Both modules are PROFIBUS-DP interface devices with "4-channel digital output+8-channel digital input". The core difference lies in the explosion-proof level of the output terminal. The specific comparison is as follows:
Comparison item model 07-7331-2305/000 model 07-7331-2305/1000
Output explosion-proof level Ex e (increased safety type) Ex i (intrinsic safety type)
Output voltage U2-0.2V (approximately 23.8V when U2 is 24V) DC 22V (when U2 ≥ 24V)
Single channel maximum output current 500mA-
Single channel internal resistance -301 Ω
Module loss power maximum 3.5W maximum 4.5W
Control object: 4-channel Ex e valve, 4-channel Ex i valve
3. Maintenance and disposal
Maintenance: No maintenance is required under normal use, and regular inspections by electricians are required according to EN/IEC 60079-17/19;
Repair: Self repair is prohibited, please contact BARTEC GmbH;
Disposal: Belonging to B2B equipment under the WEEE directive, it needs to be disposed of in accordance with local regulations and can be returned to BARTEC (with shipping costs borne by the sender), WEEE number DE 95940350.