring from the back, ensure that the installation ring buckle is aligned with the shell protrusion, press the buckle with your thumb until you hear a "click" sound, and check that the distance between the panel and the shell is ≤ 0.483mm (ensure sealing).

Dismantling method: Use a thin screwdriver or putty knife to gently pry open the 6 buckles of the installation ring, detach them one by one, and then shake the installation ring back and forth to remove it, avoiding pulling and damaging the shell with force.

(2) Wiring Details

Power wiring

High voltage type (93_ -1 0-00): Terminal 11 is connected to L1 (100-240V AC, actually compatible with 85-264V), terminal 12 is connected to L2, built-in 1A slow melting fuse (250V), cannot be replaced with fast melting fuse.

Low voltage type (93_ -1 1-00 _): Terminal 11 is connected to positive (12-24V AC/DC, actually compatible with 10-26V), terminal 12 is connected to negative, with built-in 2A slow melting fuse. It is strictly prohibited to connect high voltage (which may cause irreversible damage).

Input wiring

Thermocouple: Terminal 3 is connected to the positive pole (if the red color of the J-type thermocouple is negative, pay attention to the polarity), terminal 5 is connected to the negative pole, and the extension wire should be made of the same material as the thermocouple (if the J-type thermocouple uses iron constantan material) to avoid errors; If the external device is not isolated, an isolated thermocouple should be used.

3-wire RTD: Terminal 2 is connected to S1, Terminal 3 is connected to S2, and Terminal 5 is connected to S3. The three leads must have the same specifications (same wire diameter and length), and the total lead resistance should be ≤ 20 Ω to avoid measurement errors caused by resistance differences; 2-wire RTD requires short circuiting terminals 3 and 5, resulting in low accuracy (+2 ° F error per 1 Ω lead resistance).

4-20mA signal: Terminal 2 is connected to the negative pole, terminal 5 is connected to the positive pole, and the input impedance is 5 Ω. It is necessary to ensure that the signal source and controller are grounded together to avoid grounding loops.

Output wiring

Mechanical relay (Output 1: Terminals 8/9/10): Terminal 8 is normally closed (NC), 9 is common terminal (COM), 10 is normally open (NO), maximum load 5A@240V Communication, inductive loads (such as relay coils) require parallel RC suppressors (Watlow 0804-0147-0000), minimum load 100mA@5V DC (to avoid contact oxidation).

4-20mA output (Output 1: Terminal 9/10): Terminal 9 is connected to the positive pole and 10 to the negative pole, with a maximum load impedance of 800 Ω. It is used to control actuators such as frequency converters and valves. Shielded wire is required for wiring, and the shielding layer is grounded at one end (controller end).

Safety Specifications

All wiring must comply with NEC and local electrical standards, with wire diameter of 20-14AWG and terminal torque of 1.4Nm (12in lb), to avoid poor contact caused by looseness and damage to terminals caused by tightness.

Disassembling the controller after power failure may result in residual voltage at the casing terminals, and insulated gloves should be worn during operation; When installing in high temperature environments, insulation pads should be added between the controller and the heat source to avoid ambient temperatures exceeding 65 ° C (rated operating limit).

image.png

Menu Configuration and Operation Guide

(1) Menu Structure

Menu Type Entry Method Core Parameter Function Description

Long press the up and down arrow keys for 3 seconds in the Setup menu, and the lower display will show "['LOC]" [LOC] [Lock Level], [In] (Input Type), [rL]/[rH] (Range), [Ot1]/[Ot2] (Output Mode), [HSC] (Switch Difference), [LAt] (Alarm Lockout). Configure the controller hardware logic, input and output basic parameters, and some parameters (such as [In]) will be reset to factory default values after modification

Press the forward button in the Operation menu to display parameters [Pb1]/[Pb2] (proportional band), [It1]/[rE1] (integral/reset), [dE1]/[rA1] (differential/rate), [ALO]/[AHI] (alarm threshold), [AUT] (self-tuning), [CAL] (calibration offset) in sequence. Real time adjustment of control parameters, start self-tuning, set alarm threshold, and automatically save 5 seconds after parameter modification

Calibration menu: Long press the up and down arrow keys from the settings menu. The lower part displays "[CAL]", and the upper part is set to "[YES]". [000] (0mV input calibration), [500] (50mV input calibration), [440] (44.01 Ω RTD calibration), [rSt] (factory calibration restored). To calibrate the input/output accuracy, professional equipment (such as precision millivolt sources, resistance boxes) is required. The output is turned off during calibration

(2) Key parameter configuration steps

Input type configuration

Open the controller chassis (press the buckles on both sides of the panel to remove it), and set the left DIP switch (8 positions) according to the input type: set the thermocouple to "O N", the RTD to "N O", and the process signal to "O O" (refer to Figure 4.1b for details).

Enter the settings menu and set the [In] parameter (such as setting the J-type thermocouple to "[J]" and the 100 Ω RTD to "[rtd]"), ensuring consistency with the DIP switch, otherwise an error of "[Er7]" will be displayed.

PID parameter self-tuning

Enter the operation menu, set [AUt] to 2 (medium response), press the forward button to start, the controller enters switch control mode (output full power), and starts "learning" when the temperature approaches 90% of the set value.

After self-tuning is completed, [AUt] automatically resets to 0, and the PID parameters ([Pb1]/[It1]/[dE1]) are updated to their optimal values. If manual fine-tuning is required, it can be modified in the operation menu.

Alarm configuration (deviation alarm as an example)

Setting menu: [Ot2] set to "[dEA]" (with display), [SIL] set to "[` On]" (mute enabled), [HSA `] set to "5" (5 ° C lag).

Operation menu: Set [ALO] to "-10" (alarm for temperatures below the set value of 10 ° C), set [AHI] to "+10" (alarm for temperatures above the set value of 10 ° C), lower will flash "[LO]"/"[HI]" when the temperature exceeds the set value, press the infinite key to clear.

(3) Display and button operation

Display screen function

Upper display screen: default display process value (PV), parameter value is displayed during parameter configuration, "[---]" is displayed when the sensor fails, and an error code (such as "[Er7]") is displayed when the infinite key is pressed twice.

Lower display screen: By default, the set value (SP) is displayed. When configuring parameters, the parameter name (such as "[Pb1]") is displayed. When an alarm is triggered, the alarm type flashes. In manual mode, the output power (such as "50%") is displayed.

Indicator lights: Output 1/2 indicator light (red) on indicates output activation, percentage indicator light (green) constantly on indicates manual mode, flashing indicates mode to be switched.

Shortcut key operation

Return to default display: Press and hold the infinite key for 2 seconds, regardless of the current menu, directly return to PV/SP display.

Clear alarm: After the alarm is triggered, press the infinite key once to clear the locking alarm (the temperature needs to return to the safe range).

Quickly enter the settings menu: Long press the up and down arrow keys on any interface for 3 seconds to directly enter the [LOC] parameter.


Troubleshooting and Maintenance

(1) Common Error Handling

Steps for handling error code reasons

[Er2] RTD input below -200 ° C (or sensor failure) 1. Check if the RTD wiring is loose or broken; 2. Measure the RTD resistance with a multimeter and confirm that it is within the normal range (such as 100 Ω at 0 ° C); 3. If the resistance is normal, enter the calibration menu to perform RTD calibration

[Er4] microprocessor configuration error 1. Power off and restart, observe if it is restored; 2. If it repeatedly occurs, contact Watlow technical support (provide model and fault frequency); 3. Chassis cannot be disassembled by oneself to avoid warranty expiration

[Er5] Non volatile memory verification error: 1. Power off and restart after 30 seconds to eliminate transient interference; 2. Enter the calibration menu and execute [rSt] (restore factory calibration); 3. If it is ineffective, it needs to be returned to the factory for repair (memory damage)

[Er6]/[Er7] Analog to digital conversion undercurrent/overflow (sensor open circuit, polarity reversed) 1. Check sensor wiring: thermocouple confirms polarity, RTD confirms lead resistance, process signal confirms signal source; After replacing the sensor, press the forward button to clear the error; 3. If the wiring is normal, check if the DIP switch matches the In parameter

(2) Daily maintenance

regular maintenance

Check monthly whether the wiring terminals are loose (especially in vibration environments), whether the sealing gasket is aging (IP65 model), and whether the sensor probe is scaled (affecting temperature measurement accuracy).

Calibrate once every quarter: Use a precision temperature source (such as a dry furnace) to simulate the standard temperature. If the measurement deviation exceeds ± 1 ° C, enter the calibration menu to adjust the [CAL] parameter (if the actual temperature is 200 ° C, it displays 198 ° C and is set to+2 ° C).

image.png

  • ABB FAZ-C2/2-DC Circuit Breaker
  • ABB FAZ-XHIN11 auxiliary contact equipment
  • ABB Z-NTS neutral wire circuit breaker
  • ABB M3V4-1/0-0 64122088 Input/Output Module
  • ABB NDBU-95C 64008366D control module
  • ABB LWN2660-6EG Automation Control Module
  • ABB LWN2660-6E power supply
  • ABB FPX86-9377-A capacitor
  • ABB MR627 P89627-0-2333400-300-401-601-701 Motor Control Unit
  • ABB 57619414 A 1/2 connector module
  • ABB 57619414 A 2/2 connector module
  • ABB LDMTR-01 63940135F Input/Output (I/O) Module
  • ABB LDSTA-01 63940143B Input/Output (I/O) Module
  • ABB CRBX01 2VAA008424R1 Remote Bus Expander
  • ABB UNITRAL1010 3BHE035301R1002 UNS 0121A-Z, V1 high-performance excitation controller
  • ABB UNITRAL1010 3BHE035301R0001 UNS 0121 A-Z, V1 brushless excitation system
  • ABB CHBX01R 2VAA008575R1 Compact Bus Expander
  • ABB CHBX01L 2VAA008574R1 Bus Expander
  • ABB RMU610 2VAA008425R1 redundant communication module
  • ABB 3BUS208796-501 Communication Module
  • ABB 128057-204 086345-504 multifunctional module
  • ABB HIEE205014R1 HI220856-312/20 UNC4673AV1 redundant controller
  • ABB PP882 3BSE069275R1 Control Panel
  • ABB AC800M PM891 3BSE053240R1 Controller Module
  • ABB AC900F PM904F 3BDH0001002R0001 Controller
  • ABB P8151B communication interface module
  • ABB P8403C controller module
  • ABB P8431 controller module
  • ABB Y129740-002 Analog Module
  • ABB PFTL201D 100KN 3BSE008922R0100 Tension Sensor
  • ABB PPD117A3011 3BHE030410R3011 Excitation Controller
  • ABB PPD512A10-454000 3BHE040375R103E Static Excitation System Unit Module
  • ABB 3BHE046836R0101 GFD563A101 Interface Module
  • ABB 3BHE023784R2530 PPD113B01-25-111000 Controller Module
  • ABB PFCL201CE 50KN 3BSX802939-108 Tension Controller
  • ABB LS4000 diode laser analyzer
  • ABB REM615 HBMBCCAHNB1NN1XD Motor Protection Control
  • ABB 3BHE017628R0002 PPD115A02 SG579989013 Controller Module
  • ABB G2000A5.7ST human-machine interface
  • ABB DKTFM418B 3BHB015651P0001 Controller
  • ABB 3BHE039724R0C3D PPD513 A0C-100440 AC800PEC Controller
  • ABB PPD513AOC -100440 3BHE039724R0C3D 800 D513 Integrated Gate Commutator Transistor (IGCT)
  • ABB XUD194 XUD194A 3BHC018137R0001 Controller Unit Module
  • ABB UDC920BE01 3BHE034863R0001 High Voltage Inverter
  • ABB PPD517A3011 3BHE041576R3011 Excitation Controller
  • ABB MT-91-ARC FP A Control Panel
  • ABB UAC383AE01 HIEE3008900001 interface module
  • ABB XVC722AE101 3BHB002751R0101 High Performance Industrial Control Module
  • ABB TB820V2 3BSE013208R1 Modulebus Cluster Modem
  • ABB 3BHE003604R0102 UFC765AE102 circuit board
  • ABB SPSED01 High-Performance SOE DI Module
  • ABB GFD233A103 3BHE02294R0103 multifunctional control machine
  • ABB DO810 3BSE008510R1 Digital Output Module
  • ABB PM866A 3BSE076359R1 Process Controller
  • GE P111-6053 Advanced Microcontroller
  • GE SPU232.1-CAN PART NO: 029.354 630. Industrial grade module
  • ALSTOM VCM 232.2 029.359 088 VME-MANAGER-MASTER 0085.022.99
  • ALSTOM Centrol Unit COP 232.2 029.232 446
  • ABB PPD539A102 3BHE039770R0102 Control System Module
  • ABB UFC921A101 3BHE024855R0101 Digital Control Module
  • ABB UFC911B106 3BHE037864R0106 Voltage Measurement Board
  • ABB 5SHY4045L0006 3BHB030310R0001 IGCT module
  • ABB HIEE300024R4 UAA326A04 control module
  • ABB PPC905AE101 3BHE014070R010 Controller Module
  • ABB CDP-312R CONTROL PANEL
  • ABB TPPB-02 Control Processor Module
  • ABB UFC762AE101 3BHE006412R0101 motor control interface
  • ABB 1TGE120020R0614 industrial control module
  • ABB UFC760BE145 3BHE004573R0145 High-Voltage Interface Board
  • ABB XVC768116 3BHB007211R116 Programmable Controller
  • ABB XVC767AE105 3BHB007209R0105 Current Monitoring Board
  • ABB PCS6000 VLM70 3BHE034262R0001 Medium-Voltage Converter Module
  • ABB FPX86-9364-A controller motherboard
  • ABB FPX86-9345-B 3BHL000986P0006 Controller Module
  • ABB S-053M 3BHB012897R0003 Phase controller module
  • ABB 3BHE05077R0102 UNS0881b-PV2 control board
  • ABB VIPA972-0DP01 bus connector
  • ABB HS810 3BDH000305R0101 Controller Module
  • ABB PF900-NR 3BDH000357 power module
  • ABB 3BHB005245R0101 power board
  • ABB SUE3000 1VCR007346 G0032 Synchronous Motor Exciter
  • ABB SUE3000 1VCR007346 G0028 High speed Transmission Equipment
  • ABB UFC921A 3BHE024856P106 Communication Module
  • ABB GMKP2800-32IBY Communication Module
  • ABB PS203PRESSPMPPS Intelligent Control Module
  • ABB UNS4681V511 3BHE004074R0511 Expansion Unit Module
  • ABB PFTL101B 10KN 3BSE004197R1 high-performance weighing sensor
  • ABB CI532V02 3BSE003B27R1 Communication Module
  • ABB COM0034 control module
  • ABB 216VC626/P1000 HESG324442R112 processor unit relay card
  • ABB 216MB66 HESG324510M1 PLC Memory Expansion Module
  • ABB SPAJ140C overcurrent and ground fault relay
  • ABB DI840 3BSE020836R1 Digital Input Module
  • ABB AI845 3BSE023675R1 Analog Input Module
  • ABB B5LA HENF327886R0001 DC power module
  • ABB P7LA HNEF105323R0002 High Performance Control Module
  • ABB PPC322AEV01 HIEE300697R1 excitation control board
  • ABB REF620C_F NCFNAAAAABC2DNN1XF Feeder Protection and Control
  • ABB P72140-4-0788740 CTI21-P Input/Output Module
  • ABB DYTP123A 61430001-TW Ethernet Connection Module
  • ABB DYSF118B 61430001-XG Communication Interface Module
  • ABB DYPS154C 61430001-YP Serial Communication Module
  • ABB DTCC901B 61430001-FU Ethernet Communication Module
  • ABB SB510 3BSE000861R1 Backup Power Supply 110/230V AC
  • ABB CI535V26 3BSE022161R1 Communication Interface Module
  • ABB RAO02 redundant analog output module
  • ABB RAI02J redundant analog input module
  • ABB 1MRK002133-ABr02 analog-to-digital module
  • ABB UNITRAL1010 3BHE035301R0004 voltage regulator
  • ABB 3BHB019265R0410 Analog Input/Output (I/O) Module
  • ABB UNC4672AV1 HIEE205012R1 multi-functional input/output analog module
  • ABB REC650 1MRK008514-CB multifunctional circuit breaker
  • ABB RER 103 bus connection module
  • ABB REF545KB133AAAA High Performance Protection Relay
  • ABB REC670 1MRK002814-AC High-Performance Relay Module
  • ABB DASD001 3ASC25H241 Industrial Digital Input Module
  • ABB RED670 touchpad film
  • ABB NTAC-02 fiber optic cable
  • ABB XVC768AE102 3BHB007211R0102 Analog Input Module
  • ABB AD02 multi-channel integrated I/O module
  • ABB TU842 3BSE020850R1 module terminal unit
  • ABB APBU-44C 64669982 High Performance Controller Module
  • ABB REM611 panel
  • ABB RED615 panel
  • ABB L003748-AR 3BSX108237R300 Voltage Regulating Control Module
  • ABB COM0034 2RCA023019A0004C control module
  • ABB REU615E-D HBUAEAADNCA1BNN1XD Voltage Protection and Control Relay
  • ABB S-113H 3BHB01808R0003 Hydraulic Control Module