RTD module 8 Pt100/Pt200/Ni120 2/3/4 wire system, excitation current 100 μ A, Pt100 measurement range -200~850 ℃, accuracy ± 0.5 ℃ (25 ℃)
Thermocouple/mV module 8 B/E/J/K/N/R/S/T type thermocouple, mV signal cold end compensation ± 1 ℃, mV range -100~100mV, accuracy ± 0.1mV (25 ℃)
Isolation type AI module 4 thermocouples/mV/V/RTD channel optical isolation 1500V DC, supports wide range voltage signals (0-5V/0-10V, etc.), and improves accuracy (such as E-type thermocouples ± 0.5 ℃)
(2) Analog Output (AO) Module
Module type, channel number, signal type, key parameters
AO 4-20mA HART 8 4-20mA resolution 14 bits, -40~60 ℃ accuracy 0.25% range, channel optical isolation 1500V DC, supports open circuit detection (<0.7mA)
AO Plus 4-20mA HART 16 4-20mA resolution 14 bits, accuracy 0.25% range, channel optical isolation 1000V DC, supports Mass terminal block, maximum on-site power supply 400mA@24V DC
(3) Discrete Input (DI) module
Module type, channel number, signal type, key parameters
DI 24V DC dry contact 8 dry contact (compatible with NAMUR sensor) with conductivity detection>2.2mA, shutdown<1mA, input impedance 5k Ω, channel optical isolation 1500V DC
DI Plus 24V DC dry contact 32 24V DC dry contact conductivity detection>2mA, shutdown<0.25mA, supports terminal fault detection (requires Mass terminal block), on-site power supply 150mA@24V DC
Pulse Counting Input (PCI) 4 24V DC frequency range 0.1Hz~50kHz, minimum pulse width 10 μ s, 32-bit unsigned counter, channel optically isolated 1500V DC
Sequence of Events (SOE) input 16 24V DC dry contact channel scan rate 0.25ms/16 channels, timestamp accuracy ± 0.25ms (single card)/± 1ms (single controller), supports event logging
DI 120V AC isolation type 8 120V AC conduction detection 84~130V AC, turn off 0~34V AC, input impedance 60k Ω, channel to channel optical isolation 250V AC
(4) Discrete Output (DO) module
Module type, channel number, signal type, key parameters
DO 24V DC high side 8 24V DC maximum 1A continuous output per channel (surge 4A<100ms), turn off leakage<1.2mA, channel optical isolation 1500V DC
DO Plus 24V DC high side 32 24V DC output of 100mA per channel, cut-off leakage<0.1mA, supports terminal fault detection, on-site power supply 3.2A@24V DC
DO 120/230V AC isolation type 8 120/230V AC maximum 1A continuous output per channel (surge 5A<100ms), turn off leakage 2mA (120V AC)/4mA (230V AC), channel to channel optical isolation 250V AC

Terminal block and system compatibility
1. Terminal block type and adaptation
Terminal blocks are divided into standard terminal blocks, fuse terminal blocks, redundant terminal blocks, and Mass terminal blocks. Different I/O modules require dedicated terminal blocks, and the core adaptation relationship is as follows:
Example features of terminal block type adaptation module
8-channel standard terminal block, 8-channel AI/AO, 8-channel DI/DO basic wiring, supporting single-mode installation
8-channel fuse terminal block. All 8-channel modules are equipped with 2A fuses to protect the on-site circuit
Redundant 8-channel terminal block with 8-channel redundant AI/AO and DI/DO supports parallel installation of 2 modules to achieve redundant backup
Mass terminal block (16/24/40/48 pins) Plus series modules, some standard modules are compatible with S-series Mass connection solutions or third-party devices (such as Pepperl+Fuchs HiC safety barriers), optimizing on-site wiring
2. System compatibility requirements
Controller: SQ or SX series controllers are required, and V11.3.1 and above versions of the DeltaV system support S-series and M-series controllers running on the same network.
Software version: The Plus series modules (16 channel AI/AO, 32 channel DI/DO) require DeltaV v13.3 or higher.
Installation restrictions: only supports horizontal carriers, not compatible with vertical carriers; Vertical I/O applications require the use of CHARMS electronic grouping I/O.

Certification and Security Standards
International certification:
Electrical safety: CE (EN 61326-1), FM (3600/3611), CSA (C22.2 No.213/1010-1).
Explosion proof certification: ATEX(II 3G Ex ec IIC T4 Gc)、IECEx(II 3G Ex ec IIC T4 Gc)、FM/CSA Class I, Division 2(Groups A-D, T4)。
Classification certification: IACS E10, ABS design evaluation certificate, DNV marine certificate.
Safety design:
Isolation protection: All module channels are optically isolated from the system (1000~1500V DC), and some discrete module channels are additionally isolated from each other.
Fault alarm: Hardware faults (such as module failure, communication interruption, on-site wiring failure) automatically trigger system alarms, with logs recorded in the Event Chronicle, and support for real-time viewing of module status on the diagnostic interface.
Order
1. Core module ordering model (example)
Module Description Model Example
8-channel AI 4-20mA HART (with AI 8-channel terminal block) SE4003S2B1
16 channel AO Plus 4-20mA HART (with 48 pin Mass terminal block) SE4005S2B5
32 channel DI Plus 24V DC (with redundant 40 pin Mass terminal block) SE4081S2T2B7
8-channel DO 120/230V AC isolated type (with fuse terminal block) SE4002S2T1B2
Email:wang@kongjiangauto.com