The Eaton HMCP400W5C is a magnetic-only motor circuit protector (MCP) designed for motor branch circuit protection in industrial applications. As part of the Series C product family, this 400 ampere, three-pole device provides reliable instantaneous short-circuit protection while allowing the motor starting current to pass without nuisance tripping. The HMCP is intended to be used in combination with a separate overload relay and contactor to form a complete motor starter, meeting NEC requirements for coordinated motor protection.
Current rating: 400 A continuous
Voltage rating: 600 VAC / 250 VDC maximum
Number of poles: 3-pole configuration with common trip
Frame size: J-K frame, Series C design
Adjustable magnetic trip range: 1250-2500 A (field adjustable)
Magnetic-only trip mechanism – no thermal overload element
Terminal connections: Line and load terminals (non-aluminum compatible)
Compact dimensions: 10.13" height x 4.1" length x 5.5" width
UL489 listed as a motor circuit protector (MCP)
Frame type: HMCP400, Series C
Interrupting capacity: Suitable for motor branch circuits (refer to UL489 ratings)
Magnetic trip adjustment: Field adjustable via external dial
Maximum system voltage: 600 VAC, 50/60 Hz; 250 VDC
Terminal material: Non-aluminum (copper only)
Mounting: Panel mount with screw terminals
Weight: 11.5 lb (approximately 5.2 kg)
Operating temperature: Standard industrial range
UPC: 786679150962
The HMCP400W5C contains a solenoid mechanism that reacts to high fault currents. When the current exceeds the magnetic trip setting, the solenoid pulls in and trips the breaker instantaneously, disconnecting the circuit. Because it has no thermal element, it will not trip on overloads; this function is delegated to an external overload relay. This separation allows precise coordination between short-circuit protection and overload protection, with the magnetic trip range adjustable from 1250 to 2500 amperes to accommodate different motor sizes and starting characteristics.

Individual motor branch circuits in industrial control panels
Motor control centers (MCCs) with separate overload relays
Compressor, pump, and fan starters
HVAC equipment requiring high fault current ratings
Any application requiring magnetic-only short-circuit protection
The HMCP is typically mounted directly upstream of a contactor. The magnetic trip setting must be selected to allow the motor's locked rotor current (typically 6-8x FLA) to flow without tripping, yet trip on higher short-circuit currents. The J-K frame design ensures compatibility with standard panel layouts, and the line/load terminals accept copper conductors for secure connections. Coordination with upstream feeders can be achieved by selecting appropriate trip settings.
The Eaton HMCP400W5C is a reliable, code-compliant solution for protecting motor circuits against short circuits while maintaining flexibility in overload protection selection.